ICM Controls ICM289 Installation guide

Type
Installation guide
ICM
289
FURNACE CONTROL MODULE
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com
LII357
1. Turnoffelectricalpoweratcircuitbreakerordisconnect
2. Removeaccesspanel.
3. Verifypowerisoffatcontrolboardusingavoltmeter.
4. Removecontrolboxcover.(G20Runitswillnothaveacontrolboxcover).
5. Markanddisconnectwiresconnectedtothecontrolboard.
6. Removeblowercontrolboard.
7. InstallICM289blowercontrolboard.
8. ReconnectwirestoICM289controlboard.
9. Thequickconnectterminallabeled24VontheICM289is3/16”.Ifyourwire
forthe24Vterminalhada1/4””quickconnectterminalyoumustreplaceit
withthewireprovided.
10.Cutexistingwiresfromterminal24V,stripback5/8”andwirenutto
wireprovidedinkit.Connectterminatedendofprovidedwiretothe24V
terminalontheICM289blowercontrolboard.
11. Placeblowerpurgetimejumperoncorrectpins.
12.Placemech/electjumpertocorrectposition.
13.Reinstallthecontrolboxcover(allunitsexceptforG20R).
14.Replaceaccesspanel.
15.Turnonelectricalpowerfortheunit.
16.Testoperationperunitinstallationinstructions.
INSTALLATION
PACKAGE CONTENTS
(1)ICM289blowercontrol
(1)3/16”quickconnectterminatedwire
(1)Wirenut
FEATURES
• Controls inducer fan motor, blower fan and monitors limit switches
• Microprocessor based design
• Functions with all 24 VAC thermostats
SAFETY CONSIDERATIONS
Onlytrainedpersonnelshouldinstallorserviceheatingequipment.When
workingwithheatingequipment,besuretoreadandunderstandall
precautionsinthedocumentation,onlabels,andontagsthataccompany
theequipment.Failuretofollowallsafetyguidelinesmayresultindamageto
equipment,severepersonalinjuryordeath.
APPLICATION
ThisreplacementblowercontrolkitisforuseonG20,G20R,G23andG26seriesunits.TheICM289functionsthesameastheotherBCC(BCC1,BCC2,andBBC3)
controlboards.
ACCESSORY KIT
for an extended period
WireNut
ExistingWires
New3/16”TerminalWire
Replacement of
3/16” 24V Wire
SPECIFICATIONS
•Voltage Range:Line(98-132VAC)@60Hz
•Cool blower:20A@120VAC
•Heat blower:20A@120VAC
•Inducer motor:5A@120VAC
•Cool blower On Delay:1second
•Cool blower Off Delay:1second
•Heat blower On Delay:45seconds
•Heat blower Off Delay:90,150,220,270seconds
REPLACES
ReplacesallLennoxBCC1,BCC2andBCC3circuitboards,including48K98
and45K48.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION!
Use caution when installing and servicing the furnace to avoid and control
electrostatic discharge; ESD can impact electronic components. These
precautions must be followed to prevent electrostatic discharge from hand
tools and personnel. Following the precautions will protect the control from
ESD by discharging static electricity buildup to ground.
1. Disconnectallpowertothefurnace.Donottouchthecontrolorthewiring
priortodischargingyourbody’selectrostaticchargetoground.
2. Togroundyourself,touchyourhandandtoolstoaclean,metal(unpainted)
furnacesurfacenearthecontrolboard.
3. Servicethefurnaceaftertouchingthechassis.Yourbodywillrechargewith
staticelectricityasyoushufeyourfeetormovearound,andyoumust
regroundyourself.
4. Regroundyourselfifyoutouchungroundeditems.
5. Beforehandlinganewcontrol,regroundyourself;thiswillprotectthe
control.Storeusedandnewcontrolsinseparatecontainersbeforetouching
ungroundedobjects.
6. ESDdamagecanalsobepreventedbyusinganESDservicekit.
TERMINAL DESCRIPTIONS
WIRING DIAGRAMS
  • Page 1 1
  • Page 2 2

ICM Controls ICM289 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI