INSTALLATION HEAT RECOVERY UNIT
en-14
en
• The plate heat exchangers are wedged between the side
panels. To be able to remove them, space must be created
by removing a side panel.
Keep 30 cm of space free on the side of the unit.
• In exceptional situations, water may run out of the unit.
Make sure that this cannot cause any damage or danger-
ous situations.
•For models with heating: The distance between the ceiling
and the top of the unit must be more than 25 mm.
• Consult the symbols on the unit for the right position:
-and : channels to the interior space
-and : channels to the outside
See also:
1.3.4 "Type plate" on page 8
2.2.2 Hanging the unit up
This manual explains how to suspend the unit for each mod-
ule. Depending on the situation, a different sequence of sus-
pending the units may be selected.
Consult the overview sticker (bottom view) for the module
positions in the specific composition of your unit. If required,
tick the applicable modules.
Fixing the threaded rods
Fix threaded rods M10 in accordance with the dimensions in
the table. Make sure the threaded rods are perpendicular.
nOnly fix the threaded rods for the modules in the
specific composition of your unit. See the overview
sticker.
nThe illustration shows the unit from above, whereby
the air exchange with the interior takes place on the
left side and the air exchange with the exterior takes
place on the right side.