Danfoss VLT® AutomationDrive FC 300 90-1200 kW User guide

Type
User guide

This manual is also suitable for

MAKING MODERN LIVING POSSIBLE
Design Guide
VLT
®
AutomationDrive FC 300
90–1200 kW
www.danfoss.com/drives
Contents
1 How to Read this Design Guide
9
1.1 How to Read This Design Guide - FC 300
9
1.2 Available Literature
9
1.3 Approvals
10
1.4 Symbols
10
1.5 Abbreviations
10
1.6 Definitions
11
1.7 Power Factor
14
2 Safety and Conformity
15
2.1 Safety Precautions
15
2.2 Caution
15
2.3 CE Labeling
15
2.4 Enclosure Types
17
2.5 Aggressive Environments
18
3 Product Introduction
19
3.1 Product Overview
19
3.2 Controls
21
3.2.1 Control Principle 22
3.2.2 Control Structure in VVC
plus
Advanced Vector Control 26
3.2.3 Control Structure in Flux Sensorless 27
3.2.4 Control Structure in Flux with Motor Feedback 27
3.2.5 Internal Current Control in VVC
plus
Mode 28
3.2.6 Control Local [Hand On] and Remote [Auto On] Control 28
3.3 Reference Handling
30
3.3.1 Reference Limits 31
3.3.2 Scaling of Preset References and Bus References 32
3.3.3 Scaling of Analog and Pulse References and Feedback 32
3.3.4 Dead Band around Zero 33
3.4 PID Control
37
3.4.1 Speed PID Control 37
3.4.2 Speed PID Control Parameters 37
3.4.3 Example of How to Program the Speed Control 38
3.4.4 Speed PID Control Programming Order 38
3.4.5 Tuning Speed PID Control 40
3.4.6 Process PID Control 41
3.4.7 Process PID Control Parameters 42
Contents Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved.
3.4.8 Example of Process PID Control 43
3.4.9 Process PID Control Programming Order 44
3.4.10 Optimization of the process regulator 45
3.4.11 Ziegler Nichols Tuning Method 45
3.5 General Aspects of EMC
46
3.5.1 General Aspects of EMC Emissions 46
3.5.2 EMC Test Results 48
3.5.3 Emission Requirements 49
3.5.4 Immunity Requirements 50
3.6 Galvanic Isolation (PELV)
51
3.7 Ground Leakage Current
51
3.8 Brake Functions
52
3.8.1 Mechanical Holding Brake 52
3.8.2 Dynamic Braking 53
3.8.3 Selection of Brake Resistor 53
3.9 Mechanical Brake Control
56
3.9.1 Hoist Mechanical Brake 57
3.10 Smart Logic Controller
59
3.11 Extreme Running Conditions
60
3.12 Safe Stop
62
3.12.1 Safe Torque Off Operation 62
3.12.2 Safe Torque Off Operation (FC 302 only) 62
3.12.3 Liability Conditions 62
3.12.4 Additional Information 62
3.12.5 Installation of External Safety Device in Combination with MCB 112 63
4 Selection
64
4.1 Electrical Data, 380–500 V
64
4.2 Electrical Data, 525–690 V
69
4.2.1 Electrical Data, 525–690 V AC, 12-Pulse 75
4.3 General Specifications
78
4.4 Efficiency
84
4.5 Acoustic Noise
84
4.6 dU/dt Conditions
85
4.7 Special Conditions
86
4.7.1 Manual Derating 86
4.7.2 Derating for Ambient Temperature 87
4.7.3 Automatic Derating 89
Contents Design Guide
Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
5 How to Order
90
5.1 Ordering Form
90
5.1.1 Type Code 90
5.1.2 Drive Configurator 91
5.2 Ordering Numbers
95
5.2.1 Options and Accessories 95
5.2.2 Brake Resistors 96
5.2.3 Advanced Harmonic Filters 98
5.2.4 Sine-Wave Filter Modules, 380–690 V AC 105
5.2.5 dU/dt Filters 107
6 Mechanical Installation
109
6.1 Pre-installation
109
6.1.1 Receiving the Adjustable Frequency Drive 109
6.1.2 Transportation and Unpacking 109
6.1.3 Lifting 110
6.1.4 Mechanical Dimensions 112
6.1.5 Mechanical Dimensions, 12-Pulse Units 125
6.2 Mechanical Installation
131
6.2.1 Tools Needed 131
6.2.2 General Considerations 131
6.2.3 Terminal Locations - Frame Size D 133
6.2.4 Terminal Locations - Frame Size E 146
6.2.5 Terminal Locations - Frame Size F 153
6.2.6 Terminal Locations - Frame Size F, 12-Pulse 158
6.2.7 Connector/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12) 164
6.2.8 Connector/Conduit Entry, 12-Pulse - IP21 (NEMA 1) and IP54 (NEMA12) 169
6.2.9 Cooling and Airflow 173
6.2.10 Wall/Panel Mount Installation 175
6.2.11 Pedestal Installation of D-frames 175
6.2.12 Pedestal Installation of E-frames 177
6.2.13 Pedestal Installation of F-frames 178
7 Electrical Installation
179
7.1 Connections
179
7.1.1 Torque Settings 179
7.1.2 Power Connections 180
7.1.3 Power Connections 12-Pulse Adjustable Frequency Drives 205
7.1.4 12-Pulse Transformer Selection Guidelines 207
Contents Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved.
7.1.5 Shielding against Electrical Noise 208
7.1.6 External Fan Power Supply 208
7.2 Fuses and Circuit Breakers
208
7.2.1 Fuses 208
7.2.2 D-frame Short Circuit Current Rating (SCCR) 209
7.2.3 Recommendations 209
7.2.4 Power/Semiconductor Fuse Size 210
7.2.5 Power/Semiconductor Fuse Options 211
7.2.6 Supplementary Fuses 213
7.2.7 High Power Fuses 12-Pulse 215
7.2.8 Supplementary Fuses - High Power 216
7.3 Disconnectors and Contactors
217
7.3.1 Line Power Disconnects - Frame Sizes E and F 217
7.3.2 Line Power Disconnects, 12-Pulse 218
7.3.3 Line Power Contactors 218
7.4 Additional Motor Information
219
7.4.1 Motor Cable 219
7.4.2 Parallel Connection of Motors 220
7.4.3 Motor Insulation 222
7.4.4 Motor Bearing Currents 222
7.5 Control Cables and Terminals
222
7.5.1 Access to Control Terminals 222
7.5.2 Control Cable Routing 222
7.5.3 Control Terminals 224
7.5.4 Switches S201 (A53), S202 (A54), and S801 224
7.5.5 Installing Control Terminals 225
7.5.6 Basic Wiring Example 225
7.5.7 Installing Control Cables 226
7.5.8 12-Pulse Control Cables 229
7.5.9 Relay Output D Frame 231
7.5.10 Relay Output E & F-Frame 231
7.5.11 Brake Resistor Temperature Switch 232
7.6 Additional Connections
232
7.6.1 DC Bus Connection 232
7.6.2 Load Sharing 232
7.6.3 Installation of Brake Cable 232
7.6.4 How to Connect a PC to the Adjustable Frequency Drive 233
7.6.5 PC Software 233
Contents Design Guide
Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
7.7 Safety
234
7.7.1 High Voltage Test 234
7.7.2 Grounding 234
7.7.3 Safety Ground Connection 234
7.8 EMC-compatible Installation
234
7.8.1 Electrical Installation - EMC Precautions 234
7.8.2 Use of EMC-Compatible Cables 236
7.8.3 Grounding of Shielded Control Cables 236
7.8.4 RFI Switch 237
7.9 Line Power Supply Interference/Harmonics
238
7.9.1 The Effect of Harmonics in a Power Distribution System 238
7.9.2 Harmonic Limitation Standards and Requirements 239
7.9.3 Harmonic Mitigation 239
7.9.4 Harmonic Calculation 239
7.10 Residual Current Device
239
7.11 Final Set-up and Test
240
8 Application Examples
241
8.1 Automatic Motor Adaptation (AMA)
241
8.2 Analog Speed Reference
241
8.3 Start/Stop
242
8.4 External Alarm Reset
243
8.5 Speed Reference with Manual Potentiometer
243
8.6 Speed Up/Slow
244
8.7 RS-485 Network Connection
244
8.8 Motor Thermistor
245
8.9 Relay Set-up with Smart Logic Control
245
8.10 Mechanical Brake Control
246
8.11 Encoder Connection
246
8.12 Encoder Direction
247
8.13 Closed-loop Drive System
247
8.14 Stop and Torque Limit
247
9 Options and Accessories
249
9.1.1 Slot A 249
9.1.2 Slot B 249
9.1.3 Slot C 249
9.2 General Purpose Input Output Module MCB 101
250
9.2.1 Galvanic Isolation in the MCB 101 250
Contents Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved.
9.2.2 Digital Inputs - Terminal X30/1-4 251
9.2.3 Analog Inputs - Terminal X30/11, 12 251
9.2.4 Digital Outputs - Terminal X30/6, 7 251
9.2.5 Analog Output - Terminal X30/8 252
9.3 Encoder Option MCB 102
252
9.4 Resolver Option MCB 103
254
9.5 Relay Option MCB 105
256
9.6 24 V Backup Option MCB 107
258
9.7 PTC Thermistor Card MCB 112
259
9.8 MCB 113 Extended Relay Card
261
9.9 Brake Resistors
263
9.10 LCP Panel Mounting Kit
263
9.11 Sine-wave Filters
264
9.12 High Power Options
264
9.12.1 Frame Size D Options 264
9.12.1.1 Load Share Terminals 264
9.12.1.2 Regeneration Terminals 264
9.12.1.3 Anti-condensation Heater 264
9.12.1.4 Brake Chopper 264
9.12.1.5 Line Power Shield 264
9.12.1.6 Ruggedized Printed Circuit Boards 264
9.12.1.7 Heatsink Access Panel 265
9.12.1.8 Line Power Disconnect 265
9.12.1.9 Contactor 265
9.12.1.10 Circuit Breaker 265
9.12.2 Frame Size F Options 265
10 RS-485 Installation and Set-up
267
10.1 Overview
267
10.2 Network Connection
267
10.3 Bus Termination
268
10.4 RS-485 Installation and Set-up
268
10.4.1 EMC Precautions 268
10.5 FC Protocol Overview
268
10.6 Network Configuration
268
10.6.1 Adjustable Frequency Drive Set-up 268
10.7 FC Protocol Message Framing Structure
269
10.7.1 Content of a Character (Byte) 269
Contents Design Guide
Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
10.7.2 Message Structure 269
10.7.3 Message Length (LGE) 269
10.7.4 Adjustable Frequency Drive Address (ADR) 269
10.7.5 Data Control Byte (BCC) 269
10.7.6 The Data Field 270
10.7.7 The PKE Field 271
10.7.8 Parameter Number (PNU) 271
10.7.9 Index (IND) 271
10.7.10 Parameter Value (PWE) 272
10.7.11 Data Types Supported 272
10.7.12 Conversion 272
10.7.13 Process Words (PCD) 273
10.8 Examples
273
10.8.1 Writing a Parameter Value 273
10.8.2 Reading a Parameter Value 273
10.9 Modbus RTU Overview
274
10.9.1 Assumptions 274
10.9.2 Prerequisite Knowledge 274
10.9.3 Modbus RTU Overview 274
10.9.4 Adjustable Frequency Drive with Modbus RTU 274
10.10 Network Configuration
275
10.10.1 Adjustable Frequency Drive with Modbus RTU 275
10.11 Modbus RTU Message Framing Structure
275
10.11.1 Adjustable Frequency Drive with Modbus RTU 275
10.11.2 Modbus RTU Message Structure 275
10.11.3 Start/Stop Field 275
10.11.4 Address Field 276
10.11.5 Function Field 276
10.11.6 Data Field 276
10.11.7 CRC Check Field 276
10.11.8 Coil Register Addressing 277
10.11.9 How to Control the Adjustable Frequency Drive 278
10.11.10 Function Codes Supported by Modbus RTU 279
10.11.11 Modbus Exception Codes 279
10.12 How to Access Parameters
280
10.12.1 Parameter Handling 280
10.12.2 Storage of Data 280
10.12.3 IND 280
Contents Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved.
10.12.4 Text Blocks 280
10.12.5 Conversion Factor 280
10.12.6 Parameter Values 280
10.13 FC Control Profile
280
10.13.1 Control Word According to FC Profile 280
10.13.2 Status Word According to FC Profile 282
10.13.3 Bus Speed Reference Value 284
Index
288
Contents Design Guide
Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
1 How to Read this Design Guide
1.1 How to Read This Design Guide - FC 300
This contains information proprietary to Danfoss. By
accepting and using this manual, the reader agrees that
the information contained herein will be used solely for
operating units from Danfoss or equipment from other
vendors provided that such equipment is intended for
communication with Danfoss units over a serial communi-
cation link. This publication is protected under the
copyright laws of Denmark and most other countries.
Danfoss does not warrant that a software program
produced according to the guidelines provided in this
manual functions properly in every physical, hardware, or
software environment.
Although Danfoss has tested and reviewed the documen-
tation within this manual, Danfoss makes no warranty or
representation, neither expressed nor implied, with respect
to this documentation, including its quality, performance,
or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect,
special, incidental, or consequential damages arising out of
the use, or the inability to use information contained in
this manual, even if advised of the possibility of such
damages. In particular, Danfoss is not responsible for any
costs, including but not limited to those incurred as a
result of lost profits or revenue, loss or damage of
equipment, loss of computer programs, loss of data, the
costs to substitute these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any
time and to change its contents without prior notice or
any obligation to notify former or present users of such
revisions or changes.
FC 300
Design Guide
Software version: 6.6x
This Design Guide can be used for all FC 300 adjustable
frequency drives with software version 6.6x.
The software version number can be seen from 15-43 Software
Version.
Table 1.1 Software Version Label
1.2
Available Literature
1.2.1
Available Literature for VLT
®
AutomationDrive
•
The Instruction Manual is shipped with the unit
and includes information on installation and
startup.
•
The Design Guide includes all technical
information about the adjustable frequency drive,
frames D, E, and F, and customer design and
applications.
•
The Programming Guide provides information on
how to program and includes complete
parameter descriptions.
•
The Profibus Instruction Manual provides
information on how to control, monitor, and
program the adjustable frequency drive via a
Profibus serial communication bus.
•
The DeviceNet Instruction Manual provides
information on how to control, monitor, and
program the adjustable frequency drive via a
DeviceNet serial communication bus.
Danfoss technical literature is available in print from local
Danfoss sales offices or online at: www.danfoss.com/
BusinessAreas/DrivesSolutions/Documentations/Technical
+Documentation.htm
How to Read this Design Gui... Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 9
1
1
1.3 Approvals
Table 1.2 Compliance Marks: CE, UL, and C-Tick
The adjustable frequency drive complies with UL508C
thermal memory retention requirements. For more
information, refer to chapter 3.11.1 Motor Thermal
Protection.
1.4 Symbols
The following symbols are used in this document.
WARNING
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE!
Indicates important information, including situations that
may result in damage to equipment or property.
1.5 Abbreviations
Alternating current AC
American wire gauge AWG
Ampere/AMP A
Automatic Motor Adaptation AMA
Current limit I
LIM
Degrees Celsius
°C
Direct current DC
Drive Dependent D-TYPE
Electro Magnetic Compatibility EMC
Electronic Thermal Relay ETR
Adjustable frequency drive FC
Gram g
Hertz Hz
Horsepower hp
Kilohertz kHz
Local Control Panel LCP
Meter m
Millihenry Inductance mH
Milliampere mA
Millisecond ms
Minute min
Motion Control Tool MCT
Nanofarad nF
Newton Meters Nm
Nominal motor current I
M,N
Nominal motor frequency f
M,N
Nominal motor power P
M,N
Nominal motor voltage U
M,N
Permanent Magnet motor PM motor
Protective Extra Low Voltage PELV
Printed Circuit Board PCB
Rated Inverter Output Current I
INV
Revolutions Per Minute RPM
Regenerative terminals Regen
Second sec.
Synchronous Motor Speed n
s
Torque limit T
LIM
Volts V
The maximum output current I
DRIVE,MAX
The rated output current supplied by the
adjustable frequency drive
I
DRIVE,N
Table 1.3 Abbreviations used in this Manual
How to Read this Design Gui...
Design Guide
10 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
1
1
1.6 Definitions
Drive:
I
DRIVE,MAX
The maximum output current.
I
DRIVE,N
The rated output current supplied by the adjustable
frequency drive.
U
DRIVE, MAX
The maximum output voltage.
Input:
Control command
Start and stop the
connected motor with the
LCP or the digital inputs.
Functions are divided into
two groups.
Functions in group 1 have
higher priority than
functions in group 2.
Group 1 Reset, coasting stop, reset
and coasting stop, quick
stop, DC braking, stop
and the "Off" key.
Group 2 Start, pulse start,
reversing, start reversing,
jog, and freeze output.
Table 1.4 Input Functions
Motor:
f
JOG
The motor frequency when the jog function is activated
(via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The rated motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
T
M,N
The rated torque (motor).
U
M
The instantaneous motor voltage.
U
M,N
The rated motor voltage (nameplate data).
Break-away torque:
n
s
Synchronous motor speed.
n
s
=
2×
par
. 1− 23×60
s
par
. 1− 39
175ZA078.10
Pull-out
rpm
Torque
Figure 1.1 Break-Away Torque Chart
How to Read this Design Gui... Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 11
1
1
η
DRIVE
The efficiency of the adjustable frequency drive is defined
as the ratio between the power output and the power
input.
Start-disable command
A stop command belonging to the group 1 control
commands.
Stop command
See control commands parameter group.
References:
Analog Reference
A signal transmitted to the 53 or 54, can be voltage or
current.
Binary Reference
A signal applied to the serial communication port (RS-485
terminal 68-69).
Bus Reference
A signal transmitted to the serial communication port
(drive port).
Preset Reference
A defined preset reference set from -100% to +100% of
the reference range. Selection of eight preset references
via the digital terminals.
Pulse Reference
A pulse frequency signal transmitted to the digital inputs
(terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input
at 100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value is set in
3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input
at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value is set in
3-02 Minimum Reference.
Miscellaneous:
Analog Inputs
The analog inputs are used for controlling various
functions of the adjustable frequency drive.
There are two types of analog inputs:
Current input, 0–20 mA, and 4–20 mA
Voltage input, 0–10 V DC.
Analog Outputs
The analog outputs can supply a signal of 0–20 mA,
4–20 mA, or a digital signal.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for
the connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the
braking energy generated in regenerative braking. This
regenerative braking energy increases the intermediate
circuit voltage and a brake chopper ensures that the
power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for screw and scroll
refrigeration compressors.
Digital Inputs
The digital inputs can be used for controlling various
functions of the adjustable frequency drive.
Digital Outputs
The adjustable frequency drive features two solid state
outputs that can supply a 24 V DC (max. 40 mA) signal.
DSP
Digital Signal Processor.
Relay Outputs:
The adjustable frequency drive features two programmable
relay outputs.
ETR
Electronic thermal relay is a thermal load calculation based
on present load and time. Its purpose is to estimate the
motor temperature.
How to Read this Design Gui...
Design Guide
12 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
1
1
GLCP
Graphical local control panel (LCP102)
Hiperface
®
Hiperface
®
is a registered trademark by Stegmann.
Initializing
If initialization is carried out (14-22 Operation Mode), the
programmable parameters of the adjustable frequency
drive return to their default settings.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or non-
periodic duty.
LCP
The local control panel (LCP) makes up a complete
interface for control and programming of the adjustable
frequency drive. The LCP is detachable and can be
installed up to 10 ft [3 m] from the adjustable frequency
drive, in a front panel with the installation kit option.
The LCP is available in two versions:
•
Numerical LCP101 (NLCP)
•
Graphical LCP102 (GLCP)
lsb
Least significant bit.
MCM
Short for mille circular mil, an American measuring unit for
cable cross-section. 1 MCM ≡ 0.5067 mm
2
.
msb
Most significant bit.
NLCP
Numerical local control panel LCP101.
Online/Offline Parameters
Changes to online parameters are activated immediately
after the data value is changed. Changes to offline
parameters are not activated until [OK] is entered on the
LCP.
PID Controller
The PID controller maintains the desired speed, pressure
and temperature by adjusting the output frequency to
match the varying load.
PCD
Process Data.
Pulse input/incremental encoder
An external digital sensor used for feedback information of
motor speed and direction. Encoders are used for high-
speed accuracy feedback and in high dynamic applications.
The encoder connection is either via terminal 32 or
encoder option MCB 102.
RCD
Residual Current Device. A device that disconnects a circuit
in case of an imbalance between an energized conductor
and ground. Also known as a ground fault circuit
interrupter (GFCI).
Set-up
Parameter settings can be saved in four set-ups. Change
between the four parameter set-ups and edit one set-up,
while another set-up is active.
SFAVM
Switching pattern called Stator Flux oriented Asynchronous
Vector Modulation (14-00 Switching Pattern).
Slip Compensation
The adjustable frequency drive compensates for the motor
slip by giving the frequency a supplement that follows the
measured motor load, keeping the motor speed almost
constant.
Smart Logic Control (SLC)
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as
true by the SLC.
STW
Status word.
Thermistor:
A temperature-dependent resistor placed where the
temperature is monitored (adjustable frequency drive or
motor).
How to Read this Design Gui...
Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 13
1
1
THD
Total Harmonic Distortion. A state of full harmonic
distortion.
Trip
A state entered in fault situations. For example, if the
adjustable frequency drive is subject to an overtem-
perature or when it is protecting the motor, process, or
mechanism. Restart is prevented until the cause of the
fault has disappeared and the trip state is canceled by
activating reset or, in some cases, by being programmed
to reset automatically. Do not use trip for personal safety.
Trip Locked
A state entered in fault situations when the adjustable
frequency drive is protecting itself and requires physical
intervention. For example, if the adjustable frequency drive
is subject to a short circuit on the output, it will enter trip
lock. A locked trip can only be canceled by cutting off line
power, removing the cause of the fault, and reconnecting
the adjustable frequency drive.
VT Characteristics
Variable torque characteristics used for pumps and fans.
VVC
plus
Compared with standard voltage/frequency ratio control,
Voltage Vector Control (VVC
plus
) improves the dynamics
and stability, both when the speed reference is changed
and in relation to the load torque.
60° AVM
Switching pattern called 60°
Asynchronous Vector
Modulation (See 14-00 Switching Pattern).
1.7
Power Factor
The power factor is the relation between I
1
and I
RMS
.
Power
factor
=
3 ×
U
×
I
1 ×
COS
Ï•
3 ×
U
×
I
RMS
The power factor for 3-phase control:
=
I
1
×
cos
Ï•1
I
RMS
=
I
1
I
RMS
since
cos
Ï•1 = 1
The power factor indicates to what extent the adjustable
frequency drive imposes a load on the line power supply.
The lower the power factor, the higher the I
RMS
for the
same kW performance.
I
RMS
=
I
1
2
+
I
5
2
+
I
7
2
+ . . +
I
n
2
In addition, a high power factor indicates that the different
harmonic currents are low.
The built-in DC coils produce a high power factor, which
minimizes the imposed load on the line power supply.
How to Read this Design Gui... Design Guide
14 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
1
1
2 Safety and Conformity
2.1 Safety Precautions
Adjustable frequency drives contain high-voltage
components and have the potential for fatal injury if
handled improperly. Only trained technicians should install
and operate the equipment. No repair work should be
attempted without first removing power from the
adjustable frequency drive and waiting the designated
amount of time for stored electrical energy to dissipate.
Strict adherence to safety precautions and notices is
mandatory for safe operation of the adjustable frequency
drive.
2.2 Caution
WARNING
DISCHARGE TIME
Adjustable frequency drives contain DC link capacitors
that can remain charged even when the adjustable
frequency drive is not powered. To avoid electrical
hazards, disconnect the following:
•
AC line power
•
Permanent magnet type motors
•
Remote DC link power supplies, including
battery backups, UPS and DC link connections
to other adjustable frequency drives
Wait for the capacitors to fully discharge before
performing any service or repair work. The amount of
wait time is listed in the Capacitor Discharge Time table.
Failure to wait the specified time after power has been
removed before starting service or repair could result in
death or serious injury.
Voltage
[V]
Power [kW] Minimum Waiting
Time [Min]
380–500 90–250 20
315–800 kW 40
525–690 55–315 (frame size D) 20
355–1200 30
Table 2.1 Capacitor Discharge Times
2.2.1
Disposal Instructions
Do not dispose of equipment containing
electrical components together with
domestic waste.
Collect it separately in accordance with
local and currently valid legislation.
Table 2.2 Disposal Instructions
2.3 CE Labeling
2.3.1 CE Conformity and Labeling
Machinery Directive (2006/42/EC)
Adjustable frequency drives do not fall under the
machinery directive. However, if an adjustable frequency
drive is supplied for use in a machine, Danfoss provides
information on safety aspects relating to the adjustable
frequency drive.
What is CE Conformity and Labeling?
The purpose of CE labeling is to avoid technical trade
obstacles within the EFTA and the EU. The EU has
introduced the CE label as a simple way of showing
whether a product complies with the relevant EU
directives. The CE label says nothing about the specifi-
cations or quality of the product. Adjustable frequency
drives are regulated by two EU directives:
Low Voltage Directive (2006/95/EC)
Adjustable frequency drives must be CE-labeled in
accordance with the Low-voltage Directive of January 1,
1997. The directive applies to all electrical equipment and
appliances used in the 50–1000 V AC and the 75–1500 V
DC voltage ranges. Danfoss CE labels in accordance with
the directive and issues a declaration of conformity upon
request.
EMC Directive (2004/108/EC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means that the
mutual interference between different components/
appliances does not affect the way the appliances work.
The EMC directive came into effect January 1, 1996.
Danfoss CE labels in accordance with the directive and
issues a declaration of conformity upon request. To carry
out EMC-compatible installation, see chapter 7.8 EMC-
compatible Installation.
In addition, we specify which standards our products
comply with. Danfossoffer the filters presented in the
specifications and provide other types of assistance to
ensure the optimum EMC result.
Safety and Conformity
Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 15
2 2
The adjustable frequency drive is most often used by trade
professionals as a complex component forming part of a
larger appliance, system or installation. It must be noted
that the responsibility for the final EMC properties of the
appliance, system or installation rests with the installer.
2.3.2 What Is Covered
The EU "Guidelines on the Application of Council Directive
2004/108/EC" outline three typical situations of using an
adjustable frequency drive. See the following list for EMC
coverage and CE labeling.
1. The adjustable frequency drive is sold directly to
the end consumer, for example, to a DIY market.
The end consumer is a layman who installs the
adjustable frequency drive for use with a
household appliance. For such applications, the
adjustable frequency drive must be CE-labeled in
accordance with the EMC directive.
2. The adjustable frequency drive is sold for instal-
lation in a plant designed by trade professionals.
The adjustable frequency drive and the finished
plant do not have to be CE-labeled under the
EMC directive. However, the unit must comply
with the basic EMC requirements of the directive.
Compliance is ensured by using components,
appliances, and systems that are CE-labeled
under the EMC directive.
3. The adjustable frequency drive is sold as part of a
complete system, such as an air-conditioning
system. The entire system must be CE-labeled in
accordance with the EMC directive. The
manufacturer can ensure CE-labeling under the
EMC directive either by using CE-labeled
components or by testing the EMC of the system.
If the manufacturer chooses to use only CE-
labeled components, there is no need to test the
entire system.
2.3.3
Danfoss Adjustable Frequency Drive
and CE Labeling
CE-labeling is a positive feature when used for its original
purpose, which is to facilitate trade within the EU and
EFTA.
CE-labeling can cover many different specifications so
check the CE label to ensure that it covers the relevant
applications.
Danfoss CE labels the adjustable frequency drives in
accordance with the low voltage directive, meaning that if
the adjustable frequency drive is installed correctly,
Danfoss guarantees compliance with the low voltage
directive. Danfoss issues a declaration of conformity that
confirms our CE labeling in accordance with the low
voltage directive.
The CE label also applies if following the instructions for
EMC-compatible installation and filtering.
Detailed instructions for EMC-compatible installation are
found in Chapter 7.8 EMC-compatible Installation.
Furthermore, Danfoss specifies which standards our
products comply with.
2.3.4
Compliance with EMC Directive
2004/108/EC
The primary users of the adjustable frequency drive are
trade professionals, who use it as a complex component
forming part of a larger appliance, system, or installation.
The responsibility for the final EMC properties of the
appliance, system, or installation rests with the installer. As
an aid to the installer, Danfoss has prepared EMC instal-
lation guidelines for the power drive system. If the EMC-
compatible instructions for installation are followed, the
standards and test levels stated for power drive systems
are complied with. See chapter 3.5.4 Immunity
Requirements.
Safety and Conformity Design Guide
16 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
22
2.4 Enclosure Types
The VLT Series adjustable frequency drives are available
in various enclosure types to best accommodate the
needs of the application. Enclosure ratings are provided
based on two international standards:
•
NEMA (National Electrical Manufacturers
Association) in the United States
•
IP (International Protection) ratings outlined by
IEC (International Electrotechnical Commission) in
the rest of the world
Standard Danfoss VLT adjustable frequency drives are
available in various enclosure types to meet the
requirements of IP00 (chassis), IP20, IP21 (NEMA 1), or IP54
(NEMA12).
UL and NEMA Standards
NEMA/UL Type 1 – Enclosures constructed for indoor use
to provide a degree of protection to personnel against
incidental contact with the enclosed units and to provide a
degree of protection against falling dirt.
NEMA/UL Type 12 – General purpose enclosures are
intended for use indoors to protect the enclosed units
against the following contaminants:
•
fibers
•
lint
•
dust and dirt
•
light splashing
•
seepage
•
dripping and external condensation of non-
corrosive liquids
There can be no holes through the enclosure and no
conduit knockouts or conduit openings, except when used
with oil-resistant gaskets to mount oil-tight or dust-tight
mechanisms. Doors are also provided with oil-resistant
gaskets. In addition, enclosures for combination controllers
have hinged doors, which swing horizontally and require a
tool to open.
UL type validates that the enclosures meet NEMA
standards. The construction and testing requirements for
enclosures are provided in NEMA Standards Publication
250-2003 and UL 50, Eleventh Edition.
IP Codes
Table 2.4 provides a cross-reference between the two
standards. Table 2.3 demonstrates how to read the IP
number code and defines the levels of protection. The
adjustable frequency drives meet the requirements of
both.
NEMA type IP type
Chassis IP00
Protected chassis IP20
NEMA 1 IP21
NEMA 12 IP54
Table 2.3 IP Number Cross Reference
First digit (solid foreign objects)
0 No protection
1 Protected to 50 mm (hands)
2 Protected to 12.5 mm (fingers)
3 Protected to 2.5 mm (tools)
4 Protected to 1.0 mm (wire)
5 Protected against dust – limited entry
6 Protected totally against dust
Second digit (water)
0 No protection
1 Protected from vertical dripping water
2 Protected from dripping water at 15° angle
3 Protected from water at 60° angle
4 Protected from splashing water
5 Protected from water jets
6 Protected from strong water jets
7 Protected from temporary immersion
8 Protected from permanent immersion
Table 2.4 IP Number Code Definitions
Safety and Conformity Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 17
2 2
2.5 Aggressive Environments
An adjustable frequency drive contains a large number of
mechanical and electronic components, many of which are
vulnerable to environmental effects.
CAUTION
The adjustable frequency drive should not be installed in
environments with airborne liquids, particles or gases
capable of affecting and damaging the electronic
components. Failure to take the necessary protective
measures increases the risk of stoppages, thus reducing
the life of the adjustable frequency drive.
Degree of protection as per IEC 60529
To prevent cross faults and short circuits between
terminals, connectors, tracks, and safety-related circuitry
caused by foreign objects, the Safe Torque Off (STO)
function must be installed and operated in an IP54 or
higher rated control cabinet (or equivalent environment).
Liquids can be carried through the air and condense in the
adjustable frequency drive and may cause corrosion of
components and metal parts. Steam, oil, and salt water
may cause corrosion of components and metal parts. In
such environments, use equipment with enclosure rating IP
54/55. As an extra protection, coated printed circuit boards
can be ordered as an option.
Airborne particles such as dust may cause mechanical,
electrical or thermal failure in the adjustable frequency
drive. A typical indicator of excessive levels of airborne
particles is the presence of dust particles around the
adjustable frequency drive fan. In very dusty environments,
use equipment with enclosure rating IP54/IP55 or a cabinet
for IP00/IP20/TYPE 1 equipment.
In environments with high temperatures and humidity,
corrosive gases such as sulfur, nitrogen, and chlorine
compounds will cause chemical reactions on the adjustable
frequency drive components.
Such chemical reactions will rapidly affect and damage the
electronic components. In such environments, mount the
equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the adjustable frequency drive.
Optional coated PCBs also offer protection in such
environments.
NOTICE!
Mounting adjustable frequency drives in aggressive
environments increases the risk of stoppages and consid-
erably reduces the life of the drive.
Before installing the adjustable frequency drive, check the
ambient air for liquids, particles and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on instal-
lation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends.
D and E enclosures have a stainless steel backchannel
option to provide additional protection in corrosive
environments such as salt air found near sea side
applications. Proper ventilation is still required for the
internal components of the adjustable frequency drive.
Contact Danfoss for additional information.
2.5.1
Humidity
The adjustable frequency drive has been designed to meet
the IEC/EN 60068-2-3 standard, EN 50178 § 9.4.2.2 at
122 °F [50 °C].
2.5.2
Vibration
The adjustable frequency drive has been tested according
to the procedure based on the following standards:
•
IEC/EN 60068-2-6: Vibration (sinusoidal) - 1970
•
IEC/EN 60068-2-64: Vibration, broad-band random
The adjustable frequency drive complies with requirements
that exist for units mounted on the walls and floors of
production premises, as well as in panels bolted to walls or
floors.
Safety and Conformity Design Guide
18 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
22
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296

Danfoss VLT® AutomationDrive FC 300 90-1200 kW User guide

Type
User guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI