- Move the Venetian blind to the upper end limit position with the local switch.
- Press simultaneously the DOWN key and the “IP key” (for approx. 2 seconds) until the blinds move downwards.
- Stop the blinds at the desired position which is to be the future intermediate position from the upper end limit position, by pressing:
Simultaneously the up and down keys
or the IP key.
- The intermediate position can be adjusted with the local switch.
- Press and hold the “IP key” for at least 2 seconds ➜the intermediate position has been registered.
Recording of slat setting
- Move the blind downwards until the slats are closed with the local switch.
- Press simultaneously the UP key and the “IP key” (for approx. 2 seconds) to set the required slat angle at the desired position which
is to be the future slat orientation setting.
- The angle of the slats can be adjusted with the local switch.
- Once the required slat angle has been obtained, press and hold the IP button for at least 2 seconds ➜the slat angle has been recorded.
5.1 Recording the intermediate position from the upper end limit position
5.2 Calling up the intermediate position with recorded slat angle
- When the 4 blinds are at the upper end limit position, press briefly the “IP key”.
➜the blinds move to the intermediate position followed by a rotation of the slats to the recorded slat angle.
Calling up the slat setting
- the recorded slat angle can be called up at any time after a local DOWN order (i.e. blinds with closed slats), by briefly pressing the “IP
key”.
5.3 Deleting the intermediate position
The intermediate position and slat setting are deleted separately.
Deleting the intermediate position
- Move the 4 blinds to their programmed intermediate position
- Press the “IP key” for at least 10 seconds ➜the intermediate position has been deleted.
Deleting the slat setting
- Move the blinds downwards
- stop the blinds in any position
- Press the “IP key” briefly ➜the blinds move to the set slat angle.
- Press and hold the “IP key” for at least 10 seconds ➜the slat setting has been deleted.
CD 1 x 4 P6 : ( 1 822 038) 100 x 142 mm
CD 1 x 4 P8 : ( 1 822 039) 160 x 165 x 60 mm
DIN rail adapter : ( 9 008 049) 65 x 107 mm
IP 54 box 160 x 165 x 60 mm
Nominal operating voltage 220-240 V ~ 50/60 Hz
BUS line voltage SELV, 9-20 V
Cross-section trip line 2 x 2 x 0,6 mm
Switching contact current-carrying capacity relay Cos phi > 0,8/3 A/230 V/50 Hz
Permissible cross-section of connection wire max. 2,5 mm2single wire
1,5 mm2stranded wire
Fuse Per output F3,15 AH; large disconnecting
capacity, 5 x 20 mm according to IEC 127-2/1
Temperature range 0° C to 40° C
(clean environmental conditions)
Protection factor against solid and splahproof Without box : IP 00
With box : IP 54
Protection class 1
Running time (switching time of relay) Approx. 3 minutes
CE EN 60730-1; EN 50081-1; EN50082-1
SOMFY SAS, capital 20.000.000 Euros, RCS Bonneville 303.970.230
All rights reserved to make changes without prior notice. ©SOMFY. GMD021010
6
Technical data