Buzzer enabling
Operation mode of temperature sensor S3
Temperature difference (S3 S1) above which the setpoint SP1 is activated
Temperature difference (S3 S1) below which the setpoint SP2 is activated (economic setpoint)
Sensor S3 temperature (condenser) for visual and audible alarm
Sensor S3 temperature (condenser) to turn off the loads (visual and audible alarm)
Control differential (hysteresis) for sensor S3 (F34 and F35)
0-Disable
0
0.1
0.1
-50
-50
0.1
-
-
°C
°C
°C
°C
°C
1-Enable
3
20.0
20.0
75.0
75.0
20.0
0-Disable
0
1
1
-58
-58
1
-
-
°F
°F
°F
°F
°F
1-Enable
3
36
36
167
167
36
0
9
4
113
140
2
1-Enable
0
5.0
2.0
45.0
60.0
1.0
1-Enable
F11 - Minimum compressor time OFF
F12 - Compressor status with detached room sensor (S1)
It is the minimum time that the compressor will keep turned off, it means, the time period between the last
stopped and the next started. It serves to alliviate the pressure and to increase the useful life of the
compressor.
If the room sensor (S1) is detached or out specified range, the compressor assumes the configured status
in this function.
For counters that storage fruits it is better that the compressor keeps turned off, but in counters
thatstorage meatsit is better thatthe compressorkeepsturned on.
Exemple:
F13 - Defrost when the instrument is powered on
F14 - Evaporator temperature (S2 / S3*) for determine end of defrost
F15 - Ma
It possibilities the defrost at the moment that the controller is turned on, for example, in return of
electrical energy (in case of energy lacks).
If evaporator temperature (sensor S2 / S3) reaches the adjusted value, the end defrost will happen for
temperature. With this , the defrost process is optimized.
ximum duration of defrost
This function serves to adjust the maximum value of time to defrost. If in this period the evaporator
temperature will not reach theconfigured valuein F14 a pointwill be blinking on inferiordown rightside of
display indicatingthat the end defrostocurredfor time andnot for temperature.
The end of defrosting by time (whichis not desirable)may occurin the following situations:
-Adjusted temperature (F14) is toohigh;
-Maximum defrostingtime (F15) is insufficient;
-Sensor (S2 / S3) is disconnected or detachedfrom the evaporator.
It possibilities the fan functioning during defrost.
Natural defrost or by finned resistances installedoutside the evaporator.
an turned on during defrost
Defrost type
cked temperature indication (S1) during defrost
ripping of defrost water)
Example:
F16 - F
F17 -
F18 - Lo
F19 -Draining time (d
“0” - Electric defrosting (by resistance), where only the defrost output is activated
“1” - Defrosting by hot gas, where the compressor output and the defrost output are activated
This function prevents that room temperature elevation during defrost be visualized, keeping the last
indication before defrost. The indication is released again in the initial of refrigeration cycle, after fan-
dela (delay to fan return).
Necessary time for dripping, it means, to drain the last water drops of the evaporator. All the outputs
keep turned off. If you do not need this stage, adjust this time for ”zero”.
F20 -
F21 - Maximum time of fan return after draining (fan-delay)
F22 - Fan on with compressor off (refrigeration)
F23 - Fan stopped for high temperature in the evaporato
For security, if the temperature in the evaporator does not reach the adjusted value in F20 or sensor S2
is detached, the fan-delay will happen on the adjusted time in this function.
During the refrigeration cycle, the fan activation may depends on the compressor status.
"0" = The fan is actived only while the compressor is active( this alternative, in some cases, allows great
economy of electric energy).
"1" = The fan is kept on during all refrigeration cycle.
This function cycles the evaporator fan until that room temperature approaches of the temperature
desired in the refrigerating installation project. This preventing high temperature and suction pressures
that can damage the compressor. If the temperature in evaporator pass the adjusted value, the fan is
turned off, reconnecting with a hysteresis of 2 ° C below this value.
Valuable resource when refrigeration equipment that had been inactive for a few days or refrigerated
cases are restocked with its proper merchandise.
Evaporator temperature (S2) for fan return after draining
r
The fan-delay cycle starts after draining. Refrigeration (REFR) starts immediately, since the ambient
temperature is high, but the fan will only be activated after the temperature in the evaporator goes down
below the adjusted value. This is necessary in order to remove the heat that is still present in the
evaporator because of defrosting, thus avoiding its contact with the environment.
F24 - Operation mode of digital input
F25 - Low room temperature alarm (sensor S1)
The digital input can be configured to operate as follows:
“0” - Off;
“1”- Defrost start signal. If this option is configured, the F09 time will not be considered;
“2” - Door status monitor;
“3” - Shuts down all outputs with digital input closed, the instrument shows .
“4” - Shuts down all outputs with digital input open, the instrument shows .
In the event that ambient temperature (sensor S1) is below the adjusted value for this function, blinking
lights will appear on the display and the buzzer (if powered on) will be activated.
F26 - Low temperature alarm hysteresis
Value above which the low temperature alarm is disabled.
*Sensor S3 regulates the end of defrosting for evaporator 2 when function F31 – Operation Mode of
Temperature Sensor S3 is configured as “3” – temperature control of the 2nd evaporator.
F27 - High room temperature alarm (sensor S1)
F28 - High temperature alarm hysteresis
F29 -Alarm inhibition time after powering the instrument on (Sensor S1 alarm)
F31 - Operation mode of temperature sensor S3
In the event that ambient temperature (sensor S1) is above the adjusted value for this function, blinking
lights will appear on the display and the buzzer (if powered on) will be activated.
Value below which the high temperature alarm is powered off.
When the controller is powered on, the alarm will only go off after the time set in this parameter. This
prevents, for instance, the high ambient temperature alarm from being activated before the compressor
has been activated by the controller.
“0” = Off: sensor S3 is disabled.
“1” = Temperature differential for economical Setpoint (using functions F32 and F33): The difference
between the reading of sensor S3 and that of S1 determines which setpoint is going to be used (regular
or economy).
“2” = Control of temperature condenser (using functions F34 to F36): The sensor S3 is used to control
the temperature of the condenser. If the temperature exceeds the adjusted value in F34, both the visual
F30 - Buzzer enabling
“0” = Disables the buzzer
“1” = Enables the buzzer
and sound alarm will go off. If the temperature continues to rise and go over the adjusted value in F35,
both the visual and sound alarms will go off and the control outputs will be powered off.
“3” = Control of the temperature of the 2nd evaporator: In this mode, sensor S1 reads the ambient
temperature inside the refrigerator, sensor S2 in evaporator 1 and sensor S3 in evaporator 2. The
defrosting of evaporator 1 is done through the defrost relay (DEFR), whereas the defrosting of
evaporator 2 will be done through the ventilation relay (FANS). The temperature sensor S2 will
determine the end of defrosting in evaporator 1 and sensor S3 in evaporator 2. The fan-delay period is
not observed in this mode. Defrosting in the evaporators will end when both reach the final defrost
temperature or if the maximum time for defrosting is exceeded.
When the difference between the temperature of sensor 3 and sensor 1 is larger than the adjusted value
in this parameter, the controller starts to operate with setpoint SP1.
When the difference between the temperature of sensor 3 and sensor 1 is smaller than the adjusted
value in this parameter, the controller starts to operate with setpoint SP2 (economical setpoint).
The visual and sound alarm will go off if the temperature is above the adjusted value in this parameter.
F32 - Temperature difference (S3 S1) above which the setpoint SP1 is activated
F33 - Temperature difference (S3 S1) below which the setpoint SP2 is activated (economic
setpoint)
F34 - Sensor S3 temperature (condenser) for visual and audible alarm
F35 -Sensor S3 temperature (condenser) for visual and audible alarm
F36 - Control differential (hysteresis) for sensor S3 (F34 and F35)
The visual and sound alarm will go off if the temperature is above the adjusted value in this parameter
and the activated loads by the outputs will be turned off.
For the loads to be powered back on, the temperature of sensor S3 (condenser) must fall to the adjusted
value in F35 minus the configured value in this parameter.
For both the visual and sound alarm to be powered off, the temperature of sensor S3 (condenser) must
fall to the adjusted value in F34 minus the set up value in this parameter.
5. OPERATION
5.1 - Parameters visualization
a)
b)
c)
d
e)
a)
b)
c) 5.1-b 5.1-c
d)
e)
Press at the same time and for 2 seconds until appear , releasing them after that.
Soon, appears .
Use and to access the desired function.
After selecting the function, press (short touch) to visualize the configured value.
) Press again (short touch) to return the functions menu.
To reset the menu and return to normal operation (temperature indication), press until appear
.
Accessthe function F01 by pressing at the same time and for 2 seconds until appear ,
releasing then afterthat. Soonwill appear , and then press (shorttouch).
Use and to enter the access code (123), and then press .
Select the desired function and visualize the configured value (see itens and ).
Use and to change the value and then press to record the configured value and return
to the functions menu.
To reset the menu and return to normal operation (temperature indication), press until appear
.
5.2 - Parameters configuration
SET
SET
SET
SET
SET
SET
SET