NSI PL3/0-6 Installation guide

Type
Installation guide

This manual is also suitable for

©2023 NSI Industries
POL_PLSeries_MCH_ProdInstall
03/02/2023
800.321.5847
nsiindustries.com/polaris
Strip wire insulation in accordance with Chart 1 below.
If oxidation is present, use a wire brush to clean the conductor.



Connector sizes 350 to 750 MCM are suitable for use on the line side of
the service equipment per NEC 230.46 requirements.

INSTALLATION INSTRUCTIONS
PL SERIES
CONNECTOR SIZE HEX SIZE STRIP LENGTH (IN)
  
  
  
  
  
  
  
  
  
  
  
  
1: WIRE INSTALLATION
WIRE RANGE
(MCM/AWG)
CONNECTOR SIZE
750 600 500 350 250 3/0 2/0 1/0 #2 #4
750 - 600  
500   
400   
350    
250     
4/0 - 3/0      
2/0       
1/0        
#1       
#2 - #3        
#4 - #6         
#8     
#10 - #14     
2: TORQUE VALUES
  • Page 1 1

NSI PL3/0-6 Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI