Emerson E3 is a versatile system combining energy management and monitoring for various facility systems. It offers HVAC and lighting control, refrigeration monitoring, and energy consumption reporting. The E3 can reduce energy costs by optimizing HVAC and lighting operation, minimizing energy consumption during peak periods. It also provides alerts for issues requiring attention, helping maintain optimal store conditions.

Emerson E3 is a versatile system combining energy management and monitoring for various facility systems. It offers HVAC and lighting control, refrigeration monitoring, and energy consumption reporting. The E3 can reduce energy costs by optimizing HVAC and lighting operation, minimizing energy consumption during peak periods. It also provides alerts for issues requiring attention, helping maintain optimal store conditions.

E3 Supervisor Control
Quick Setup Guide
1
Contents
 TechnicalSpecications ...................................................................................................2
Wiring .............................................................................................................................2
 EthernetConnections ......................................................................................................3
E3 RS485 Wiring Guide Example ......................................................................................4
 DirectConnectInstructions ............................................................................................ 5
LoggingIntotheE3Controller ......................................................................................... 6
 HowtoChangetheIPAddress ......................................................................................... 7
 Method1:DirectConnect ...........................................................................................7
 Method2:USBPort ..................................................................................................... 8
Setup Wizard ..................................................................................................................8
 LocalizationScreen .....................................................................................................8
 SystemValuesScreen ..................................................................................................9
 NetworkSettingsScreen ............................................................................................. 10
2
The E3 (P/N 860-1300)isasystemthatcombinesenergymanagementwiththeabilitytomonitorvariousfacility
systemsandprovidealertswhenthereareissuesthatneedattention.ThissystemprovidesHVACcontrol,
RefrigerationSystemMonitoringandControl,aswellasLightingControl.Inaddition,theE3canmonitorand
reportenergyconsumptionandtakeactiontoreducetheenergydemandduringpeakperiods.Thiscanhavea
directimpactonutilitybillsbyreducingtotalenergycosts.E3ensuresthattheHVACandlightingsystemsare
onandoffattheappropriatetimes.Thisabilitytomonitorstoreconditionscanpotentiallyminimizeenergy
consumption.
*Operating Temperature -40°Fto113°F(-40°Cto45°C)
*Tested to UL60730-1 standard
Operating Humidity
Storage Humidity
5%-95%RHnon-condensingat90°F
5% - 100% RH
24 VAC 24VAC±20%,50/60Hz,Class2
Dimensions 12” L x 12.5” W x 3.75 H”
4 RS485 ports
COM1=RS485-COM2AandRS485-COM2B
COM2=RS485-COM6<ISOLATED>
COM3=<ISOLATED>RS485
COM4=RS485-COM4AandRS485-COM4B
2 Ethernet ports ETH0,ETH1
2 USB ports J2,J3
External Pollution Rating AllModels:PollutionDegree3
Rated Impulse Voltage 2500/4000V
Lithium Battery Marking Caution:Thecellusedinthisdevicemaypresentareorchemicalburnhazardifmistreated.
Donotdisassemble,heatabove212°F(100°C),orincinerate.
Technical Specifications
Wiring
1. ConnecttheRS485Communicationwiretotheterminalblockheadersasshown.TheCablesare
numbered1through4.
2. Connectthe2-pin7.5mmpowerconnectorandGroundwireasshownin“PIB Board Layout”illustration.
3. Connecttheotherendofthepowercabletooneofthe50VAP/N 640-0040transformers.
4. Plugthe50VA P/N 640-0040Transformersintoa120VACoutlet.
5. TurnthepowerswitchON(upposition).Theunitshouldbootuptothehomescreen.
6. Youcanlogintotheunitthersttimebyusingthebelowusernameandpasswordifneeded.
Username=user
Password=pass
7. Onceloggedinyouwillbepromptedtochangeyourpassword.
3
PIB Board Layout
Ethernet Connections
ETH 0isusedtoconnecttocorporateLAN.
ETH 1isdesignedtobeusedfordirectlyconnectingtoPIB,andlaptoporPCandnetworkdevices.
ThedefaultIPforETH 1is192.168.1.250.
ETH Ports
4
E3 RS485 Wiring Guide Example
ForE3SerialIONetconnections,connectthewhitewiretothepositiveterminalandtheblackwiretothe
negativeterminal.
For8ROandMultiFlexRS485IONetconnections,connectthewhitewiretothepositiveterminalandthe
blackwiretothenegativeterminal.
Connecttheshieldwiretoearth/chassisattheendoftheIONet(network)segment.Connecttheshieldwire
tothecenterterminal(0V)oftheIONetconnectorontheE3.
Fordaisy-chaincongurations,terminatedevicesatthebeginningandtheendofthenetworksegment.
Allotherdevicesinthenetworksegmentarenotterminated(terminationjumpersinthenot-terminated
position).
E3, MultiFlex, and 8RO Wiring Layout
E3 and XR75 Wiring
5
Direct Connect Instructions - Connect your Laptop to E3’s Ethernet
Port ETH1:
AllcongurationcanbeaccomplishedthroughtheE3’sbuilt-indisplayorthroughalaptop,PC,ortablet.Onyour
PC:
1. UnderControl Panel - Network and Sharing Center,selectChange adapter settings.
2. Select the Local Area Connectionportbeingused.
3. Select Properties.
4. HighlightthesectionInternet Protocol
Version 4 (TCP/IPv4) and click Properties:
5. Click Use the following IP address: and enter
the IP address 192.168.1.251 and the Subnet
mask 255.255.255.0 ofthePCbeingusedon
theLocalAreaNetworkordirectconnection
and click OK.
Change Apapter Settings
Highlight Internet Protocol Version 4 (TCP/IPv4)
IP Address and Subnet Mask
6
Logging Into the E3 Controller
1. LaunchapreferredWebbrowser:GoogleChrome105.0.5195andlater,Firefox105.0andlater,MAC
Safari14.1.2andlater,iOSSafari14.7andlater,MicrosoftEdge84.0.522andlater,andChrome/WebView
105.0.5195andlaterarethesupportedbrowsers.
2. EntertheIPAddressofthedevice.
3. EnteryourUsername/Password(defaultuser/pass) and click Login.Thenupdateyourpasswordtothe
minimumcomplexityrequirementsandclickSave.
Note that when directly connecting your laptop or PC to ETH1, enter the default IP into the browser address bar:
ETH1 Default IP Address is 192.168.1.250.
Update Password
Login Screen at Controller Startup
7
How to Change the IP Address
Method 1: Direct Connect
1. SelecttheMainMenuicon>Configure System >General System Properties>Network Settings:
2. On the INTERNET (TCP/IP)sectiononthescreen,entertheIPAddressintheETH 0 IP Addresseld.
Note that you can set up the Peer Group, Unit Number, Network Mask, and Default Gateway on this screen.
Method 2: USB Port
1. Createa“network.txt”withyourdesiredsettings(Enter IP Address in the ETH 0 IP Address Field):
2. Savetotherootfolderofathumbdrive.InsertthethumbdriveintotheUSBportofE3.
3. PowercycletheE3.ThenewIPAddresswillbesaved.
Network.txt Notepad
Enter IP Address in the ETH 0 IP Adress Feild
8
Setup Wizard
Note that if setpoints have been pre-loaded in the unit, the Setup Wizard will not auto-start after logging in.
IfyourunithasbeenreceiveddirectlyfromtheEmersonfactory,theSetupWizardwillopenandtakeyouthrough
thefollowingsetupscreens:
Localization Screen
SettheE3’slocalizationdatasuchaslanguage,dateandtimeformats,andengineeringunitsfromtheLocalization
screen.
Language:ThedefaultforthelanguageselectionisAmericanEnglish(UnitedStates).Thesystemstoresasetting
forthepreferredsystemlanguage(internallanguagecode).Thedefaultlanguageisusedwhennouseriscurrently
loggedintotheE3orwhenthecurrentlyactivepreferredlanguagedoesnothaveatranslationforagivenlabel,
prompt,ordisplaytext.
Date:TheDateformatcanbesettoeitherDay,Month,andfullYear(D-M-YR)orMonth-DayandfullYear(M-D-YR)
format.Theday,month,andyearvaluesareseparatedbyeitheraforwardslashoradashlinedependingonuser
selection.
TheDateFormatcanbechangedbasedonuserpreferenceandsavedtouserproles.OninitialE3startup,theDate
formatdefaultstotheformatofthelanguageselected.Forexample,en-USwilldefaulttoD-M-YRandallothers
willdefaulttoM-D-YR.
Time: TheTimeformatcanbesettoeithera12-hour(12-hr)formator24-hour(24-hr)format.Thehour,minute,
andsecondvaluesareseparatedbyeitheracolonoraperioddependingonuserselection.
TheTimeformatcanbechangedbasedonuserpreferenceandsavedtouserproles.OninitialE3startup,the
Timeformatdefaultstotheformatofthelanguageselected.
DateandTimedelimitersdefaulttoforwardslashesandcolons.
Engineering Units:Thedefaultengineeringunitsarebasedontheassignedunitsforthechosenpreferred
language.Userscanchooseorchangetheirpreferredsetofengineeringunitsandsavethemtotheiruserproles.
ThedefaultengineeringunitsarebasedontheInternationalSystemofUnits(SISystem)format.
SetthesystemlanguagetypeintheLanguagedrop-downmenu.Clicktherightarrow>tosaveandproceedto
theSystemValuesscreen.
Localization Screen
9
System Values Screen
FromtheSystemValuesscreen,nametheunitbyenteringitintheSite Nameeld.TheConrmationwindowwill
slideopen.ClickOK.Thenclicktherightarrow>toproceedtotheNetworkSettingsScreen.
Network Settings Screen
CongurethesettingsontheInternetTCP/IPscreensuchashostname,text,andemailsettings.Ifyouhave
Internetaccess,enterthe IP Subnet Mask and Default Gatewaysettings(seeyourITAdministrator).Ifconnecting
directlytoalaptop,usetheDefaultIPandleavetheDHCPsettoDisable.Fortextmessaging,enabletheSMS
settingandusetheSMTPaddress(seeyourITAdministrator).Clickthearrow>tosaveandnishtheSetupWizard.
Network Settings
System Values Screen
NOTES
11
Climate.Emerson.com
026-4167Rev6
EmersonisatrademarkofEmersonElectricCo.oroneofitsafliatedcompanies.©2023EmersonDigitalColdChain,Inc.Allrightsreserved.
Thecontentsofthispublicationarepresentedforinformationalpurposesonlyandtheyarenottobeconstruedaswarranties
orguarantees,expressorimplied,regardingtheproductsorservicesdescribedhereinortheiruseorapplicability.Emerson
reservestherighttomodifythedesignsorspecicationsofsuchproductsatanytimewithoutnotice.Responsibilityforproper
selection,useandmaintenanceofanyproductremainssolelywiththepurchaserandend-user.
Formoreproduct
information,scanthe
QRcode:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Emerson E3 User manual

Type
User manual

Emerson E3 is a versatile system combining energy management and monitoring for various facility systems. It offers HVAC and lighting control, refrigeration monitoring, and energy consumption reporting. The E3 can reduce energy costs by optimizing HVAC and lighting operation, minimizing energy consumption during peak periods. It also provides alerts for issues requiring attention, helping maintain optimal store conditions.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI