Eaton NRX Digitrip 1150 Owner's manual

Type
Owner's manual
Effective September 2013 Series NRX
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
1600 NRX SUB-TITLE IMAGE (12/15/2010)
Series NRX, Type NF Frame
ANSI, UL1066, UL489 / IEC, IZMX16, IZM91
Series NRX, Type RF Frame
IEC, IZMX40
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010)
Instructions apply to:
Effective September 2013
2
EATON www.eaton.com
Instructional Leaet IL01301064E Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
TABLE OF TABLES
Description page
Table 1. Digitrip 1150/1150i Trip Units Functions ...............................6
Table 2. Current Protection Functions .....................................6
Table 3. Protective Relay Functions ........................................7
Table 4. Alarms .......................................................8
Table 5. Current Voltage Frequency Metering Data ............................9
Table 6. Power and Energy Metering Data ...................................9
Table 7. Metered Power Quality System Data ...............................10
Table 8. Event Recording ...............................................11
Table 9. Event Recording continued .......................................12
Table 10. Series NRX/Digitrip Ground Fault Sensing Modes ....................18
Table 11. Series NRX NF Frames and Rating Plugs ...........................34
Table 12. Series NRX RF Frames and Rating Plugs ...........................35
TABLE OF CONTENTS
Description page
Section 1: Introduction ..................................................5
Section 2: Specification Tables ............................................6
Section 3: General description ...........................................13
Section 4: Principles of operation .........................................16
Section 5: Display Module Interface .......................................20
Section 6: Programming Settings .........................................24
Section 7: Test procedures ..............................................28
Section 8: Record keeping ..............................................31
Section 9: Trip unit battery ...............................................33
Section 10: Frame ratings and rating plugs ..................................34
Section 11: Maintenance Mode feature ....................................35
Section 12: References .................................................36
Section 13: Time-current curves ..........................................36
Section 14: Communications .............................................37
Appendix A: Zone Selective Interlocking Examples ...........................38
Appendix B: Troubleshooting .............................................40
Appendix C: Electrical Specifications ......................................42
Appendix D: Display, Indicators and Menus .................................43
Appendix E: Power and Power Factor Sign Conventions .......................92
Appendix F: Setpoint Defaults and Worksheet ...............................94
3
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
TABLE OF FIGURES
Description page
Figure 1. Digitrip 1150 Trip Unit With Rating Plug and Frame Module ...............5
Figure 2. NRX NF Circuit Breaker with Digitrip 1150 ............................5
Figure 3. Series NRX NF Frame Phase Current Sensor ........................13
Figure 4. Trip Unit Installation on a Frame Module ...........................14
Figure 5. Installation of the Rating Plug into the Trip Unit .......................14
Figure 6. Trip Unit Locking Tabs ...........................................15
Figure 7. Frame Module With Trip Unit Removed .............................15
Figure 8. Block Diagram With Breaker Interface ..............................16
Figure 9. Series NRX RF Frame Neutral Sensor ..............................18
Figure 10. Series NRX NF Frame Neutral Sensor .............................18
Figure 11. Trip Unit and Display Module .....................................20
Figure 12. Trip Unit Indicators (LSIG style with Maintenance Mode) ..............20
Figure 13. Display Module Push Buttons ...................................21
Figure 14. Long Delay Time Setting Bands for I
2
t settings ......................24
Figure 15. Short Delay Time Setting Bands - Flat and I
2
t .......................25
Figure 16. Functional Test Kit .............................................28
Figure 17. Connections for Single-Pole, Single-Phase Current Tests ...............30
Figure 18. Connections for Single-Phase Current Tests With Two Poles in Series ....30
Figure 19. Typical Trip Function Record Nameplate ............................31
Figure 20. Automatic Trip Operation Record .................................31
Figure 21. Typical Performance Test Record Form .............................32
Figure 22. Digitrip Battery Installation ......................................33
Figure 23. CAM Module ................................................37
Figure 24. Example of Interlocking with Three Zones ..........................39
Figure 25. ZSI Example With Mains (M1, M2) and Tie (T) Circuit Breakers .........39
Figure 26. IEC Sign Convention Phasor Diagram .............................92
Figure 27. IEEE Sign Convention Phasor Diagram .............................93
Figure 28. IEEE Direct Mathematical Sign Convention Phasor Diagram ...........93
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
4
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064E
WARNING
DANGEROUS ELECTRICAL VOLTAGE!
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON
EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE INJURY CAN
RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS
VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.
ALWAYS FOLLOW SAFETY PROCEDURES. EATON IS NOT LIABLE FOR
MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.
Before commencing any installation
Disconnect the power supply of the device
Ensure that devices cannot be accidentally closed or
powered up
Verify isolation from the supply, Earth, and short circuit
Cover or enclose neighboring units that are live
Danger if circuit breaker mechanism spring is charged!
Discharge spring
Follow the engineering instructions of the device concerned
Only suitably qualified personnel in accordance with
applicable national work safety regulations may work on this
device/system
Before installation and before touching the device ensure
that you are free of electrostatic charge
Connecting cables and signal lines should be installed so
that inductive or capacitive interference do not impair the
automation functions
Suitable safety hardware and software measures should
be implemented for the I/O interface so that a line or wire
breakage on the signal side does not result in undefined
states in the automation devices and create an unwanted
action in the circuit breaker
WARNING
OBSERVE ALL RECOMMENDATIONS, NOTES, CAUTIONS, AND
WARNINGS RELATED TO THE SAFETY OF PERSONNEL AND
EQUIPMENT. OBSERVE AND COMPLY WITH ALL GENERAL AND
LOCAL HEALTH AND SAFETY LAWS, CODES, AND PROCEDURES.
Deviation of the mains voltage from the rated value
must not exceed the tolerance limits given in the
specifications, otherwise this may cause malfunction and
dangerous operation
Emergency stop devices complying with IEC 60204-
1, EN 60204-1 must be in all operating modes of the
automation devices. Unlatching the emergency-stop
devices must not cause restart
The electrical installation must be carried out in
accordance with the relevant regulations (e.g. with
regard to cable cross section size, fuses, and earthing
(PE)
All work relating to transport, installation, commissioning
and maintenance must be carried out by qualified
personnel in accordance with applicable national work
safety regulations
Note: The recommendations and information contained herein are
based on experience and judgement, but should not be considered to
be all inclusive or to cover every application or circumstance that may
arise.
If you have any questions or need further information or
instructions, please contact your local Eaton representative or
visit www.Eaton.com.
5
EATON www.eaton.com
Section 1: Introduction
Figure 1. Digitrip 1150 Trip Unit With Rating Plug and Frame
Module
This instruction book specifically covers the application of
Digitrip 1150 and 1150i trip units installed in the Series NRX-NF
frame or Series NRX-RF frame circuit breakers.
The styles of trip units consists of the Digitrip 1150 for
compliance with UL/ANSI standards and the 1150i for the IEC
standards applications.
The Digitrip 1150 and 1150i trip units may be applied on either
50 and 60 Hz systems.
The Digitrip 1150/1150i trip unit system consists of 3 parts, the
frame, the trip unit and the display. The frame module is fixed
to the circuit breaker. This module is matched to the frame
interruption rating and sensors of the circuit breaker and should
not be changed. The trip unit module contains the Digital
Signal Processor (DSP) that performs the measurements and
calculations for protection and metering. The display module
is the user interface and requires external control power to
operate.
The Digitrip 1150/1150i trip units work with either the current
sensors of the NF or RF frame Series NRX circuit breakers. The
appropriate rating plug must be matched to the frame and style
of circuit breaker that the trip unit is applied to.
Effective September 2013
Instructional Leaet IL01301064EOperating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Figure 2. NRX NF Circuit Breaker with Digitrip 1150
6
EATON www.eaton.com
Table 1. Digitrip 1150/1150i Trip Units Functions
Trip Unit Type Digitrip 1150 Digitrip 1150i
Ampere range NF Frame 400 –1200A
RF Frame 800 – 3200A
NF Frame 400 – 1600A
RF Frame 800 – 4000A
Ordering catalog number N11RLSIG, N11RLSI, N11RLSIA, N11LSIG,
N11LSI, N11LSIA
N11IEC, N11IECEF, N11RIEC, N11RIECEF
Available styles LSI, LSIA, LSIG LSI, LSIG
System frequency 50 or 60 Hz 50 or 60 Hz
RMS sensing
Relays - Programmable for alarms or trips 2 2
Communications
Display - LCD Color Graphic
Table 2. Current Protection Functions
Current Protection and Coordination Digitrip 1150/1150i Step Size
Protection
Fixed rating plug (I
n
)
Overtemperature trip
Long delay protection Slope
Long delay pickup
I
2
t, I
4
t
IEEE - MI, IEEE - VI, IEEE - EI l
IEC-A, IEC-B, IEC-C k
50 – 100% x (I
n
) 5%
Long delay time @6 x (I
r
) I
2
t
Long delay time @6 x (I
r
) I
4
t
Time Dial Multiplier IEC slope
Time Dial Multiplier IEEE slope
Long delay thermal memory (only on I
2
t and I
4
t slopes)
2 – 24 seconds
1
5 seconds
0.05 – 1
0.1 – 5
Enable / Disable
500 ms
500 ms
0.05
0.01
Short delay protection Short delay slope
Short delay pickup
Short delay time at 8 x (I
r
) I
2
t
Short delay time flat
Short delay zone interlock
Flat, I
2
t
200 – 1000% x (I
r
)
0.10 – 0.50 seconds
0.10 – 0.50 seconds
(option)
50%
5 ms
5 ms
Instantaneous protection Instantaneous pickup
OFF setting
Making current release
200 – 1200% x (I
n
)
50%
Neutral protection
4th pole or external neutral trip
50, 100, 150, 200%
Ground (earth) fault
protection (option)
Ground fault pickup
OFF position
Ground fault delay at 0.625 x
(I
r
) I
2
t
Ground fault delay flat
Ground fault zone interlock
Ground fault thermal memory
24 – 100% x
(I
n
)
j
k
0.10 – 0.50 seconds
0.10 – 0.50 seconds
(option)
Enable / Disable
1%
50 ms
50 ms
Maintenance mode
protection (ARMS)
(option)
Setting
Contact for remote Indication of mode
Maintenance mode pickup
On, Off / remote enable
NF Frame: 1000A
– 5000A = Pickup
RF Frame: 4000A – 20000A = Pickup
1000A
4000A
Current unbalance
protection trip
Current unbalance pickup
Current unbalance time delay
Off, 5% – 25%
0 – 240 seconds
1%
1 second
Phase loss protection -
current based trip
Phase loss setting
Phase loss time delay
On, Off
1 – 30
seconds 1 second
j Digitrip 1150 ANSI/UL versions are limited to 1200A to comply with UL and NEC® standards.
k Only available on Digitrip 1150i versions
l Only available on Digitrip 1150 versions
Section 2: Specication Tables
Effective September 2013
Instructional Leaet IL01301064E Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Table 3. Protective Relay Functions
Protection Digitrip 1150/1150i Step Size
Voltage Protection
Voltage trip protection (Line to Line) Enable, Disable
Undervoltage trip Off, 90 - 670 V 1 volt
Undervoltage time 1 - 250 seconds 1 second
Overvoltage trip Off, 180 - 720 V 1 volt
Overvoltage time 1 - 250 seconds 1 second
Voltage unbalance trip Off, 5% - 50% 1%
Voltage unbalance time 1 - 250 seconds 1 second
Frequency Protection
Frequency trip protection Enable, Disable
Underfrequency trip Off, 45 - 65 Hz 0.1 Hertz
Underfrequency time 0.20 - 5.0 seconds 0.02 seconds
Overfrequency trip Off, 45 - 65 Hz 0.1 Hertz
Overfrequency time 0.20 - 5.0 seconds 0.02 seconds
Power Quality Protection
Reverse Power Pickup Off, 1 - 65500 kW 1 kW
Reverse Power Time Delay 1 - 60 seconds 1 second
7
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064EOperating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
8
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Table 4. Alarms
Alarm Type Digitrip 1150/1150i Step Size
Alarms - Current
High load alarm setting
Off, 50% - 100% x
(I
r
)
5%
High load alarm time delay 1 - 60 seconds 1 second
Amp unbalance alarm setting
Off, 5% - 25% x
(I
r
)
1%
Amp unbalance alarm time delay 0 - 240 seconds 1 second
Neutral ampere alarm setting Off, 10% - 100% 5%
Neutral ampere alarm time delay 1 - 60 seconds 1 second
Ground alarm Off, 10% - 100% Style LSIG or LSIA only 1%
Ground alarm time delay 100 ms
Alarms - Voltage
Voltage Alarms Enable, Disable
Undervoltage alarm Off, 90 - 670V 1 volt
Undervoltage alarm time 1 - 250 seconds 1 second
Overvoltage alarm Off, 180 - 720V 1 volt
Overvoltage alarm time 1 - 250 seconds 1 second
Voltage unbalance alarm Off, 5% - 50% 1 %
Voltage unbalance alarm time 1 - 250 seconds 1 second
Phase rotation alarm Off, ABC, CBA
Alarms - Frequency
Frequency Alarms (based on Van) Enable, Disable
Underfrequency alarm Off, 45 - 65 Hz 0.1 Hz
Underfrequency alarm time 0.20 - 5.0 seconds 20 ms
Overfrequency alarm Off, 45 - 65 Hz 0.1 Hz
Overfrequency alarm time 0.20 - 5.0 seconds 20 ms
Alarms - Power Quality
Power Alarms Enable, Disable
kW Demand Setting off, 1- 65500 kW 1 kW
kW Demand Time Delay 1 - 60 seconds 1 second
kVA Demand Setting off, 1 - 65500 kVA 1 kVA
kVA Demand Time Delay 1 - 60 seconds 1 second
Reverse Power Setting off, 1 - 65500 kW 1 kW
Reverse Power Time Delay 1 - 60 seconds 1 second
Power Factor Setting off, 50% - 95% 5 %
Power Factor Time Delay 1 - 60 seconds 1 second
THD Setting off, 10% - 30% 1 %
THD Time Delay 1 - 60 seconds 1 second
Alarms - System Diagnostics
Status/long pickup LED
Cause of trip LEDs j
Alarm LED
Operation count alarm
Off, 1 - 12500 counts
1 count
j Four cause of trip LEDs indicate LONG, SHORT, INST, or GROUND trip. Making Current Release protection trip is indicated by the Instantaneous LED
Table 5. Current Voltage Frequency Metering Data
Current Metering Units Accuracy Notes
IA, IB, IC, IN, IG Amperes ±1% of
Reading j
IA, IB, IC, IN, IG
(min.)
Amperes ±1% of
Reading jl
Group values held until reset
IA, IB, IC, IN, IG
(max.)
Amperes ±1% of
Reading jl
Group values held until reset
IA, IB, IC, IN, IG
(demand)
Amperes ±1% of
Reading jl
Window 5 - 60 minutes
Sliding or Fixed
IA, IB, IC, IN, IG
(demand max)
Amperes ±1% of
Reading jl
Group values held until reset
Current Metering Range Notes
Current Unbalance --- 0 - 100%
Voltage Metering
Units Accuracy Notes
VAB, VBC, VCA Volts ±1% of
Reading k
Line to Line Voltage
VAB, VBC, VCA
(min)
Volts ±1% of
Reading k
VAB, VBC, VCA
(max)
Volts ±1% of
Reading k
VAN, VBN, VCN Volts ±1% of
Reading k
Line to Neutral Voltage
VAN, VBN, VCN
(min)
Volts ±1% of
Reading k
VAN, VBN, VCN
(max)
Volts ±1% of
Reading k
Frequency
Metering Units Accuracy Notes
Frequency Hz ±0.2 Hz of
Reading k
Range is 20 to 255 Hz
Frequency (min)) Hz ±0.2 Hz of
Reading k
Value held until reset
Frequency (min)) Hz ±0.2 Hz of
Reading k
Value held until reset
j Accuracy applicable for 5 to 100% of I
n
and current will start metering at 2% of rating plug
k Applicable to the voltage range of 34 to 690 Vac.
l All currents share a common configured demand window. All powers share a common configured demand window.
9
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Table 6. Power and Energy Metering Data
Power Metering Units Accuracy Notes
Power kW ±2% of Reading
jk
Approximately 1- second
update
kVA kVA ±2% of Reading
jk
Approximately 1- second
update
kvar kvar ±2% of Reading
jk
Approximately 1- second
update
Demand kW kW ±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max). kW kW ±2% of Reading
jkl
Value held until reset
Demand kVA kVA ±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max). kVA kVA ±2% of Reading
jkl
Value held until reset
Demand kvar kvar ±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max) kvar kvar ±2% of Reading
jkl
Value held until reset
Power Metering Range Notes
PF (power factor) --- 0 - ±1.00
PF (min. absolute) --- 0 - 1.00 Value held until reset
PF (max. absolute) --- 0 - 1.00 Value held until reset
Energy Metering Units Accuracy Notes
Energy kWh kWh ±2% of Reading
jk
Total
Energy fwd kWh kWh ±2% of Reading
jk
Forward
Energy rev kWh kWh ±2% of Reading
jk
Reverse
kVAh kVh ±2% of Reading
jk
Net Reactive
Metering
Configuration
Settings Notes
Reverse Feed
Configuration
Normal or Reverse Line to load is normal and
the default setting
Energy Log Interval Off, 5, 10, 15, 20, 30, 60
minutes
Table 7. Metered Power Quality System Data
Harmonics Range Notes
Crest Factor IA 1.0 - 64 Peak divided by the RMS
Crest Factor IB 1.0 - 64
Crest Factor IC 1.0 - 64
Crest Factor IN 1.0 - 64
THD IA 0 - 6300% Total Harmonic Distortion
THD IB 0 - 6300%
THD IC 0 - 6300%
THD IN 0 - 6300%
Individual Harmonic
Current Data
IA Harmonics from 1 to 31 0 - 100% Phase A current
IB Harmonics from 1 to 31 0 - 100% Phase B current
IC Harmonics from 1 to 31 0 - 100% Phase C current
IN Harmonics from 1 to 31 0 - 100% Neutral current
Individual Harmonic Line to
Line Voltage Data
VAB Harmonics from 1 to 31 0 - 100%
VBC Harmonics from 1 to 31 0 - 100%
VCA Harmonics from 1 to 31 0 - 100%
Individual Harmonic Line to
Neutral Voltage Data
VAN Harmonics from 1 to 31 0 - 100%
VBN Harmonics from 1 to 31 0 - 100%
VCN Harmonics from 1 to 31 0 - 100%
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
10
EATON www.eaton.com
Table 8. Event Recording
Data
Number of
Events Saved
in Digitrip
Trip Unit j
Number of
Events Saved
in CAM
Modules jl Data Captured
Voltage and
Current Waveforms
Captured in
Digitrip Trip Unit j
Voltage and
Current Waveforms
Captured in CAM
Modules jl
Summary 60 200 _ _
Power Up Event Type
Time Stamp
Setpoint Download
TIme Adjustment
Trip
Alarm
Enter Test Mode
Exit Test Mode
Test Complete
Plug Changed
Enter Maintenance Mode
Exit Maintenance Mode
Closed by Communications
Opened by Communications
Trip (Prime)
20 k 100 max n
3 5
Long Delay Time Stamp
Status: Primary, Secondary and Cause
Currents: IA, IB, IC, IN, IG
Voltage: VAB, VBC, VCA, VAN, VBN, VCN
Power: Watts, VAR, VA
THD: IA, IB, IC
Demand: IA, IB, IC, IN, Watts, VAR, VA
Frequency
Operations Count
Temperature
Power Factor
IA, IB, IC, IN, IG,
VAB, VBC, VCA
10 cycles - 6 pre-event
and 4 post event
IA, IB, IC, IN, IG,
VAB, VBC, VCA
10 cycles - 6 pre-event
and 4 post event
Short Delay
Instantaneous
Ground
Phase Loss
Current Unbalance
Over Voltage
Under Voltage
Voltage Unbalance
Reverse Power
Over Frequency
Under Frequency
Maintenance Mode
Neutral
Trip (Basic) Time Stamp
Status: Primary, Secondary and Cause
Currents: IA, IB, IC, IN, IG
Voltage: VAB, VBC, VCA, VAN, VBN, VCN
Power (Watts, VAR, VA)
THD: IA, IB, IC
Demand: IA, IB, IC, IN, Watts, VAR, VA
Frequency
Operations Count
Temperature
Power Factor
_ _
Missing Plug
Communication Initiated
Test Initiated
Over-Temperature
Making Current Release
On-demand Harmonic
Waveform Capture
1 1 Currents: IA, IB, IC, IN, IG
Voltage: VAB, VBC, VCA, VAN, VBN, VCN)
IA, IB, IC, IN, IG,
VAB, VBC, VCA, VAN,
VBN, VCN
1 cycle
IA, IB, IC, IN, IG,
VAB, VBC, VCA, VAN,
VBN, VCN
1 cycle
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Effective September 2013
Instructional Leaet IL01301064E
11
EATON www.eaton.com
j All event buffers and waveforms are stored in a serial sequence retaining the most recent data.
k Data buffers from the event are retained independent of whether waveform data was or could be captured at the time of the event.
l Data is approximate for most styles of CAM module. Consult the specific CAM module literature for more information.
m Discrete logging data is not stored and not viewable in the display module.
n Prime and Basic events share the same memory space. The maximum number stored will dependent upon the maximum number received of each event.
Table 9. Event Recording (continued)
Data
Number of
Events Saved
in Digitrip
Trip Unit j
Number of
Events Saved
in CAM
Modules jl Data Captured
Voltage and
Current Waveforms
Captured in
Digitrip Trip Unit j
Voltage and
Current Waveforms
Captured in CAM
Modules jl
Alarm (Prime)
20 k 100 max n
3 8
Long Delay Pick-up Time Stamp
Status: Primary, Secondary and Cause
Currents: IA, IB, IC, IN, IB
Voltage: VAB, VBC, VCA, VAN, VBN, VCN
Power: Watts, VAR, VA
THD: IA, IB, IC
Demand: IA, IB, IC, IN, Watts, VAR, VA
Frequency
Operations Count
Temperature
Power Factor
IA, IB, IC, IN, IB,
VAB, VBC, VCA
6 cycles
IA, IB, IC, IN, IG,
VAB, VBC, VCA
6 cycles
Current Unbalance
Ground Fault
Incomplete Contact Close
High Load
Neutral Current
Phase Rotation
Over Voltage (Line to Line)
Under Voltage (Line to Line)
Voltage Unbalance (Line to Line)
Over Frequency
Under Frequency
Low Power Factor
Reverse Power
Apparent Power Demand
Power Demand
THD
Alarm (Basic) Time Stamp
Status: Primary, Secondary and Cause
_ _
Calibration Alarm
Setpoint Fault
RAM Fault
ROM Fault
RTC Error
NV Memory Error
Watchdog Timer Operation
ADC Calibration Error
Long Delay Pick-up (test mode)
Ground Fault (test mode)
Trip Actuator Fault
Operations Count
Low Control Voltage
Trend Logging
0 m
50 Forward Active Energy
Reverse Active Energy
Apparent Energy
_ _
Energy Log
Time Adjustment 20 200 Previous Time
New Time
_ _
Real Time Clock Change
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
12
EATON www.eaton.com
Section 3: General description
Series NRX Circuit Breakers
Series NRX circuit breakers are tripped automatically on
overload and fault current conditions by the combined action of
three components:
1. The current sensors, which provide lower-level signals to the
Digitrip trip unit.
2. The Digitrip trip unit, which measures the signals from the
sensors, and when the levels and time delay settings are
exceeded will provide a tripping signal to the trip actuator.
3. The low-energy trip actuator, which converts electrical
energy to mechanical energy to trip the circuit breaker.
The automatic overload and short circuit tripping characteristics
for a specific circuit breaker are determined by the rating plug
and the selected functional protection settings.
When the functional protection settings are exceeded, the
Digitrip unit supplies a trip signal to the trip actuator. As
a result, all tripping operations initiated by the protection
functions are performed by its internal circuitry. There is no
mechanical or direct magnetic action between the primary
current and the mechanical tripping parts of the circuit breaker,
and external control voltage is not required
for basic current protection functionality.
WARNING
IMPROPER POLARITY CONNECTIONS ON THE TRIP ACTUATOR COIL
TO THE DIGITRIP TRIP UNIT WILL DEFEAT THE OVERLOAD AND
SHORT CIRCUIT PROTECTION, WHICH COULD RESULT IN PERSONAL
INJURY. OBSERVE POLARITY MARKINGS ON THE TRIP ACTUATOR
LEADS IF LEADS OR CONTACTS ARE EVER REMOVED.
Low-energy trip actuator
The mechanical force required to initiate the tripping action of
Series NRX circuit breakers is provided by a special low-energy
trip actuator. The circuit breaker mechanism assembly contains
a mechanism-actuated reset lever and a trip lever to actuate the
tripping action of the circuit breaker.
Digitrip trip units
The Digitrip 1150/1150i trip units are circuit breaker subsystems
that provide the protective functions of a circuit breaker. The
trip units are in removable housings, installed in the breaker,
and can be replaced or upgraded in the field by the customer.
All trip unit models are microprocessor-based AC protection
devices that provide true RMS current sensing for the proper
coordination with the thermal characteristics of conductors
and equipment. The primary function of the trip unit is circuit
protection. The Digitrip unit analyzes the secondary current
signals from the circuit breaker current sensors. When current
level and time delay settings are exceeded, the Digitrip trip unit
will send an initiating trip signal to the trip actuator of the circuit
breaker.
The Digitrip trip unit system consists of 3 modules, the
frame, the trip unit and the display. The frame module is
fixed to the circuit breaker. This module is matched to the
frame interruption rating of the circuit breaker and should
not be changed. The trip unit module contains the Digital
Signal Processor (DSP) that performs the measurements and
calculations for protection and metering. The display module
is the user interface and requires external control power to
operate. The trip unit does not require the display module to be
operational to perform any of the protective functions.
The current sensors consist of two coils; one coil on an iron
core and one coil on an air core (Rogowski) (Figure 3). As
current begins to flow through the circuit breaker, the iron core
coil generates a secondary current which powers the trip unit.
At the same time, the air core coil provides signal values which
are processed by the electronic circuitry.
Figure 3. Series NRX NF Frame Phase Current Sensor
Protection
Each trip unit is completely self-contained and requires no
external control power to operate its current protection system
functions. It operates from power and current signal levels
derived through sensors mounted in the circuit breaker. To
satisfy the protection needs of any specific installation, the
exact selection of the available protection function adjustments
should be set by the user.
Ground fault sensing schemes
When the trip unit includes ground fault protection features, the
distribution system characteristics (such as system grounding,
number of sources, and number and location of ground points)
must be considered along with the manner and location in
which the circuit breaker is applied to the system.
The Digitrip trip unit can use one of three modes of sensing
to detect ground fault currents: residual, source ground, and
zero sequence. 3-pole and 4-pole Series NRX circuit breakers
can accom modate all three types of sensing. A jumper
connection on the circuit breaker secondary contact inputs is
used to select either internal residual ground fault sensing or an
external sensor for source ground or zero sequence schemes.
If a Communications Adapter Module (CAM) is used the jumper
is located on the CAM module not on the circuit breaker
terminal contacts.
If there is no jumper from contacts 19 to 20 of the circuit
breaker the trip unit will be programmed for a residual ground
fault scheme. The jumper from 19 to 20 programs the trip unit
for either a source ground or zero sequence configuration. In
all three schemes, the proper current sensor is required ( Table
10).
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Effective September 2013
Instructional Leaet IL01301064E
13
EATON www.eaton.com
Mode of trip and status information
All trip units have a tricolored light-emitting diode (LED), labeled
STATUS that could light green, red or orange. The LED will blink
green approximately once each second to indicate the trip unit
is operating normally. This Status LED will blink at a faster rate
if the Digitrip is in a pick-up or overload condition.
The Digitrip has the ability to detect a problem with nonvolatile
memory or if the trip actuator coil is an open circuit, or if there
is a circuit breaker mechanism problem. Depending upon the
state and the status of power to the trip unit when a problem is
detected, the Status LED will light red or flash red or orange.
There are LEDs on the face of the trip units (for INST, LONG,
SHORT, and GROUND) that flash red to indicate the cause or
trip mode for an automatic trip operation. A battery located in
the Frame Module maintains the trip indication until the Reset/
Battery Test button is pushed. The battery is good if the LED
lights green when the Battery Check button is pushed (see
Section 9: Trip unit battery).
ote:N The trip unit provides all protection functions regardless of the
status of the battery. The battery is only needed to maintain the cause
of trip indication during a power loss condition.
Trip Unit Installation
The Digitrip trip units are designed as a field replaceable
unit. To mount the Digitrip trip unit align it with the two guide
grooves of the Series NRX circuit breaker. Keep it parallel with
the receiving, molded deck plate. Press the unit into the circuit
breaker until the trip unit seats firmly into the receiving housing
and the two latching tabs click into place.
Figure 4. Trip Unit Installation on a Frame Module
Rating Plug Installation
Insert the rating plug into the cavity on the right side of the trip
unit. Wiggle the plug slightly to help align the pins on the plug
with the sockets in the cavity. The plug should engage with a
slight insertion force when it is approximately 3/16-inch (4 mm)
above the Digitrip. When this occurs, tighten the mounting
screw to its stop positions. 4 turns should be sufficient.
CAUTION
IF A RATING PLUG IS NOT INSTALLED IN THE TRIP UNIT, THE UNIT
WILL INITIATE A TRIP WHEN IT IS ENERGIZED.
Figure 5. Installation of the Rating Plug into the Trip Unit
ote:N Rating plugs are keyed to circuit breaker frame groups. If the
wrong rating plug is used it will not engage and properly tighten down
to the circuit breaker frame, see Section 10: Frame ratings and rating
plugs for the tables of available rating plugs.
CAUTION
DO NOT FORCE THE RATING PLUG INTO THE CAVITY.
Use a 1/8-inch (3 mm) wide screwdriver to tighten the
mounting screw and secure the plug and the trip unit to the
circuit breaker.
CAUTION
THE RATING PLUG SCREW SHOULD BE TIGHTENED ONLY UNTIL IT
STOPS. DO NOT USE A LARGE SCREWDRIVER. A 1/8-INCH (3 MM)
WIDE SCREWDRIVER BLADE IS ADEQUATE.
Trip unit/rating plug removal
To remove the rating plug from the trip unit, use a 1/8-inch (3
mm) wide screwdriver to loosen the screw. It will take about
four turns to release it. Pry up the top or bottom side lips of the
rating plug to pull it away from the trip unit.
To remove the trip unit from the circuit breaker’s Frame Rating
Module, break the factory seal, deflect the two locking tabs,
and pull to release the unit from the frame module mounting
plate. Pull the unit to disengage the molded, 24-pin connector
from the frame module printed circuit board. (See Figure 6 and
Figure 7.)
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
14
EATON www.eaton.com
Figure 6. Trip Unit Locking Tabs
Figure 7. Frame Module With Trip Unit Removed
Wiring
The internal components of the circuit breaker and how
they are wired internally and externally to the circuit breaker
secondary contacts are shown in the master connection
diagrams. See “Section 12: References” for the number of
the Technical Document that contains the Series NRX circuit
breaker master connection diagrams.
Plexiglass cover
A clear, tamper-proof, plexiglass cover fits on the Digitrip.
This cover allows the settings to be viewed but not changed
(except by authorized personnel). The plexiglass cover meets
applicable tamper-proof requirements. Security is ensured by
the insertion of a standard meter seal wire through the thumb
screw holes. The plexiglass cover denies access to the SAVE
pushbutton to prevent unauthorized access to change settings.
Auxiliary voltage requirements
When the circuit breaker is wired for external 24 Vdc input,
it will provide an auxiliary voltage supply so that the Digitrip
graphic Liquid Crystal Display (LCD) will be functional. A
Digitrip 1150 trip unit without auxiliary voltage will not display
any data on the display. The burden of the trip unit is 6 watts.
If a CAM module is used the 24 Vdc input is connected to the
CAM terminal block. The CAM will then provide an isolated
supply for the trip unit which allows the external power supply
to be used for both trip unit power and communications power.
ote:N All current protection features will be active when the current
breaker load current reaches approximately the following levels.
Single Phase Three Phase
NF Frame 200A 50A
RF Frame 400A 100A
Display
The Digitrip 1150 trip unit is equipped with a color graphic Thin
Film Transistor Liquid Crystal Display (TFT-LCD). The display
has 1/4 VGA resolution capability for a sharp color and graphical
interface to the user. The display has LED back lighting
capability which incorporates 3 redundant LEDS in parallel.
The display has a power saver feature that after 10 minutes of
inactivity will blank the screen. The power saver mode will then
flash a display showing the present screen menu for 2 seconds,
and then turn blank for 10 seconds. If any pushbutton is
pressed the display will go back to the screen that was diplayed
last before the 10 minute inactivity period occurred.
Standards
The Digitrip 1150/1150i trip units are listed by Underwriters
Laboratories Inc. for use in Series NRX-NF and Series NRX-
RF circuit breakers. These same units are also listed by the
Canadian Standards Association (CSA).
All Digitrip units have also passed the IEC 60947-2 test program
that includes EMC testing according to Appendix F. As a result,
all units meet the low voltage and EMC directives and carry the
CE mark.
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Pry Locking
Tabs Open
15
EATON www.eaton.com
16
EATON www.eaton.com
Section 4: Principles of operation
General
All models of trip units are designed for industrial circuit
breaker environments where the ambient temperatures can
range from –20°C to +85°C but rarely exceed 70°C to 75°C. If,
however, temperatures near the trip unit exceed this range,
the trip unit performance may be degraded. In order to ensure
that the tripping function is not compromised due to an over-
temperature condition, the microcomputer chip has a built-in
over-temperature protection feature, factory set to trip the
circuit breaker if the trip unit temperature is excessive. If over-
temperature is the reason for the trip, the LONG LED will flash
on and off with an orange color.
The Digitrip uses an integrated circuit that includes a Digital
Signal Processor (DSP) to perform its numeric and logic
functions. A block diagram of the major components of
operation of the trip unit are shown in Figure 8.
All sensing and tripping power required to operate the current
protection functions is derived from the current sensors in
the circuit breaker. The signals from these sensors provide the
correct input information for the protection functions, as well as
tripping power, whenever the circuit breaker is carrying current.
The DSP microcomputer continually digitizes the signals from
the sensors even when the circuit breaker is open. This data is
used to calculate the true RMS current values, which are then
continually compared with the protection function settings and
other operating data stored in the memory. The trip unit then
determines whether to initiate protection functions, including
tripping the circuit breaker using the trip actuator.
Trip and operation indicators
The LEDs on the face of the trip unit, shown in Figure 12,
flash red or orange to indicate the reason for any automatic trip
operation. Following an automatic trip operation, the backup
battery continues to supply power to the LEDs. An LED pulse
circuit is provided to reduce battery burden and will flash a trip
LED approximately once every four seconds. It is therefore
important to view the unit for at least five seconds to observe a
flashing cause of trip indicator.
Following a trip operation, push the Reset/Battery Test button to
turn off the cause of trip LED.
A Status LED, shown in Figure 12, indicates the operational
status of the trip unit. Once the load current through the circuit
breaker exceeds approximately 50A (NF Frame) or 100A (RF
Frame) three phase power, the green LED will flash on and off
once each second to indicate that the trip unit is energized and
operating properly.
Note: A steady green STATUS LED typically indicates a low level
of circuit breaker load current indicating that the trip unit is not fully
powered up.
Alarm LED
An orange Alarm LED is provided to indicate real-time alarm
conditions are existing on the power system. See Appendix
D: Display, Indicators and Menus for the programing of these
alarms. If an unusual condition is detected within the Digitrip’s
hardware or firmware, this LED will light with a message on the
display indicating the type of alarm.
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
PT
Module
Com
Com
+
24 V dc
+
24 V dc
Analog
Circuits
Voltage Signals
Figure 8. Block Diagram With Breaker Interface
Trip LED
The Trip LED is illuminated upon any trip condition. It is also
a real-time display and incorporates the circuit breaker’s 52b
auxiliary switch (also called MCR switch) input for its logic.
Pushing the Reset pushbutton or closing the circuit breaker will
clear this LED.
Making current release (MCR)
All trip units styles have a making current release function.
This safety feature prevents the circuit breaker from being
closed and latched-in on a faulted circuit. The NRX NF Frame is
equipped with a nonadjustable release that is preset to pick up
at a peak current of 45,000A. The release level of the RF Frame
is preset to 36,000A for 1600A frame ratings, 56,000A for
2000A and 2500A frame ratings, and 90,000A for 4000A frame
ratings. The level is set by the sensors, frame module, and the
trip unit of the circuit breaker.
The MCR is enabled only for the first two cycles following the
initial circuit breaker closing operation. The MCR circuit will trip
the circuit breaker instantaneously with no intentional delay and
flash the instantaneous (INST) red LED.
High instantaneous
All Series NRX NF frame modules have a high instantaneous
withstand trip feature. Some Series NRX RF frame modules
will have the high instantaneous feature if specified.
This element is always active even when the customer
instantaneous adjustment is set to the OFF position. The high
instantaneous is a separate analog peak detecting circuit that
is set in the frame rating module of the circuit breaker. It will
initiate a trip at a current peak set to match the withstand rating
of the circuit breaker frame. A trip from this feature will be
indicated by flashing the red instantaneous (INST) LED. For
additional information regarding high instantaneous trip levels,
consult the time current curves for the R-Frame breaker located
in publication AD0130100SE.
Ground current sensing schemes
Depending upon the installation requirements, alternative
ground fault sensing schemes may be dictated. The Digitrip
1150 trip units can accommodate one of three different
schemes of sensing.
Ground fault alarm
A ground fault alarm is one of many possible programmable
alarms and can provide an early warning of a ground fault
condition through an alarm LED. In addition, this trip unit can
be programmed to energize an alarm relay upon this condition.
The alarm relay will reset automatically if the ground current is
less than the Ground Alarm Pickup setting.
The Digitrip 1150 provides a greater flexibility in the use of
ground current alarms. If the Ground Alarm option has been
enabled on the LSIA, RLSIA, LSIG, or RLSIG style trip units,
a red Alarm LED will indicate the presence of ground current
when it is in excess of the Ground Alarm setting. See Table
4 for the specifications on all settings for all of the alarms. A
programmed alarm relay (Relay 1 or 2) will be energized when
the ground current continuously exceeds the ground alarm
setting for a time in excess of 0.1 second. The alarm relay will
reset automatically if the ground current reduces to a value less
than the ground fault pickup setting.
Ground fault trip alarm
On LSIG and RLSIG style trip units, Relay 1 and Relay 2 can be
programmed as a trip relay to indicate when the circuit breaker
trips on a ground fault. You must then push the Reset button in
order to reset the relay contact.
Residual ground current sensing
Residual sensing is the standard mode of ground fault sensing
in Series NRX circuit breakers. This mode uses one current
sensor on each phase conductor and one on the neutral for a
four-wire system. If the system neutral is grounded, but no
phase to neutral loads are used, the Digitrip trip unit includes
all of the components necessary for ground fault protection.
This mode of sensing vectorially sums the outputs of the three
or four individual current sensors. If the vectorial sum is zero,
then no ground fault exists. Residual ground fault sensing
features are adaptable to main and feeder circuit breaker
applications. If an external neutral sensor is used with reverse
feed breaker applications, the proper polarity of the neutral
needs to be considered.
CAUTION
ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION
DRAWINGS. IF THE NEUTRAL SENSOR CONNECTIONS ARE
INCORRECT, A NUISANCE TRIP MAY OCCUR.
To ensure correct ground fault equipment performance and
compliance, conduct field testing as required to comply with
country or regional requirements.
Source ground sensing
The ground return method is usually applied when ground fault
protection is desired only on the main circuit breaker in a simple
radial system. This method is also applicable to double-ended
systems where a mid-point grounding electrode is employed.
For this mode of sensing, a single current sensor mounted on
the equipment-bonding jumper will directly measure the total
ground current flowing in the grounding electrode conductor.
Applying the source ground jumper will enable this protection.
ote:N When using a Communication Module (see Section 14:
Communications), the enabling of source ground mode is done via the
position of the jumper located on this module.
Zero sequence sensing
Zero sequence sensing, also referred to as vectorial
summation, is applicable to mains, feeders, and special
schemes involving zone protection.
17
EATON www.eaton.com
Effective September 2013
Instructional Leaet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Figure 9. Series NRX RF Frame Neutral Sensor
Figure 10. Series NRX NF Frame Neutral Sensor
Zone selective interlocking (optional)
The zone selective interlocking function is an option when
ordering the Series NRX circuit breaker. The circuit breakers
that are built with the zone interlocking function ordered will
have three wires (Zout, Zcom, Zin) connected to secondary
contacts (27, 28, 29). These contacts can then be wired for
zone interlocking to other circuit breakers above and below in
the other zones.
Table 10. Series NRX/Digitrip Ground Fault Sensing Modes
Ground (Earth)
Sensing Method Sensor Style IZMX Type Code
Breaker Secondary
Contacts - if no
CAM module
Optional
CAM Module
Jumper Position
Neutral Input
Contacts
Ground Sensor
Input Contacts
Residual NF Frame 5721B76G12 IZMX-CT16-N No jumper Disable position 15 ,16 -
Residual RF Frame 70C1718G11 IZMX-CT40-N No jumper Disable position 15 ,16 -
Source ground 70C1527G14 IZMX-CT-NGS Jumper 19 to 20 Enable position - 17 ,18
Zero sequence 70C1527G14 IZMX-CT-NGS Jumper 19 to 20 Enable position - 17 ,18
ote:N This information applies to only trip units with ground fault or ground protection.
Zone selective interlocking is available on the SHORT delay and
GROUND fault protection functions. The zone interlocking, if
supplied, is wired via a single set of three wires labeled Zone
In (Zin) and Zone Out (Zout) along with a zone common wire.
The zone selective interlocking function has combined the logic
interlocking of SHORT delay and GROUND fault in one signal.
A zone out signal is sent whenever the ground fault pickup is
exceeded or when the short delay value of 2 x (Ir) is exceeded.
This provides maximum selectivity for coordination with larger
upstream circuit breakers. Zone selective interlocking provides
the fastest possible tripping for faults within the zone of
protection of the circuit breaker and yet also provides positive
coordination among all circuit breakers in the system (mains,
ties, feeders, and downstream circuit breakers). When zone
interlocking is employed, a fault within the zone of protection of
the breaker will:
Trip the affected circuit breaker immediately.
Send a signal to upstream Digitrip units to restrain from
tripping immediately. The restraining signal causes the
upstream circuit breakers to follow their set coordination
time delays, so that the service is interrupted to the
isolated fault area only while the fault is cleared in the
shortest time possible.
For an example of how zone selective interlocking may be used,
see Appendix A: Zone Selective Interlocking Examples of
this manual.
Diagnostics indicator—circuit breaker/trip unit
The Digitrip trip unit has LEDs for diagnostic reasons. The
Status LED is bicolored. A normally powered trip unit will flash
the green status at a 1 second repetition rate. The Status LED
will flash red and orange if a problem is encountered in any of
the following scenarios:
Internal self test problem
MCR auxiliary switch or circuit breaker mechanism is in an
improper state
Trip actuator (TA) coil circuit is open
This LED status is indication of an issue that needs attention
as soon as possible (see Appendix B: Troubleshooting). In
addition, the Digitrip units provide a relay contact that can
provide a diagnostic alarm signal externally.
18
EATON www.eaton.com
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Effective September 2013
Instructional Leaet IL01301064E
Potential Transformer module
The PT (potential or voltage transformer) module is external to
the circuit breaker on the NRX NF frame. It may be externally
mounted or internally mounted and wired in the NRX RF frame
circuit breaker to the line side circuit breaker terminals. It
provides the signals to measure the system voltage. These
input signals are used to measure voltage and calculate; power,
energy, and if selected, perform protection functions on voltage
and frequency. The PT module is a three-phase, three-wire
input and a four-wire output step-down transformer with a wye
to wye configuration.
The power and energy metering and protection functions are
calculated with the convention that power flow is from line to
load through the circuit breaker. This assumes the top side
conductor to be the line side. If the distribution system is
configured such that the bottom side is the incoming side, the
power values will indicate reverse power. This can be changed
via setpoint programming.
Trip Events
1. Observe any Trip LED flashing on trip unit.
2. Observe message on the display.
3. Step to the event submenu to observe the timestamp
of event and trip current data. This data, along with the
timestamp, will also be stored in the event log. The maximum
trip current value that can be displayed is 65535A.
4. After any trip condition, the trip unit should be reset by
pressing the Reset pushbutton
A reset pushbutton operation does the following after a trip:
Clears the cause of trip flashing LED after a trip event
Clears the Trip LED
Clears display data
5. Reclose circuit breaker as desired.
See Appendix D: Display, Indicators and Menus for more
information on viewing trip events and screen information that
can be viewed after the event
Waveform capture - Trip
The following causes for a trip will perform a 10 cycle waveform
capture. The waveform information will contain 6 pre-event
cycles and 4 post-event cycles of data.
Long Delay
Short Delay
Instantaneous
Ground
Phase Loss
Current Unbalance
Over Voltage
Under Voltage
Voltage Unbalance
Reverse Power
Over Frequency
Under Frequency
Maintenance Mode
Neutral
19
EATON www.eaton.com
Alarm Events
1. Alarm LED flashing on trip unit.
2. Observe message on the display.
3. Step to the event submenu to observe the timestamp of
event and data. This data, along with the timestamp, will also
be stored in the event log.
4. After any alarm condition, the trip unit should be reset by
pressing the Reset pushbutton
See Appendix D: Display, Indicators and Menus for more
information on viewing alarm events and screen information
that can be viewed after the event.
Alarms are tracked in real-time and a Reset pushbutton may
momentarily clear the alarm but the Alarm LED and alarm
message will reappear if the condition is still present.
The ESCape pushbutton activation will remove the alarm
message from the display and return to normal menu viewing
mode, but the Alarm LED will remain lit.
ote:N A way to clear an alarm if desired, after reviewing the alarm
and its associated data, is to enter the Program settings submenu and
change or turn off the associated alarm setpoint value.
Waveform capture - Alarms
The following alarms will perform a 6 cycle waveform capture:
Long Delay Pickup
Current Unbalance
Ground Fault
High Current Fault
High Load
Neutral Current
Phase Rotation
Over Voltage
Under Voltage
Voltage Unbalance
Over Frequency
Under Frequency
Low Power Factor
Reverse Power
kVA Demand
kW Demand
THD
Effective September 2013
Instructional Leaet IL01301064EOperating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Trip Unit Indicators
Status Indicator – A red and green colored LED can be
switched on to produce colors of green, red or orange for this
indicator. When the trip unit is healthy and operational with
auxiliary power or current through the circuit breaker that is
greater than 50A (NF Frame) or 100A (RF Frame) three phase,
the indicator will ash green at a 1 second (1 Hz) rate. If the
trip unit is picked up in long delay overload protection, the
green LED will ash at twice the speed of the normal status
indication. When an abnormal condition is detected in the
circuit breaker the trip unit will turn on the red status LED
creating a red then orange ashing color from the indicator.
This Status LED indication can occur if an abnormal condition
is detected in the circuit breaker, trip actuator, or an internal
electronic validation check has failed.
Maintenance Mode Indicator (optional) – A blue colored LED
will be illuminated whenever the ARC FLASH MAINTENANCE
MODE protection circuit is active.
Long Indicator – A red colored LED that ashes when a long
delay protection overload trip has occurred. An orange colored
LED will be illuminated and ashing to indicate if an over-
temperature trip has occurred.
Metering
Current
Voltage
Power
Energy
Frequency
SEL
SAVE
ESC
Status
Maint. Mode
Long
Short
Inst.
Ground
Trip
Type NF Frame
Group A
Rating Plug
In=400A
Cat NA250T
Test
Port
Aux.
Power
Alarm
+
Battery
-
CR 1/3N
DL 1/3N
Battery Check
Reset/
Bettery Test
Metering
Current
Voltage
Power
Energy
Frequency
SEL
SAVE
ESC
Status
Maint. Mode
Long
Short
Inst.
Ground
Trip
Type NF Frame
Group A
Rating Plug
In=400A
Cat NA250T
Test
Port
Aux.
Power
Alarm
+
Battery
-
CR 1/3N
DL 1/3N
Battery Check
Reset/
Bettery Test
Figure 12. Trip Unit Indicators (LSIG style with Maintenance
Mode)
20
EATON www.eaton.com
Section 5: Display Module Interface
Display
The Digitrip 1150 trip unit has a graphic color LCD display on
the front of the trip unit. The self contained display module
holds the LCD display and the push buttons that interface to
the trip unit as shown in Figure 11.
The Digitrip 1150 trip unit will be operational in the event
that something on the display module is not functional or
is removed. All protective setpoints are stored in the main
trip unit body. If any one of the Communication Accessory
Modules (CAM) is used with the Digitrip 1150, a duplicate
copy of the setpoints may be stored in that module as well
as the trip unit body.
Figure 11. Trip Unit and Display Module
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Effective September 2013
Instructional Leaet IL01301064E
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98

Eaton NRX Digitrip 1150 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI