Owner’s Manual
Switched Rack PDU
208/230V, 50/60Hz
AC Input and Output
Model: PDUMH20HVNET
(Series Number: AGPD6684)
Important Safety Instructions 2
Installation 3
Features 6
Technical Support 7
Warranty and Product Registration 7
Español 8
Français 15
Русский 22
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
18-11-320-933681.indb 1 1/25/2019 2:54:55 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be
followed during the installation, operation, and storage of this product.
Failure to heed these instructions and warnings may affect the product
warranty.
The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or line noise
protection for connected equipment.
The PDU is designed for indoor use only, in a controlled environment, away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
Keep indoor ambient temperature between 32°F and 104°F (0°C and 40°C).
The PDU must be installed by a qualified technician only.
Do not attempt to mount the PDU to an insecure or unstable surface.
Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
Never attempt to install electrical equipment during a thunderstorm.
Individual equipment connected to the PDU should not draw more current than the individual
PDU’s outlet’s rating.
The total load connected to the PDU must not exceed the maximum load rating for the PDU.
Do not attempt to modify the PDU, input plugs or power cables.
Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
Do not attempt to use the PDU if any part of it becomes damaged.
Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its
safety or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
18-11-320-933681.indb 2 1/25/2019 2:54:55 PM
3
Installation
RESET
S
TAT
U
S
CONFI
G
A
B
A
RE
SET
STATUS
CONFIG
C
D
Mounting the PDU
The PDU supports five primary mounting configurations: 1U Rack, 0U Rack (Vertical), Wall,
Under-Counter and Reduced-Depth.
Note: Regardless of configuration, the user must determine the fitness of hardware and procedures before mounting. The PDU
and included hardware are designed for common rack and rack enclosure types and may not be appropriate for all applications.
Exact mounting configurations may vary. Screws for attaching the mounting brackets to the PDU are included. Use only the screws
supplied by the manufacturer, or their exact equivalent (#6-32, 3/16" flat head).
1-1
1U Rack Mounting: Use 3 screws
A
to
attach each of the 2 longer mounting
brackets
B
to the PDU as shown. You
can mount the PDU in a recessed
position by attaching the mounting
brackets so they extend beyond the front
panel of the PDU. Mount the PDU in the
rack by inserting 4 user-supplied screws
C
through the mounting brackets
D
and
into the mounting holes of the rack rails.
1-2
0U Rack Mounting: Use 3 screws
A
to
attach each of the 2 shorter mounting
brackets
B
to the PDU as shown. Mount
the PDU vertically by inserting 2 or more
user-supplied screws
C
through the
mounting brackets
D
and into mounting
points in the rack or rack enclosure.
1-3
Wall Mounting: Use 3 screws
A
to
attach each of the 2 shorter mounting
brackets
B
to the PDU as shown. Mount
the PDU to the wall by inserting 2 or
more user-supplied screws
C
through the
mounting brackets
D
and into secure
mounting points.
1-4
Under-Counter Mounting: Use 3 screws
A
to attach each of the 2 shorter
mounting brackets
B
to the PDU as
shown. Mount the PDU under the counter
by inserting 2 or more user-supplied
screws
C
through the mounting brackets
D
and into secure mounting points.
1-1
A
B
C
D
A
B
C
D
A
B
C
D
1-2
1-3
1-4
18-11-320-933681.indb 3 1/25/2019 2:54:57 PM
4
A
B
C
D
1-5
1-5
Reduced-Depth Mounting: Use 3
screws
A
to attach each of the 2 shorter
mounting brackets
B
to the PDU as
shown. Mount the PDU to a stable
surface with the outlets facing upward by
inserting 2 or more user-supplied screws
C
through the mounting brackets
D
and
into secure mounting points.
Installation
15
Connecting the PDU
2-1
Input Power Cord Connection: Attach
the cable clamp to the PDU by inserting
the tabs into available slots on the top
and bottom of the power inlet
A
. Secure
the clamp by sliding it to the right. Attach
the included power cord to the PDU by
inserting the IEC C19 connector
B
of the
power cord into the cable clamp and IEC
C20 power inlet
C
. Install the included
screw
D
on the cable clamp to secure
the power cord connection. Connect the
other end of the input power cord to a
compatible source of AC power, such as
a UPS system, PDU or utility outlet.
Note: The AC power source should not share a circuit with a heavy electrical load.
Note: When connecting the PDU, it should be provided with over-current protection and a maximum 20A branch-rated
over-current protection device.
2-2
NEMA Adapter Connection: This product
includes a plug adapter that adds a NEMA
L6-20P plug to the input power cord. Use
this adapter only if you will be connecting
the PDU to a NEMA L6-20R outlet. Insert
the IEC C19 connector
A
of the adapter
into the IEC C20 connector
B
of the input
power cord. Secure the connection with
the retention bracket
C
by using the
included bolts to fasten the two halves of
the bracket around the connection as
shown. Connect the NEMA L6-20P plug to
a compatible source of AC power
D
, such
as a UPS system, PDU or utility outlet.
CAUTION: To avoid the risk of electric
shock, ensure that the Neutral (L2)
conductor has been identified before
connecting the PDU.
Note: Do not attempt to attach a user-supplied power
cord unless it is certified to be compatible with the input
power source that will be used by the PDU.
B
D
A
C
2-1
2-2
A
C
B
D
A
B
C
18-11-320-933681.indb 4 1/25/2019 2:54:58 PM
5
Installation
A
2-4
15
A
B
C
D
2-3
Equipment Power Cord Connection:
Insert the IEC C14 connectors
A
of the
equipment power cords into the PDU’s
IEC C13 output receptacles
B
. The LED
C
near each output receptacle
illuminates when the receptacle is ready
to distribute live AC power. The digital
load meter
D
will display the total
connected equipment load in amps.
2-3
Networking the PDU
For network configuration instructions, please refer to the WEBCARDLX owner’s manual (PN
93358E) included with this product.
2-4
Optional Cord Retention Procedure:
Use the included C14 sleeves to secure
plugs to receptacles. Attach the sleeve to
the plug, making sure that the pull tabs
A
remain outside the plug and that the
fit is secure. To unplug equipment
properly, use the pull tabs to remove the
plug and sleeve from the receptacle.
18-11-320-933681.indb 5 1/25/2019 2:54:58 PM
6
Features
A
B
AC Input Power Inlet: The IEC 60320 C20 inlet connects to the
detachable AC Input Power Cord.
AC Input Power Cord: The detachable cord has an IEC 60320
C19 connector
A
and an IEC 60320 C20 connector
B
.
AC Input Adapter: The adapter converts the AC input power
cord to a NEMA L6-20P plug. The included retention bracket (not
shown) secures the connection.
IEC 60320 C13 Output Receptacles: During normal operation,
the output receptacles distribute AC power to connected
equipment. When an outlet is live, the associated LED
illuminates.
Digital Load Meter (Ammeter): The total electrical current
drawn by connected equipment is displayed on the meter in
amperes.
Longer Mounting Brackets: Use these brackets to mount the
PDU horizontally in a standard rack or rack enclosure. The
mounting depth can be adjusted by attaching the brackets to
different positions on the PDU.
Shorter Mounting Brackets: Use these brackets to mount the
PDU in a 0U rack, wall or under-counter configuration.
Factory Port: The port is reserved for configuration by factory
authorized personnel only. Do not connect anything to the port.
WEBCARDLX: Allows you to operate this PDU as a managed
network device, accessible via SNMP network management
platform, web browser, SSH or Telnet.
18-11-320-933681.indb 6 1/25/2019 2:54:59 PM
7
Technical Support
Website: www.tripplite.com/support
Warranty and Product Registration
LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and
workmanship for a period of 2 years from the date of initial purchase. If the product should prove defective in material or
workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty can only
be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th
Street, Chicago, IL 60609 USA. Seller will pay return shipping charges. Visit www.tripplite.com/support before sending any
equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR
NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO
THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR
FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES
ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts,
and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or
exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from
jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the
use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as
to the suitability or fitness of these devices for any specific application.
PRODUCT REGISTRATION
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into a drawing for a
chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
FCC Notice, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause
undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense. The user must use shielded cables and connectors with this equipment. Any changes or
modifications to this equipment not expressly approved by Tripp Lite could void the user’s authority to operate this equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique
series number. The series number can be found on the product nameplate label, along with all required approval markings and
information. When requesting compliance information for this product, always refer to the series number. The series number
should not be confused with the marking name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers
buy new electrical and electronic equipment from Tripp Lite they are entitled to:
Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
Send the new equipment back for recycling when this ultimately becomes waste
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
18-11-320-933681.indb 7 1/25/2019 2:54:59 PM
8
Manual del Propietario
PDU Controlable para Rack
Entrada y Salida de CA
208V / 230V, 50/60Hz
Modelo: PDUMH20HVNET
(Número de Serie: AGPD6684)
Instrucciones de Seguridad Importantes 9
Instalación 10
Características 13
Soporte Técnico 14
Garantía 14
English 1
Français 15
Русский 22
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • www.tripplite.com/support
Copyright © 2019 Tripp Lite. Todos los derechos reservados.
18-11-320-933681.indb 8 1/25/2019 2:55:00 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Tripp Lite PDUMH20HVNET Owner's manual

Category
Power distribution units (PDUs)
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI