XPSLCMUT1160 muting relay
Troubleshooting guide
Telemecanique Sensors 2
- Technical Support – Sept 15th, 2022
Internal
XPSLCMUT1160 muting relay
Troubleshooting guide
Table from the user manual
Telemecanique Sensors 3
- Technical Support – Sept 15th, 2022
Internal
XPSLCMUT1160 muting relay
Troubleshooting examples
Yellow MUT led blinking 2 times muting lamp in fault
●Root cause : bad connection, lamp missing or in fault, led lamp not compatible, too
much current or not enough current in the lamp
●How to solve : check lamp connection, check voltage & power of the lamp (24 Vdc /
0.5 - 5 W). Change led lamp by filament lamp if necessary
Yellow MUT led blinking 3 times wrong selected value of the muting timeout
●Root cause : 30s value not enough
●How to solve : select « infinite » value by wiring
Yellow MUT led blinking 4 times wrong override configuration at power-up
●Root cause : 1 muting photoelectric sensor in reflex mode not correctly adjusted
●How to solve : check the muting sensors and mirrors, their fixing …
Telemecanique Sensors 4
- Technical Support – Sept 15th, 2022
Internal
Troubleshooting examples
No sensor S1-S2 connected on terminals 1 & 2
●Root cause: no sensor connection
see picture showing leds status
leds « fail » & « Guard break » On state
no led on left side S1 S2 Mut.
muting function does not operate at the light curtain
●How to solve: connect the photoelectric sensors, complying to the user manual
specifications, according to the wiring diagram show in the user manual of the unit
Don’t forget to connect the muting lamp, because it is monitored