  • Hello! I've reviewed the installation instructions for the EYE Lighting Turbo.Mini 100W/50W LED Floodlight. This document covers important aspects such as safety precautions, mounting, aiming, electrical wiring and features including different CCT options. I am ready to assist with any questions about operating or installing this device.
  • What is the input voltage for this floodlight?
    What is the recommended distance to avoid prolonged staring into the light?
    What is the maximum pole height?
    What is the maximum projected area?
    What are the options for CCT?
Eye Lighting Australia Pty Ltd All Rights Reserved.
For the latest product informaon visit www.eyelighng.com.au
Tools :
Turbo.Mini LED FLOODLIGHT Options
Turbo.Mini 100W/50W LED FLOODLIGHT
INSTALLATION INSTRUCTIONS
The luminaire with clear optic should be
positioned so that prolonged staring into
the luminaire at a distance 3m is not expected
Caution: Electric Shock
Non-professionals are
not allowed to operate
3 6
*Standard Model
IP66 IK09
Outdoor Indoor
LED PH2
Pg. 1
Product
Code Beam Angle CCT Weight
Turbo.Mini
100W/50W 4000K Max 5.5kg
Symmetrical 9
3000K Max 5.5kg
5000K Max 5.5kg
Pole Height
Projected Area
(m2)
(m)
Max 8m
Max 8m
Max 8m
201 m2
201 m2
201 m2
Input: 200V - 240Vac (50Hz), Ta = -35°C~ 60°C
Back View Side View
Front View
Model
185700
185705 Symmetrical 9
Symmetrical 9
185710
Turbo.Mini
100W/50W
Turbo.Mini
100W/50W
*
*Standard Default Model
PRODUCT DIMENSION
334.3
318.0
250.8
301.6
170.2
221.6
270.1
180.1
128.8
40.5
30.0
Dimensions in (mm)
125.0
35.0
R5.0 Ø20
180.1
TURBO.MINI-08.03.23
Incorrect
MOUNTING INSTRUCTIONS Pg. 2
All Rights Reserved.
75°
85°
120°
Floor Ceiling Wall
AIMING INSTRUCTIONS
Aiming
Angle
Indicator
Aiming:
2 x toothed gear locks secure the mounting bracket allowing rotation with 5° increment.
1
2
sides.
3
0Nm
3
30Nm
ELECTRICAL WIRING
L N L N
Loop in Loop out
AC loop-in
Factory Wired
Lesser Chamber on the LED Fixture
Open the rear Lesser Chamber lid: 4 x M4 Screws (3Nm)
AC loop-in: Flex round cable up to 3 x 2.5mm²
Connect Loop-in: L, ,N terminals with single-phase 220-240 V 50 Hz
AC input
AC loop-out (If applicable): Flex round cable up to 3 x 2.5mm² Connect
Loop-out (If applicable): L, , N terminals to the next
Tighten the cable glands and replace lid of the Lesser Chamber: 4 x M4
Screws (3Nm)
Note
t test
OUTPUT SW1 SW2 SW3
100% OFF OFF ON
75% OFF ON OFF
50% ON OFF OFF
Set Value Dimmer Table
TURBO.MINI-08.03.23
/