ABB ACS880-207 User manual

  • Hello! I am an AI chatbot trained to assist you with the ABB ACS880-207 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ABB industrial drives
Hardware manual
ACS880-207 IGBT supply units
List of related manuals
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
General manuals Code (English)
Safety instructions for ACS880 multidrive cabinets and
modules
3AUA0000102301
Electrical planning instructions for ACS880 multidrive
cabinets and modules
3AUA0000102324
Mechanical installation instructions for ACS880 multidrive
cabinets
3AUA0000101764
Cabinet design and construction instructions for ACS880 air-
cooled and liquid-cooled multidrive modules
3AUA0000107668
BCU-02/12/22 control units hardware manual 3AUA0000113605
Supply unit manuals
ACS880-207 IGBT supply units hardware manual 3AUA0000130644
ACS880 IGBT supply control program firmware manual 3AUA0000131562
ACS880-307 +A003 diode supply units hardware manual 3AUA0000102453
ACS880-307 +A018 diode supply units hardware manual 3AXD50000011408
ACS880 diode supply control program firmware manual 3AUA0000103295
ACS880-907 regenerative rectifier units hardware manual 3AXD50000020546
ACS880 regenerative rectifier control program firmware
manual
3AXD50000020827
Inverter unit manuals and guides
ACS880-107 inverter units hardware manual 3AUA0000102519
ACS880 primary control program firmware manual 3AUA0000085967
ACS880 primary control program quick start-up guide 3AUA0000098062
Brake unit and DC/DC converter unit manuals
ACS880-607 1-phase brake units hardware manual 3AUA0000102559
ACS880-607 3-phase brake units hardware manual 3AXD50000022034
ACS880 brake control program firmware manual 3AXD50000020967
ACS880-1607 DC/DC converter units hardware manual 3AXD50000023644
ACS880 DC/DC converter control program firmware manual 3AXD50000024671
System description
Parallel connected ACS880-207 IGBT supply units system
description
3AXD50000032517
Parallel connected ACS880-307 +A018 diode supply units
system description
3AXD50000032421
Parallel connected ACS880-907 regenerative rectifier units
system description
3AXD50000036609
Option manuals and guides
ACS-AP-x assistant control panels users manual 3AUA0000085685
Drive composer start-up and maintenance PC tool users
manual
3AUA0000094606
Manuals and quick guides for I/O extension modules,
fieldbus adapters, safety options etc.
Hardware manual
ACS880-207 IGBT supply units
3AUA0000130644 Rev C
EN
EFFECTIVE: 2017-11-29
2017 ABB Oy. All Rights Reserved.
3. Electrical installation
5. Start-up
Table of contents
5
Table of contents
1. Introduction to the manual
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Contents of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Categorization by frame size, option code and item designation . . . . . . . . . . . . . . . . . . 10
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2. Operation principle and hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operation principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Main circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Overview diagram of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Layout drawing of an IGBT supply unit 1×R8i (limited scope version) . . . . . . . . . . . . . . 16
Overview drawing of a drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Layout drawings of the cubicles in the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Layout drawing of an auxiliary control cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Layout drawings of incoming cubicles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Layout drawing of a 400 mm incoming cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Layout drawing of a 600 mm incoming cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Layout drawing of a 1000 mm incoming cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Layout drawing of a supply module cubicle 2×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Layout drawings of supply and LCL filter modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
IGBT supply module (frame R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LCL filter module (BLCL-1x-x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
LCL filter module (BLCL-2x-x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overview of power and control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overview of the control connections on the BCU control unit . . . . . . . . . . . . . . . . . . 28
Supply unit control devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Door switches and devices for frame R8i cabinet (limited scope version) . . . . . . . 29
Door switches and devices for frame R8i cabinet . . . . . . . . . . . . . . . . . . . . . . . . . 30
Main switch-disconnector / breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Auxiliary voltage switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Grounding switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Charging switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operating switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Emergency stop button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
E-stop reset button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Other door controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
The ACS-AP-W control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PC connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fieldbus control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Type designation labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6
Type designation label of the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Type designation label of the supply module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Type designation label of the LCL filter module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Type designation keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Type designation key of the cabinet-installed IGBT supply unit . . . . . . . . . . . . . . . . 35
Type designation key of the IGBT supply module . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Type designation key of the filter module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3. Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Electrical safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Input power cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Checking the compatibility with IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . 43
Connecting the input power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Connection diagram (frame 1×R8i, limited scope version) . . . . . . . . . . . . . . . . . . . . 44
Connection diagram (frame R8i and multiples) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Connection procedure (frame R8i, limited scope version) . . . . . . . . . . . . . . . . . . . . 46
Connection procedure (frame R8i and multiples) . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Setting the voltage range of the auxiliary voltage transformers (option +G344) . . . . . . 52
[T21/T101] connections (400...500 V units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
[T21/T101] connections (690 V units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
[T111] connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Checking the settings of the cooling fan transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connecting the control cables for the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Default I/O connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Connection procedure (frame R8i, limited scope version) . . . . . . . . . . . . . . . . . . . . 55
Connection procedure (frame R8i and multiples) . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Grounding the outer shields of the control cables at the cabinet lead-through . . 57
Wiring the functional safety options +Q951, +Q952, +Q963, +Q964 or +Q979 . . . . . . 60
Connecting a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4. Installation checklist
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5. Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Checks/Settings with no voltage connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Powering up the auxiliary circuit of the supply unit . . . . . . . . . . . . . . . . . . . . . . . . 64
Setting up the supply unit parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Powering up the main circuit of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
On-load checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Switching off the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Disconnecting and temporary grounding the drive
(excluding the input power terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Disconnecting and temporary grounding the drive
7
(including the input power terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6. Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Maintenance timers and counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Cleaning the interior of the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Cleaning the door air inlets (IP22 and IP42, option +B054) . . . . . . . . . . . . . . . . . . . . 72
Cleaning the door air inlets (IP54, option +B055) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Replacing the outlet (roof) filters (IP54, option +B055) . . . . . . . . . . . . . . . . . . . . . . . . 74
Cleaning the heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Power connections and quick connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Tightening the power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Replacing the cooling fan of the IGBT supply module (frame R8i) . . . . . . . . . . . . . . . 75
Replacing the direct-on-line (option +C188) module fan (frame R8i) . . . . . . . . . . . . . 77
Replacing the circuit board compartment fan (frame R8i) . . . . . . . . . . . . . . . . . . . . . 78
Replacing the fan of the LCL filter (BLCL-1x-x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Replacing the fan of the LCL filter (BLCL-2x-x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Replacing the fan in the incoming cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Replacing the fan in the auxiliary control cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Replacing the roof fan for IP54 cabinet (option +B055) . . . . . . . . . . . . . . . . . . . . . . . 84
IGBT supply module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Cleaning the module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Reduced run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Starting reduced run operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Resuming normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Replacing the IGBT supply module (limited scope version) . . . . . . . . . . . . . . . . . . . . 87
Replacing the IGBT supply module (frame R8i and multiples) . . . . . . . . . . . . . . . . . . 90
LCL filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Replacing the LCL filter (limited scope version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Replacing the LCL filter (frame R8i and multiples) . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Reforming the capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Checking and replacing the DC fuses (limited scope version) . . . . . . . . . . . . . . . . . 101
Checking and replacing the AC fuses (limited scope version) . . . . . . . . . . . . . . . . . 103
Checking and replacing the DC fuses (frame R8i and multiples) . . . . . . . . . . . . . . . 104
Checking and replacing the AC fuses (frame R8i and multiples) . . . . . . . . . . . . . . . 104
Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Replacing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Cleaning the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Memory unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Transferring the memory unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
LEDs and other status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
7. Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
8
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Main circuit AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Main circuit DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Fuses on CVAR board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
LCL filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Free space requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Losses, cooling data and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Terminal and lead-through data for the input power cable . . . . . . . . . . . . . . . . . . . . . 118
Frame R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
400 mm incoming cubicle with main switch, bottom cable entry . . . . . . . . . . . . . . . 118
600 mm incoming cubicle – main switch (+F253) . . . . . . . . . . . . . . . . . . . . . . . . . . 119
600 mm incoming cubicle with main switch, bottom cable entry . . . . . . . . . . . . . . . 120
600 mm incoming cubicle with main breaker, bottom cable entry . . . . . . . . . . . . . . 121
600 mm incoming cubicle with main breaker, top cable entry . . . . . . . . . . . . . . . . . 122
1000 mm incoming cubicle with main breaker, bottom cable entry . . . . . . . . . . . . . 123
1000 mm incoming cubicle with main breaker, top cable entry . . . . . . . . . . . . . . . . 124
Tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Cable lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Mechanical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Insulation supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Electrical power network specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Control unit connection data (BCU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Disclaimers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Generic disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Cybersecurity disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
8. The control unit
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Layout and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Default I/O connection diagram (BCU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
External power supply for the control unit (XPOW) . . . . . . . . . . . . . . . . . . . . . . . . . 136
Drive-to-drive link (XD2D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
SDHC memory card slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Introduction to the manual 9
1
Introduction to the manual
What this chapter contains
This chapter gives basic information on the manual.
Applicability
The manual is applicable to the cabinet-installed ACS880-207 IGBT supply units that form
a part of an ACS880 multidrive system.
Safety instructions
Follow all safety instructions delivered with the drive.
Read the complete safety instructions before you install, commission, use or
service the drive. The complete safety instructions are given in ACS880 multidrive and
multidrive modules safety instructions (3AUA0000102301 [English]
).
Read the software-function-specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are given in
the section describing the related user-adjustable parameters.
Read the task-specific safety instructions before starting the task. See the section
describing the task.
Target audience
This manual is intended for people who install, start-up and service multidrives. Read the
manual before working on the drive. You are expected to know the fundamentals of
electricity, wiring, electrical components and electrical schematic symbols.
10 Introduction to the manual
Purpose of the manual
This manual helps in installing, commissioning, using and maintaining a multidrive with
and IGBT supply unit.
Contents of the manual
Introduction to the manual
Operation principle and hardware description
Electrical installation
Installation checklist
Start-up
Maintenance
Technical data
The control unit.
Related documents
The multidrive user documentation consists of technical drawings and a set of manuals.
The technical drawings are tailor-made for each drive. The composition of the manual set
depends on the composition of the drive, eg, which supply unit type, options and inverter
control program has been ordered by the customer. The main manuals have been listed
on the back of the front cover.
Categorization by frame size, option code and item
designation
The instructions and technical data which concern only certain unit or frame sizes are
marked with the size identifier.
The unit size can be identified from the basic code visible on the type designation label, for
example, ACS880-207-0420A-3 where 0420A is the unit size. The option codes of the unit
are listed after the plus sign. Section Type designation keys on page 35 explains the type
designation code in detail.
The frame size of the IGBT supply module is, for example, R8i. The Ratings table on
page 109 lists the frame sizes.
Some device names in the manual include the item designations in brackets, for example
[Q2] to make it possible to identify the components in the circuit diagrams of the drive.
Introduction to the manual 11
Terms and abbreviations
Term/Abbreviation Description
Auxiliary control cubicle
(ACU)
The cubicle with auxiliary devices such as auxiliary voltage circuit breakers,
control electronics, measurement boards, etc.
BCON Type of a control board
BCU Type of a control unit (contains BCON)
Control board Circuit board in which the control program runs.
Control unit Control board built in a rail-mountable housing
Cubicle One section of a cabinet-installed drive. A cubicle is typically behind a door of
its own.
CVAR Varistor board (for UL/CSA installations)
DC link DC circuit between supply unit and inverter unit(s)
DI Digital input
Drive Frequency converter for controlling AC motors. The drive consists of the supply
unit and one or multiple inverter units connected by the DC link. The drive may
also contain other units such as the brake unit.
FCAN-01 Optional CANopen® adapter module
FCNA-01 Optional ControlNet™ adapter module
FDCO-01 Optional DDCS communication module
FDNA-01 Optional DeviceNet™ adapter module
FDPI-02 Diagnostics and panel interface
FEA-03 Optional option module extension adapter
FECA-01 Optional EtherCAT® adapter module
FENA-11 Optional high-performance Ethernet/IP™, Modbus/TCP and PROFINET
adapter module
FENA-21 Optional high-performance Ethernet/IP™, Modbus/TCP and PROFINET
adapter module
FEPL-01 FEPL-01 Ethernet POWERLINK adapter module
FIO-01 Optional digital I/O extension module
FIO-11 Optional analog I/O extension module
FLON-01 Optional LonWorks® adapter module
FPBA-01 Optional PROFIBUS DP® adapter module
Frame (size) Relates to the construction of power modules (such as Inverter). For example,
several inverter module types with different power ratings may have the same
basic construction, and the frame size is used in reference to all those modules.
The frame size marking indicates the quantity and frame size of the inverter
modules, eg. “3×R8i”.
To determine the frame size of an inverter unit, see the rating tables in chapter
Technical data.
FSCA-01 Optional Modbus/RTU adapter module
FSO-xx Optional safety function module (not used in supply units)
12 Introduction to the manual
IGBT Insulated gate bipolar transistor; a voltage-controlled semiconductor type
widely used in drives due to their easy controllability and high switching
frequency
IGBT supply module IGBT type rectifier and related components enclosed inside a metal frame or
enclosure. Intended for cabinet installation.
IGBT supply unit IGBT supply module(s) under control of one control board, and related
components such as LCL filters, main contactor, fuses etc. See IGBT supply
module.
Incoming cubicle (ICU) In cabinet-installed drives, ICU is the incoming unit (cubicle) which contains
main circuit breaker and the busbars for the input power cable.
Intermediate circuit DC link
INU Inverter unit
Inverter Converts direct current and voltage to alternating current and voltage.
Inverter module Inverter bridge, related components and drive DC link capacitors enclosed
inside a metal frame or enclosure. Intended for cabinet installation.
Inverter unit The part of the Drive that converts DC to AC for the motor. Consists of one or
more inverter modules and their auxiliary components.
The inverter unit is also capable of feeding energy from a decelerating motor
into the DC link.
ISU IGBT supply unit
I/O Input/Output
LCL filter Inductor-capacitor-inductor filter for attenuating harmonics
Limited scope Simplified version of a low power multidrive (400V and 500V) with less options
and configurations. Includes only max 980A DSU, max 810A IGBT supply units
and R1i-R7i inverter units.
Multidrive Drive for controlling several motors which are typically coupled to the same
machinery. Includes one supply unit, and one or several inverter units.
Parameter In the control program, user-adjustable operation instruction to the drive, or
signal measured or calculated by the drive
RDCO-0x Optional DDCS communication module
Rectifier Converts alternating current and voltage to direct current and voltage.
Single drive Drive for controlling one motor
Term/Abbreviation Description
Operation principle and hardware description 13
2
Operation principle and
hardware description
What this chapter contains
This chapter describes the operation basics and the hardware of the IGBT supply unit
(ACS880-207).
Operation principle
IGBT supply unit rectifies three-phase AC current to direct current for the intermediate DC
link of the drive. The intermediate DC link supplies the inverters that run the motor. There
can be one inverter unit only (single drives) or several inverter units (multidrives)
connected to the intermediate circuit.
The
LCL filter is an essential part of the IGBT supply unit. It suppresses the AC voltage
distortion and current harmonics. The high AC inductance smooths the line voltage
waveform distorted by the high-frequency switching of the converter. Capacitive
component of the filter effectively filters the high-frequency (over 1 kHz) harmonics.
14 Operation principle and hardware description
Main circuit diagram
The following figure shows the simplified main circuit diagram of the rectifier.
Charging
Charging is always needed to power up the DC link capacitors smoothly. Discharged
capacitors cannot be connected to the full supply voltage. The voltage must be increased
gradually until the capacitors are charged and ready for normal use. In ACS880-207 IGBT
supply units, a resistive charging circuit consisting of fuses, a contactor and charging
resistors, is used. The resistive charging circuit is in use after power-up as long as DC
voltage has risen to a predefined level.
The IGBT supply control program has a function for controlling the charging circuit in the
IGBT supply unit. For further information, see the firmware manual.
LCL filter
DC fuses
IGBT supply module
AC fuses
DC output
AC input
Operation principle and hardware description 15
Overview diagram of the drive
The following figure shows a single-line diagram of a drive with an IGBT supply unit.
The figure includes:
Description
1. Auxiliary voltage transformer ([T21], option +G344)
2. Auxiliary voltage switch [Q21]
3. Main switch-disconnector ([Q1], option +F253) (standard, always with +F250)
4. AC fuses [F1]
5. Main contactor ([Q2], option +F250) (standard, always with +F253)
6. Charging switch fuse [Q3]
7. Charging contactor [Q4]
8. Charging resistors [R1]
9. LCL filter [R03]
10. IGBT supply module [T01]
11. Common mode filter [R1]
12. DC fuses [F2]
13. Inverter modules [T11]
14. Motor(s)
M
3~
M
3~
~ 3
M
3~
3
4
5
9
1310
2
1
1313
12 12
11
1212
14
6
7
8
11 11 11
16 Operation principle and hardware description
Layout drawing of an IGBT supply unit 1×R8i (limited
scope version)
Note that there is also another version of 1×R8i supply unit available, see the drawings
below. The multidrive version contains separate auxiliary control and incoming cubicles.
No. Description
1. Incoming cubicle
2. IGBT supply module cubicle
3. BCU control unit [A51] with optional modules
4. AC fuses [F1]
5. Main switch-disconnector ([Q1], option +F253)
6. Input power cable connections [L1, L2, L3]
7. Location of PE busbar and input power cable lead-throughs
8. LCL filter module [R03]
9. DC fuses [F2]
10. IGBT supply module [T01]
11. Module cooling fan
12. Cabinet cooling fan
13. Auxiliary voltage switch [Q21]
14. Charging assembly plate containing charging contactor [Q4] and resistors
15. Charging switch [Q3]
Doors closed Doors open
1
3
2
4
5
6
7
8
9
10
11
12
11
13
14
15
Operation principle and hardware description 17
Overview drawing of a drive
This drawing shows an example of a drive with an IGBT supply unit and an inverter unit.
Cables enter the cabinet through the bottom.
Description
A Auxiliary control cubicle (ACU). Contains control electronics and customer I/O connections. See
page 18.
B Incoming cubicle (ICU). Contains the power input cable terminals and switchgear. See page 20.
C Supply module cubicle. Contains IGBT supply modules. See page 23.
D Inverter module cubicle. Contains inverter modules.
E Inverter control cubicle. Contains inverter control unit.
A B C D E
Supply unit Inverter unit
18 Operation principle and hardware description
Layout drawings of the cubicles in the supply unit
This section contains layout drawings of cubicles that are included in a supply unit:
auxiliary control cubicle, incoming cubicle and supply module cubicle. The components,
layout and size of the cubicles vary depending on the supply unit size and options.
Layout drawing of an auxiliary control cubicle
This is an example of a 600 mm wide auxiliary control cubicle. The control unit of the
supply unit, and auxiliary and control devices of the whole drive are located in the auxiliary
cubicle, as well as the auxiliary voltage transformer(s) that supply the auxiliary circuits.
The composition and size of the cubicle vary depending on the selected options.
Door closed Door open
5
32
4
14
7
8
9
10
11
12
13
16
15
17
18
19
6
1
Operation principle and hardware description 19
No. Desig. Description
1 S21, etc. Control panel and operating switches. See section Supply unit control devices on page
29.
2 F111 Fuses, direct-on-line cooling fans of the module (option +C188)
3 F101 Fuses, IP54 roof fans (option +B055)
4 F21 Fuses, auxiliary voltage transformer
5 A51 Control unit (BCU) for IGBT supply unit ACS880-207
6 T130 24 V DC power supply for cabinet lighting (option +G301)
7 Reserved space for customer-defined equipment
T21 At the backside of the assembly plate:
Auxiliary voltage transformer (option +G344).
Note: Connections are accessible from front. (Terminal block is at the lower part of
cubicle.)
T101 At the backside of the assembly plate:
Auxiliary voltage transformer, IP54 roof fans
(option +B055). Note: Connections are accessible from front. (Terminal block is at the
lower part of cubicle.)
8 A61 Main safety relay (optional)
A62 Safety relay (optional)
A63 Safety relay (optional)
9 A611 Safety relay (optional)
A612
A613
A614
A621
A622
A623
A624
10 K61…K66 Relays (optional)
11 X60 Terminal block, emergency stop circuit (optional)
12 T61 Power supply, safety circuit (optional)
T62 Power supply, safety circuit (optional)
F61 Protection switch, safety circuit (optional)
13 T21X1,
T101X1
Terminal blocks, auxiliary voltage transformers T21 and T101 connections
14 T111 Auxiliary voltage transformer. Supplies direct-on-line cooling fans (option +C188).
15 X22 Auxiliary circuit terminal block (on side plate)
16 T22, X21 24 V DC power supply (on side plate)
17 F20, F22 Circuit breakers, auxiliary voltage circuits (on side plate)
18 Q20 Connections and switches for external auxiliary voltage supplies (UPS), (option +G307,
on side plate)
Q95
Q130
19 X60, X61 Terminal blocks, emergency stop circuits (option, on side plate)
20 Operation principle and hardware description
Layout drawings of incoming cubicles
This section shows examples of the incoming cubicle layouts. The input power cables are
connected to the incoming cubicle and it contains the main switching and disconnecting
devices. The components, layout and size vary depending on the supply unit size and
options.
Layout drawing of a 400 mm incoming cubicle
These layout drawings show a 400 mm wide incoming cubicle.
1
2
5
6
7
8
9
12
11
10
4
3
Door closed Door open
No. Description
1. Main switch-disconnector handle
2. Earthing/grounding switch handle
([Q9], option +F259)
3. Auxiliary voltage switch handle
4. Selector switch for V-meter (option
+G334)
5. Grounding busbar (PE)
6. Input power cable terminals [L1…L3]
7. Main switch-disconnector [Q1]
8. Earthing/grounding switch [Q9]
(option +F259)
9. Main AC fuses (F1…3)
10. Main contactor [Q2] (option +F250)
11. Auxiliary voltage switch [Q21]
12. Cubicle cooling fan
13. Charging switch handle
14. Charging switch [Q3]
15. Charging resistors
13
14
15
/