Hoshizaki KMS-830MLH User manual

Type
User manual
Hoshizaki
“A Superior Degree
of Reliability”
www.hoshizaki.com
Model
KMS-830MLH
Including
Condensing Unit Models
SRK-8H/3
Modular Crescent Cuber
Serenity Series
Hoshizaki America, Inc.
SERVICE MANUAL
Number: 73185
Issued: 7-27-2011
2
IMPORTANT
Only qualied service technicians should install, service, and maintain the
icemaker. No service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual. Failure to service and maintain
the equipment in accordance with this manual may adversely affect safety,
performance, component life, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Phone: 1-800-233-1940 Technical Support
(770) 487-2331
Fax: 1-800-843-1056
(770) 487-3360
E-mail: techsuppor[email protected]
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
•ModelNumber
•SerialNumber
•Completeanddetailedexplanationoftheproblem.
3
CONTENTS
Important Safety Information ................................................................................................. 5
I. Specications ...................................................................................................................... 7
A. Icemaker ....................................................................................................................... 7
B. Condensing Unit ............................................................................................................ 9
II. General Information ..........................................................................................................11
A. Construction .................................................................................................................11
1. Icemaker .................................................................................................................11
2. Condensing Unit .................................................................................................... 12
B. Sequence of Operation ............................................................................................... 13
1. Sequence Cycles and Shutdown ........................................................................... 13
a) 1-Minute Fill Cycle ............................................................................................ 13
b) Initial Harvest Cycle ........................................................................................ 13
c) Freeze Cycle .................................................................................................... 13
d) Pump-Out Cycle ............................................................................................... 14
e) Harvest Cycle ................................................................................................... 14
f) Shutdown .......................................................................................................... 14
2. Sequence Flow Chart ............................................................................................ 15
C. Control Board .............................................................................................................. 16
1. Control Board Layout ............................................................................................. 17
2. LED Lights and Audible Alarm Safeties ................................................................. 18
3. Controls and Adjustments ...................................................................................... 19
a) Default Dip Switch Settings .............................................................................. 19
b) Harvest Timer (S4 dip switch 1 & 2) ................................................................. 19
c) Pump-Out Timer (S4 dip switch 3 & 4) ............................................................. 20
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)......................................... 20
e) Harvest Pump Timer (S4 dip switch 7) ............................................................. 21
f) Factory Use (S4 dip switch 8) ........................................................................... 21
g) Freeze Timer (S4 dip switch 9 & 10) ................................................................ 21
h) Float Switch Control (S5 dip switch 1) ............................................................ 22
i) Rell Counter (S5 dip switch 2 through 5) ......................................................... 22
D. Control Switch ............................................................................................................. 22
III. Technical Information ...................................................................................................... 23
A. Water Circuit and Refrigeration Circuit ........................................................................ 23
B. Wiring Diagram ............................................................................................................ 24
C. Performance Data ....................................................................................................... 26
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualied service technicians
should install, service, and maintain the icemaker. Read the warnings contained
in this booklet carefully as they give important information regarding safety.
Please retain this booklet for any further reference that may be necessary.
4
IV. Service Diagnosis .......................................................................................................... 28
A. Diagnostic Procedure ................................................................................................. 28
B. Control Board Check ................................................................................................... 32
C. Bin Control Check and Cleaning ................................................................................. 33
1. Bin Control Check .................................................................................................. 33
2. Bin Control Cleaning .............................................................................................. 35
D. Float Switch Check and Cleaning ............................................................................... 36
1. Float Switch Check ................................................................................................ 36
2. Float Switch Cleaning ............................................................................................ 37
E. Thermistor Check ........................................................................................................ 38
F. Diagnostic Charts ........................................................................................................ 39
1. No Ice Production ................................................................................................... 39
2. Freeze-Up .............................................................................................................. 40
3. Low Ice Production ................................................................................................ 42
V. Replacement of Components .......................................................................................... 43
A. Service for Refrigerant Lines ....................................................................................... 43
1. Refrigerant Recovery ............................................................................................. 43
2. Brazing .................................................................................................................. 44
3. Evacuation and Recharge (R-404A) ...................................................................... 44
B. Important Notes for Component Replacement ............................................................ 46
VI. Cleaning and Maintenance ............................................................................................. 47
A. Cleaning and Sanitizing Instructions ........................................................................... 47
1. Cleaning Procedure ................................................................................................ 48
2. Sanitizing Procedure - Following Cleaning Procedure ........................................... 50
B. Maintenance ................................................................................................................ 51
C. Preparing the Icemaker for Long Storage ................................................................... 51
5
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the unit.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the unit or
property.
IMPORTANT Indicates important information about the use and care of the
unit.
WARNING
This icemaker should be destined only to the use for which it has been
expressly conceived. Any other use should be considered improper and
therefore dangerous. The manufacturer cannot be held responsible for injury or
damage resulting from improper, incorrect, and unreasonable use.
To reduce the risk of death, electric shock, serious injury, or re, follow
basic precautions including the following:
•Thisunitshouldbedisassembledorrepairedonlybyqualiedservice
personnel to reduce the risk of electric shock, injury, or re.
•Movethecontrolswitchtothe"OFF"positionandturnoffthepowersupplyto
the SRK condensing unit before servicing the KMS or SRK. Place the KMS
disconnect (if applicable) in the off position. Lockout/Tagout to prevent the
power supply from being turned back on inadvertently.
•Donotmakeanyalterationstotheunit.Alterationscouldresultinelectric
shock, injury, re, or damage to the unit.
For KMS
•PowersupplyandgroundconnectionaresuppliedfromtheSRKremote
condensing unit via the wire harness provided. Do not connect the wire
harness leads to an external power source.
•Wireharnessrouting(conduit)anddisconnect(ifrequired)mustmeet
national, state, and local electrical code requirements. Failure to meet these
code requirements could result in death, electric shock, serious injury, re, or
severe damage to equipment.
•THE ICEMAKER MUST BE GROUNDED. Failure to properly ground
the icemaker could result in death, serious injury, or severe damage to
equipment.
6
For SRK
•Electricalconnectionmustbehard-wiredandmustmeetnational,state,and
local electrical code requirements. Failure to meet these code requirements
could result in death, electric shock, serious injury, re, or severe damage to
equipment.
•Theremotecondensingunitrequiresanindependentpowersupplyofproper
capacity. See the nameplate for electrical specications. Failure to use a
properly sized breaker or fuse can result in a tripped breaker, blown fuses, or
damage to existing wiring. This could lead to heat generation or re.
•THE REMOTE CONDENSING UNIT MUST BE GROUNDED. Failure to
properly ground the remote condensing unit could result in death or serious
injury.
7
I. Specications
A. Icemaker
1. KMS-830MLH with SRK-8H
Note: We reserve the right to make changes in specications and design without prior
notice.
AC SUPPLY VOLTAGE 115VAC Supplied by SRK-8H via Factory Supplied
Wire Harness
APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F)
PER 24 HR. Temp.(°F) 50 70 90
lb./day ( kg/day ) 70 *820 (372) 785 (356) 737 (334)
Reference without *marks 80 793 (360) 739 (335) 691 (314)
90 785 (356) *700 (318) 652 (296)
100 776 (352) 689 (312) 607 (275)
SHAPE OF ICE Crescent Cube
ICE PRODUCTION PER CYCLE 13.6 lb. (6.2 kg) 680pcs.
ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F
KMS/SRK COMBINED ELECTRIC W (kWH/100 lb.) 1600(5.50) 1560(4.57)
WATER gal./24HR (gal./100 lb.) 112(16.0) 348(42.4)
CEE TIER LEVEL 1
ENERGY STAR YES
EXTERIOR DIMENSIONS (WxDxH) 30"x16.5"x29" (762x420x737 mm)
EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear)
WEIGHT Net 112 lb. (51 kg), Shipping 137 lb. (62 kg)
CONNECTIONS - ELECTRIC Wire Harness Connection from SRK to KMS
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
-CONDENSATION 3/8" OD Tube
-REFRIGERATION Liquid Line 1/2" Copper Tube Field Connection
Suction Line 5/8" Copper Tube Field Connection
CUBE CONTROL SYSTEM Float Switch
HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROL Timer Controlled, Overflow Pipe, and Float Switch
COOLING WATER CONTROL N/A
BIN CONTROL SYSTEM Mechanical Bin Control
COMPRESSOR In SRK
CONDENSER Air-Cooled Remote Condensing Unit SRK-8H
EVAPORATOR Vertical Type, Stainless Steel and Copper
REFRIGERANT CONTROL Thermostatic Expansion Valve
Headmaster (C.P.R.) in SRK-8H (160 PSIG)
REFRIGERANT CHARGE R404A, 13 lb. 10.7 oz. (6200g)
(Icemaker 0 lb. 7.1 oz. (200g))
(Cond. Unit 13 lb. 3.6 oz. (6000g))
DESIGN PRESSURE High 467PSIG, Low 230PSIG
CONTROL BOARD CIRCUIT PROTECTION High Voltage Cut-Out (Internal)
REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch in SRK-8
Auto-Reset Discharge Line Thermostat in SRK-8
LOW WATER PROTECTION Float Switch
ACCESSORIES -SUPPLIED N/A
-REQUIRED Dispenser Unit or Ice Storage Bin
SRK-8H Remote Condensing Unit
OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
AMBIENT TEMP. 45-100°F
WATER SUPPLY TEMP. 45-90°F
WATER SUPPLY PRESSURE 10-113 PSIG
ENG.F-011.1.0205
8
2. KMS-830MLH with SRK-8H3
AC SUPPLY VOLTAGE 115VAC Supplied by SRK-8H3 via Factory Supplied
Wire Harness
APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F)
PER 24 HR. Temp.(°F) 50 70 90
lb./day ( kg/day ) 70 *791 (359) 761 (345) 711 (322)
Reference without *marks 80 768 (349) 722 (328) 667 (302)
90 761 (345) *690 (313) 635 (288)
100 748 (339) 677 (307) 585 (265)
SHAPE OF ICE Crescent Cube
ICE PRODUCTION PER CYCLE 12.5 lb. (5.7 kg) 680pcs.
ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F
KMS/SRK COMBINED ELECTRIC W (kWH/100 lb.) 1550(5.40) 1470(4.47)
WATER gal./24HR (gal./100 lb.) 110(16.0) 338(42.7)
CEE TIER LEVEL 1
ENERGY STAR YES
EXTERIOR DIMENSIONS (WxDxH) 30"x16.5"x29" (762x420x737 mm)
EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear)
WEIGHT Net 112 lb. (51 kg), Shipping 137 lb. (62 kg)
CONNECTIONS - ELECTRIC Wire Harness Connection from SRK to KMS
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
-CONDENSATION 3/8" OD Tube
-REFRIGERATION Liquid Line 1/2" Copper Tube Field Connection
Suction Line 5/8" Copper Tube Field Connection
CUBE CONTROL SYSTEM Float Switch
HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROL Timer Controlled, Overflow Pipe, and Float Switch
COOLING WATER CONTROL N/A
BIN CONTROL SYSTEM Mechanical Bin Control
COMPRESSOR In SRK
CONDENSER Air-Cooled Remote Condensing Unit SRK-8H3
EVAPORATOR Vertical Type, Stainless Steel and Copper
REFRIGERANT CONTROL Thermostatic Expansion Valve
Headmaster (C.P.R.) in SRK-8H3 (160 PSI)
REFRIGERANT CHARGE R404A, 13 lb. 10.7 oz. (6200g)
(Icemaker 0 lb. 7.1 oz. (200g))
(Cond. Unit 13 lb. 3.6 oz. (6000g))
DESIGN PRESSURE High 467PSIG, Low 230PSIG
CONTROL BOARD CIRCUIT PROTECTION High Voltage Cut-Out (Internal)
REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch in SRK-8H3
Auto-Reset Discharge Line Thermostat in SRK-8H3
LOW WATER PROTECTION Float Switch
ACCESSORIES -SUPPLIED N/A
-REQUIRED Dispenser Unit or Ice Storage Bin
SRK-8H3 Remote Condensing Unit
OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
AMBIENT TEMP. 45-100°F
WATER SUPPLY TEMP. 45-90°F
WATER SUPPLY PRESSURE 10-113 PSIG
ENG.F-011.1.0205
Note: We reserve the right to make changes in specications and design without prior
notice.
9
B. Condensing Unit
1. SRK-8H
Note: We reserve the right to make changes in specications and design without prior
notice.
AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115VAC)
(115VAC Supplied to KMS via Factory Wire Harness)
AMPERAGE 9.1 A ( 5 Min. Freeze AT 104°F / WT 80°F )
MINIMUM CIRCUIT AMPACITY 20 A
MAXIMUM FUSE SIZE 20 A
EXTERIOR DIMENSIONS (WxDxH) 33.6"x23"x22.1" (854x585x562 mm)
DIMENSIONS INCLUDING LEGS (WxDxH) 35.7"x25.4"x37.1" (907x645x942 mm)
EXTERIOR FINISH Galvanized steel
WEIGHT Net 176 lb. (80 kg) Shipping 206 lb. (93 kg)
CONNECTIONS - ELECTRIC Main Power Supply: Permanent Connection
SRK to KMS: Wire Harness Connection
- REFRIGERANT Liquid Line 1/2" Copper Tube Field Connection
Suction Line 5/8" Copper Tube Field Connection
COMPRESSOR Hermetic, Model CS10K6E-PFV-255
CONDENSER Air Cooled, Fin and Tube Type
COMPRESSOR PROTECTION Auto-Reset Overload Protector (Internal)
FAN MOTOR PROTECTION Thermal Protection
REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch
Auto-Reset Discharge Line Thermostat
REFRIGERANT CONTROL Headmaster (C.P.R.) (160 PSIG)
REFRIGERANT CHARGE 13 lb. 10.7 oz. (6200g))
(Condensing Unit 13 lb. 3.6 oz. (6000g))
(Icemaker 0 lb. 7.1 oz. (200g))
DESIGN PRESSURE High 467 PSIG, Low 230 PSIG
OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
AMBIENT TEMP. (Outdoor use) -20-122°F
ACCESSORIES -SUPPLIED Leg 2 pcs
Hex Head Bolt w/Washer M8x16 8 pcs
Hex Nut M8 8 pcs
-REQUIRED Compatible KMS Icemaker
ENG.F-032.1.0205
10
2. SRK-8H3
AC SUPPLY VOLTAGE 208-230/60/3
(115VAC Supplied to KMS via Factory Wire Harness)
AMPERAGE 7.5 A ( 5 Min. Freeze AT 104°F / WT 80°F )
MINIMUM CIRCUIT AMPACITY 20 A
MAXIMUM FUSE SIZE 20 A
EXTERIOR DIMENSIONS (WxDxH) 33.6"x23"x22.1" (854x585x562 mm)
DIMENSIONS INCLUDING LEGS (WxDxH) 35.7"x25.4"x37.1" (907x645x942 mm)
EXTERIOR FINISH Galvanized steel
WEIGHT Net 176 lb. (80 kg) Shipping 206 lb. (93 kg)
CONNECTIONS - ELECTRIC Main Power Supply: Permanent Connection
SRK to KMS: Wire Harness Connection
- REFRIGERANT Liquid Line 1/2" Copper Tube Field Connection
Suction Line 5/8" Copper Tube Field Connection
COMPRESSOR Hermetic, Model CS10K6E-TF5-255
CONDENSER Air Cooled, Fin and Tube Type
COMPRESSOR PROTECTION Auto-Reset Overload Protector (Internal)
FAN MOTOR PROTECTION Thermal Protection
REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch
Auto-Reset Discharge Line Thermostat
REFRIGERANT CONTROL Headmaster (C.P.R.) (160 PSIG)
REFRIGERANT CHARGE 13 lb. 10.7 oz. (6200g))
(Condensing Unit 13 lb. 3.6 oz. (6000g))
(Icemaker 0 lb. 7.1 oz. (200g))
DESIGN PRESSURE High 467 PSIG, Low 230 PSIG
OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
AMBIENT TEMP. (Outdoor use) -20-122°F
ACCESSORIES -SUPPLIED Leg 2 pcs
Hex Head Bolt w/Washer M8x16 8 pcs
Hex Nut M8 8 pcs
-REQUIRED Compatible KMS Icemaker
ENG.F-032.1.0205
Note: We reserve the right to make changes in specications and design without prior
notice.
11
II. General Information
A. Construction
1. Icemaker
Spray Tube
Control Box
Drier
Hot Gas
Valve
Float Switch
Pump Motor
Control Switch
Thermostatic Expansion Valve
Inlet Water Valve
Cleaning Valve
Spray Guide
High-Side Service Valve
Low-Side Service Valve
Liquid Line Valve
Evaporator
Insulation
Fuse (KMS)
Bin Control Cover
Bin Control Extension Bracket
Bin Control
Bin Control Insulation
Strainer
Insulation
Left Side
Panel
12
2. Condensing Unit
Headmaster (C.P.R.)
Control Box
Hot Gas Valve
Condenser Fan Motor
High-Side Service Valve
Low-Side Service Valve
Compressor)
Condenser
Liquid Line Valve
Receiver
Accumulator
Discharge Line Thermostat
High-Pressure Switch
Fuse (SRK)
Control Box Cover
Left Side Panel
Louver Panel
Right Side Panel
Top Panel
13
B. Sequence of Operation
1. Sequence Cycles and Shutdown
The steps in the sequence are as outlined below. When power is supplied, CB red
"POWEROK"LEDandCBgreen"BCCLOSED"LEDturnson.IfCByellow"BCOPEN"
LED is on, the unit will not start. In this case, clear ice away from the BC actuator paddle
in the dispenser unit/storage bin area. A 5-second delay occurs at startup. Note that the
order of the green sequence LEDs from the outer edge of CB is 1,4, 3, 2.
a) 1-Minute Fill Cycle
LED 4 is on. WV and X11 relay energize. After 1 minute, CB checks for a closed F/S. If
F/S is closed, the harvest cycle begins. If open, WV remains energized through additional
1-minute ll cycles until water lls the water tank and closes F/S. This serves as a low
water safety to protect PM.
b) Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV and X11 relay remain energized, Comp, FMR, HGVs, and
X10 relay energize. CBmonitors the warming of the evaporator via the thermistor located
on the suction line. When the thermistor reaches 48°F (9°C), CB reads a 3.9kΩ signal
from the thermistor and turns harvest termination over to the harvest timer. For details,
see"II.C.3.b)HarvestTimer(S4dipswitch1&2)."Thepump-outtimer(S4dipswitch
3 & 4) acts in place of the harvest timer during cycles with a pump-out. For details, see
"II.C.3.c)Pump-OutTimer(S4dipswitch3&4).WVandX11relayareenergizedduring
harvest for a maximum of 6 minutes or the length of harvest minus 50 seconds (harvest
pump timer (S4 dip switch 7)), whichever is shorter. 50 seconds before the harvest timer
terminates, LED 4 turns off, WV and X11 relay de-energize.
Harvest Pump Timer: LEDs 1,3, and 2 are on. LED3turns on and PM energizes.
Fordetails,see"II.C.3.e)HarvestPumpTimer(S4dipswitch7)." NOTICE! S4 dip
switch 7must remain in the factory default position of 7 on. Otherwise, PM will not
energize during the last 50 seconds of harvest. When the harvest timer terminates,
the harvest cycle is complete. CB checks the position of F/S and proceeds to the next
cycle if it is closed, or calls for a 1-minute ll cycle if it is open. The minimum total time
allowed by CB for a complete harvest cycle is 2 minutes.
c) Freeze Cycle
LED 1 is on. Comp, FMR, and PM remain energized. LLVs energize, HGVs and
X10relay de-energize. CB 5-minute short cycle protection timer prevents CB from
monitoring F/S for the rst 5 minutes of freeze. After the 5-minute short cycle protection
timer terminates, CB turns freeze termination over to F/S. As ice builds on the evaporator,
the water level in the water tank lowers. The freeze cycle continues until F/S opens. There
is a 15 second delay before CB acknowledges an open F/S and terminates the freeze
cycle.
14
d) Pump-Out Cycle
LEDs 1, 3, and 2 are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on.
Fordetails,see"II.C.3.c)Pump-OutTimer(S4dipswitch3&4)."NOTICE! Do not
adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this position on this
model prevents the pump motor from rotating in the pump-out (reverse) direction.
Comp and FMR remain energized, HGVs energize. LLVs de-energize. PM de-energizes
for 2 seconds, then energizes in reverse direction for 10 seconds. Water is removed
from the bottom of the water tank and sent down the drain through the check valve. At
the same time, water ows through the small F/S tube to power ush F/S. When the
pump-out timer terminates, pump-out is complete.
The pump-out timer and pump-out frequency control are factory set, and generally no
adjustmentis required. However, where water quality is bad and the icemaker needs
a longer and/or more frequent pump-out, the pump-out timer and pump-out frequency
control can be adjusted. The pump-out timer (S4 dip switch 3 & 4) can be set to have a
10or20secondpump-out.Fordetails,see"II.C.3.c)Pump-OutTimer(S4dipswitch3&
4)."Thepump-outfrequencycontrol(S4dipswitch5&6)canbeadjustedasshownin
thetablebelow.Fordetails,see"II.C.3.d)Pump-OutFrequencyControl(S4dipswitch
5&6)."Timingoftherstpump-outisdependentonS4dipswitch5&6settings.See
the table below.
S4 Dip Switch Setting
Pump-Out
Frequency
1st Pump-Out
No. 5 No. 6
OFF OFF Every cycle After 2nd freeze cycle
ON OFF Every 2 cycles After 3rd freeze cycle
OFF ON Every 5 cycles After 6th freeze cycle
ON ON Every 10 cycles After 11th freeze cycle
e) Harvest Cycle
Sameastheinitialharvestcycle.See"II.B.1.b)InitialHarvestCycle."
Note: Unit continues to cycle until BC is satised or power is turned off. The unit always
restarts at the 1-minute ll cycle.
f) Shutdown
WhenBCisactivated(BCopen),yellow"BCOPEN"LEDturnson.Theunitthenshuts
down as outlined in the table below.
Cycle at Bin
Control Activation
Shutdown
Fill Cycle 15 seconds after activation.
Harvest Cycle At the end of the harvest cycle, or up to 15 seconds into the freeze cycle if activated
at the end of the harvest cycle.
Freeze Cycle 15 seconds after activation if activated at least 15 seconds before the 5-minute short
cycle protection timer terminates. Otherwise, at the end of the next harvest cycle.
Legend: BC–bin control; CB–control board; Comp–compressor; FMR–fan motor-remote;
F/S–oat switch; HGVs–hot gas valves (KMS and SRK); LLVs–liquid line valves
(KMS and SRK); PM–pump motor; WV–inlet water valve; X10–pump motor
direction relay; X11–X10 control relay
15
2. Sequence Flow Chart
F/S check
1 to 3-min. timer in control
(S4 dip switch 1 & 2)
"G" Control Board Sequence Flow Chart
1. 1-Minute Fill
Cycle
Cycle Steps
2. Harvest Cycle
•WVtime:6min.orthelengthofharvestminus50sec.
(S4 dip switch 7), whichever is shorter. DO NOT
ADJUST S4 dip switch 7.
•Maximumharvesttime:20min.
Thermistor
in control
3. Freeze Cycle
•Minimumfreezetime:5min.
•Maximumfreezetime:freezetimersetting
(S4 dip switch 9 & 10)
F/S in control
4. Pump-Out Cycle
•Factorysetforevery
10th cycle
(S4 dip switch 5 & 6)
•PMstopsfor2sec.,
then reverses for
10/20 sec.
(S4 dip switch 3 & 4)
DO NOT ADJUST S4
dip switch 3 and 4 to
3 off and 4 on.
WV energized
F/S open
WV continues
Comp energized
FMR energized
HGVs energized
Thermistor temperature
reaches 48°F (9°C)
(3.9 kΩ or less).
Harvest timer starts.
F/S open
Comp continues
FMR continues
PM continues
LLVs energized
HGVs de-energized
F/S closed
Comp continues
FMR continues
PM de-energized for 2 sec., then
energized in reverse
direction for 10/20 sec.
HGVs energized
LLVs de-energized
F/S check
Startup begins
here after 5-sec.
delay
If F/S is open, Comp and FMR de-energize and cycle returns to 1-Minute Fill Cycle
5-min. timer in
control
F/S closed
F/S open or freeze
timer terminates
50 sec.
PM energized
WV de-energized
Harvest Pump
Timer
KMS-830MLH with SRK-8H/3
Legend:
BC–bin control
Comp–compressor
FMR–fan motor-remote
F/S–oat switch
HGVs–hot gas valves (KMS and SRK)
LLVs–liquid line valves (KMS and SRK)
PM–pump motor
WV–inlet water valve
1. Bin Full
Shutdown Delay:
•Fill Cycle – 15 sec. after activation.
•Harvest Cycle – At the end of the harvest cycle, or up to 15 sec. into the
freeze cycle if activated at the end of the harvest cycle.
•Freeze Cycle – 15 sec. after activation if activated at least 15 sec. before
the 5-min. short cycle protection timer terminates.
Otherwise, at the end of the next harvest cycle.
Shutdown
andRestart
BC Operation
BC open
Green"BCCLOSED"LEDoff
Yellow"BCOPEN"LEDon
Yellow"BCOPEN"LEDcontinues
All components de-energized
2. Icemaker Off
All components
de-energized.
3. Ice Level Lowered
Ice level lowered. No ice
pressing against BC actuator
paddle. Icemaker starts at
"1.1-MinuteFillCycle."
To 1 above
BC closed
Green"BCCLOSED"LEDon
Yellow"BCOPEN"LEDoff
Components Energized when the Control Switch is in the "WASH" Position
The"WASH"positiononthecontrolswitchisusedwhencleaningandsanitizingtheunit.Wheninthe"WASH"position,
power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of
the evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the
inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not re-start when the
controlswitchisplacedinthe"ICE"position.
16
C. Control Board
•A Hoshizaki exclusive solid-state control board is employed in Hoshizaki Crescent
Cubers.
•All models are pretested and factory set.
•Foracontrolboardcheckprocedure,see"IV.B.ControlBoardCheck."
NOTICE
1. The control board is fragile; handle very carefully.
2. The control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the unit before handling or replacing the control board.
3. Do not touch the electronic devices on the control board or the back of the
control board.
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,
because the same style connector is used for all three.
K3 = Thermistor
K4 = Bin Control
K5 = Float Switch
5. Always replace the whole control board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
17
1. Control Board Layout
"G" Control Board
Part Number 2A3792-01
"G" Control Board
• "ALARM RESET" Button
• "OUTPUT TEST" Button
(used to test relays on control board)
• K3 Connector (white)
Harvest Control
(thermistor)
• K4 Connector (red)
Bin Control
• K5 Connector (black)
Float Switch
• Part Number
• K1 Ten-Pin Connector
Pins #1 through #10
#1, 9-LED 1:
Compressor Relay (1 phase),
Magnetic Contactor (3 phase),
and Remote Fan Motor
#2-LED 2 on: Hot Gas Valves
(KMS and SRK) and X10 Relay in
Fill and Harvest
#3-LED 2 off: Liquid Line Valves
(KMS and SRK)
#4-LED 3 off: Pump Motor in
Freeze
#5-LED 3 on: Pump Motor
in Harvest Pump Timer and
Pump-Out
#6-LED 4: Inlet Water Valve and
X11 Relay
# 7, 1 0 115VAC Power Supply
#8 Open
• Bin Control Switch
Open LED (yellow)
• S4 Dip Switch
• Bin Control Switch
Closed LED (green)
Alarm Buzzer
• Power LED (red)
(lights when
10.5VAC is supplied
to K2 connector)
• LED 2 (X2 Relay)
LED 2 on:
K1 Connector Pin #2
LED 2 off:
K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on:
K1 Connector Pin #5
LED 3 off:
K1 Connector Pin #4
• LED 4 (X4 Relay)
K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K2 Connector
Control Transformer (10.5VAC)
• S5 Dip Switch
• Relay LEDs (green)
(indicate which relays
and K1 connector pins
are energized)
18
2. LED Lights and Audible Alarm Safeties
At startup, a 5-second delay occurs while the control board conducts an internal timer
check.Abeepoccurswhenthecontrolswitchismovedtothe"ICE"position.
The red LED indicates proper control voltage and remains on unless a control voltage
problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup
as listed in the table below. Note that the order of the LEDs from the outer edge of the
controlboardis1,4,3,2.Fordetails,see"II.B.SequenceofOperation."
Sequence Step LED
Energized
Components
Time LEDs are On
Min. Max. Avg.
1-Minute Fill Cycle 4 X10 Relay, WV 1 minute
Harvest Cycle 1, 4, 2 Comp, FMR, WV,
HGVs
2 minutes 20 minutes 3 to 5 minutes
Harvest Pump Timer 1, 3, 2 Comp, FMR, PM,
HGVs
0 seconds 50 seconds harvest pump timer
setting
Freeze Cycle 1 Comp, FMR, PM,
LLVs
5 minutes freeze timer
setting
30 to 35 minutes
Pump-Out Cycle 1, 3, 2 Comp, FMR, PM,
HGVs
10 seconds 20 seconds
The built-in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
Type of Alarm Notes
1 High Evaporator Temp.
(temperature > 127°F (53°C))
Check for harvest problem (stuck HGVs), hot water
entering unit, stuck HM, or shorted thermistor.
2 Harvest Backup Timer
(harvest > 20 min. for two cycles
in a row)
Check for open thermistor, HGVs not opening, TXV or
LLVs leaking by, low charge, or inefficient Comp.
3 Freeze Timer
(freeze > freeze timer setting for
two cycles in a row)
Timer is factory set using S4 dip
switch 9 & 10
Check for F/S stuck closed (up), WV leaking by, HGVs
leaking by, PM not pumping, TXV not feeding properly,
LLVs not opening, low charge, HM not bypassing, or
inefficient Comp.
Toresettheabovesafeties,pressthe"ALARMRESET"buttonwiththepowersupplyon.
6 Low Voltage
(92Vac±5% or less)
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
7 High Voltage
(147Vac±5% or more)
Legend: Comp–compressor; FMR–fan motor-remote; F/S–oat switch; HGVs–hot gas
valves (KMS and SRK); HM–headmaster (C.P.R.); LLVs–liquid line valves (KMS
and SRK); PM–pump motor; TXV–thermostatic expansion valve; WV–inlet water
valve;
19
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6
ON
S4
S5
3. Controls and Adjustments
NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-233-1940.
a) Default Dip Switch Settings
The dip switches are factory set to the following positions:
S4 Dip Switch
Model
S4 Dip Switch No.
1 2 3 4 5 6 7 8 9 10
KMS-830MLH
OFF OFF OFF OFF ON ON ON OFF OFF OFF
S5 Dip Switch (Do Not Adjust)
Model
S5 Dip Switch No.
1 2 3 4 5
KMS-830MLH OFF OFF OFF OFF OFF
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet
and the control board reads the thermistor's 3.9 kΩ signal. The harvest timer is factory
set, and generally no adjustment is required. However, a setting longer than the factory
setting may be advised in cases where harvest needs to be prolonged for extra cleaning.
Before changing this setting, contact your local Hoshizaki distributor or Hoshizaki
Technical Support at 1-800-233-1940 for recommendations. Keep in mind that setting the
harvest timer to a longer setting decreases 24-hour production.
The pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles
withapump-out.Fordetails,see"II.C.3.c)Pump-OutTimer(S4dipswitch3&4)."
S4 Dip Switch Setting Time
(seconds)
No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 120
ON ON 180
Freeze Timer (9 & 10)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
Harvest Pump Timer (7) (Do not adjust)
Factory Use (8)
S4 Dip Switch
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6
ON
S4
S5
Do Not Adjust
S5 Dip Switch
Rell Counter
(2 through 6)
Float Switch
Selector (1)
20
c) Pump-Out Timer (S4 dip switch 3 & 4)
NOTICE
Do not adjust S4 dip switch 3& 4 to 3 off and 4 on. Otherwise, pump motor
does not rotate in the pump-out direction.
When a pump-out is called for, the pump motor de-energizes for 2seconds, then
energizes for 10/20 seconds in reverse direction. Water is removed from the bottom of
the water tank and sent down the drain through the check valve. At the same time, water
ows through the small F/S tube to power ush F/S. The pump-out drains the water tank
for the time determined by the pump-out timer. The pump-out timer also acts in place
of the harvest timer during cycles with a pump-out. The pump-out timer is factory set,
and generally no adjustment is required. However, where water quality is bad and the
icemaker needs a longer pump-out, the pump-out timer can be adjusted. The pump-out
timer (S4 dip switch 3 & 4) can be set to have a 10 or 20 second pump-out.
S4 Dip Switch Setting Time (seconds)
Inlet
Water
Valve
No. 3 No. 4
T1
T2
OFF OFF 10 150 closed
ON OFF 10 180 closed
OFF ON 10 120 open
ON ON 20 180 closed
T1: Time to drain the water tank
T2: Harvest timer at pump-out
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)
The pump-out frequency control is factory-adjusted to drain the water tank every
10cycles, and generally no adjustment is required. However, where water quality is bad
and the icemaker needs a more frequent pump-out, the pump-out frequency can be
adjusted as shown in the table below.
Timing of the rst pump-out is dependent on S4 dip switch 5 & 6 settings. See the table
below.
S4 Dip Switch Setting
Pump-Out
Frequency
1st Pump-Out
No. 5 No. 6
OFF OFF Every cycle After 2nd freeze cycle
ON OFF Every 2 cycles After 3rd freeze cycle
OFF ON Every 5 cycles After 6th freeze cycle
ON ON Every 10 cycles After 11th freeze cycle
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Hoshizaki KMS-830MLH User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI