Remko RVS75H User manual

Category
Heat pumps
Type
User manual
Edition GB – W11
REMKO RVS...H (INOX)
RVS 60H, RVS 75H, RVS 100H, RVS 150H
RVS 60H INOX, RVS 75H INOX, RVS 100H INOX,
RVS 150H INOX
Air-cooled Chiller with Heat Pump function
Air-cooled Chiller with Heat Pump function in Stainless Steel
Operation · Technology · Spare parts
Contents
Read these operating instructions carefully
before commissioning / or using the system.
These instructions are an integral part of the system and must be
kept at all times near by or on the system.
This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
Safety notes 4
Environmental protection and recycling 4
Warranty 5
Transport and packagin 5
System description 5-6
System configuration 7
Operation 7-13
Care and maintenance 14
Shut-down 14
Trouble-shooting and customer service 15-17
Installation instructions for qualified personnel 18-20
Installation 21-25
Condensate draining and ensured discharge 25-26
Electrical connection 26-28
Electrical components 29
Electrical drawings 30-31
Leak testing 32
Before commissioning 32-33
Commissioning 34
Unit dimensions 35
Exploded view 36/38
Spare parts list 37/39
Performance graphs 40-41
Technical data 42
EC – Declaration of Conformity 43
Made by REMKO
3
Safety notes
Environmental
protection
and recycling
Disposal of packaging
All products are packed for trans-
port in environmentally friendly
materials. Make a valuable con-
tribution to reducing waste and
preserving raw materials. Only
dispose of packaging at approved
collection points.
Disposal of equipment
and components
Only recyclable materials are used
in the manufacture of the system
and components.
Help protect the environment by
ensuring that the system or com-
ponents (for example batteries) are
not disposed in household waste,
but only in accordance with local
regulations and in an environmen-
tally safe manner, e.g. using certi-
fied firms and recycling specialists
or at collection points.
Carefully read the operating in-
structions before commissioning the
system. It provides useful tips and
information as well as hazard
warnings to prevent injury or mate-
rial damage .
Failure to follow the directions in
this manual can result in injury,
damage to the environment and
the system itself and will null in
void any claims for liability.
Keep this manual and the refrig-
erant data sheet by the system.
The system or components
are not to be exposed to any
mechanical stresses, extreme
levels of humidity or extreme
sunlight.
The unit should be set up and
installed only by qualified per-
sonnel.
The installation, connection and
operation of the system and its
components must be carried out
in accordance with the operat-
ing instructions as stipulated in
this manual and comply with all
applicable local regulations.
Mobile systems must be set up
securely on suitable surfaces and
in an upright position. Stationary
systems must be permanently
installed for operation.
Modification of the system or
its components supplied by
REMKO is not permitted and
can cause malfunctions.
The system and components
may not be operated in areas
where there is an increased risk
of damage. Observe the mini-
mum clearances.
The electrical supply should be
adapted to fulfil the require-
ments of the system.
The operational safety of system
and components is only assured
if they are fully assembled and
used as intended. Safety devices
may not be modified or discon-
nected.
Do not operate the system or
components with obvious de-
fects or signs of damage.
All housing parts and openings
in the system, e.g. air inlets and
outlets, must be free of foreign
objects, fluids, or gases.
The system and components
must not be installed in hazard-
ous areas or areas where the air
is contaminated with abrasive/
corrosive materials or dust.
Touching some parts of the sys-
tem can result in burns or other
injury. Wearing appropriate
protective clothing is necessary
to avoid risks.
Only authorised personnel and
personnel trained in the use of
the system and its components
are permitted access to and
allowed to operate the system
and its components.
Installation, repair and mainte-
nance work should only be car-
ried out by authorised person-
nel. Inspection and cleaning can
be performed by the operator
providing the system is not un-
der current/voltage.
To avoid any risks to persons,
appropriate precautions are to
be taken when installing, repair-
ing, maintaining, cleaning or
working on the system.
The system or components
are not to be exposed to any
mechanical stresses, extreme
levels of humidity or direct
sunlight.
REMKO RVS...H (INOX)
4
The system is designed for out-
door installation. Under certain
circumstances, it can also be used
indoors. The system’s cooling
cycle comprises of: an evaporator,
a compressor with a crankcase
heater, a thermal expansion valve,
condenser, condenser fan, fan
speed system and high and low
pressure switches. Systems with
heat pump function also have a
reversing valve and a refrigerant
tank.
The medium cycle comprises a
circulation pump, expansion vessel,
safety valve, medium storage tank
and a flow switch. Accessories in-
clude: Cabled remote control, vib-
ration dampers, glycol concentrate
and a technical acceptance test.
Intended use
Depending on the model and the
equipment, the system is only
intended to be used as a chilled
water system for the cooling or
warming of the operating medium
water or a water-glycol mixture
within a closed cycle.
Any other use or use in a way that
dose not conform with the defini-
tion above is considered an incor-
rect use.
The manufacturer/supplier as-
sumes no liability for damages aris-
ing from the incorrect use of the
system or any part of it. The user
dose so at their own risk. Using the
system correctly means working
in accordance with the operating
manual, installation instructions
and complying with the mainte-
nance requirements.
The system is shipped in sturdy
transport packaging. Immediately
check the system on delivery and
make note of any damage or miss-
ing parts on the delivery note and
inform the forwarding agent and
your contractual partner.
Warranty claims at a later date will
not be accepted.
System description
Transport and
packaging
In cooling mode, the unit (an air to
water chiller) takes heat out of the
operating medium to be cooled,
water or a mixture of water and
glycol, within a closed medium
cycle in the evaporator (plate heat
exchanger) and gives it off to the
closed cooling cycle. Through the
heat exchange, the medium cools
and the refrigerant in the cooling
cycle vaporises under low pressure.
The vaporised refrigerant passes
into an electrically driven compres-
sor (rotary piston or scroll design),
which increases the refrigerants
pressure and temperature. The
vaporise refrigerant passes into a
finned condenser, which, as a con-
sequence of the heat exchange,
condenses the refrigerant under
high pressure to a liquid. The air
that passes through the condenser
heats the surrounding area. The
liquid refrigerant is returned by
means of a thermal expansion
valve back to the evaporator
where the process starts again.
In heating mode, a chilled water
system with heat pump functions
(HP-function) can take up heat
from the ambient air in the finned
condenser and give it off to the
operating medium. A reversing
valve switches the cooling cycle.
A independent return temperature
regulator, which ensures the safety
functions of the system controls
the cooling and heating. A re-
mote Enabling switch provides for
remote on/off.
Warranty
It is important for any warranty
claims is that the customer or
his accepting representative fully
complete the warranty registra-
tion card and commissioning report
which is included with the system
at the time when it is purchased
and commissioned and that these
documents are returned to REMKO
GmbH & Co. KG. The warranty
conditions are detailed in the "Gen-
eral terms and conditions". Only
the parties to a contract can negoti-
ate any special agreements beyond
these conditions. In this case, con-
tact the contractual partner.
5
Legend:
1 Circulation pump
2 Manual bleeding valve
3 Plate evaporator
4 Flow switch
5 Expansion vessel
6 Safety valve
7 Compressor
8 Pressure switch
9 Schrader valve
10 Fin condenser
11 Condenser fan
12 Filter dryer
13 Capillary tube
14 Thermal expansion valve cooling
15 Probe medium intake
16 Probe medium outlet
17 Probe condenser
18 Pressure transducer
Construction
1
1
3
3
4
4
5
5
7
7
17
17
8
8
9
9
14
14
11
11
18
18
10
10
13
13
12
12
2
2
16
16
15
15
9
9
8
1
3
4
5
7
17
8
9
14
11
11
18
10
13
12
2
16
15
9
8
8
RVS 60H cooling and heating mode
RVS 75H cooling and heating mode
RVS 100H / RVS 150H cooling and heating mode
REMKO RVS...H (INOX)
6
System configuration
Operation
The system can be easily operated
via the fully automatic controller
μC2SE. If due to local conditions
programming via the internal con-
trol course difficulties, the system
can also be programmed via a ca-
bled remote controller (accessory)
or an external ON/OFF-Switch.
If a combination of letters /
numbers is shown in the dis-
play, then there is a malfunc-
tion in the unit (see chapter on
trouble-shooting and customer
service).
! CAUTION
The system is designed as a two
pipe system.
The system has 2 medium pipes
(supply and return) for cooling
using a cold medium or heating
using a warm medium.
The medium can be circulated
to the room to be cooled via the
floor, or via the ceiling depending
on where the unit is mounted.
For each of the different systems, a
minimum flow volume and a mini-
mum medium volume is needed
for safe operation.
Chilled water system
System configuration
Medium intake
Medium outlet
Indoor area 1
Outdoor area
Indoor area 2 Indoor area 3
Room temperature control Room temperature control
Infrared remote control
Chilled water
appliance
Chilled water
appliance
Chilled water
appliance
Condensate drain
Condensate line (only
units with HP-function)
Condensate drain Condensate drain
Condensate collecting drain
A centralised fault contact, part of
the standard equipment, can be
used for the external signalling of
a fault.
Methods of operation
Centralised
fault signal
Cable
remote control
Enable contact
On/OFF Cooling/Heating
(e.g. building management
system)
(Standard equipment)
(Standard equipment)
(Accessories)
Controller
μC2SE
(Standard equipment)
Help save on energy consump-
tion in stand-by mode! If the
device, system or component
is not in use, we recommend
disconnecting the power sup-
ply. Components with a safety
function is excluded from our
recommendation!
TIP
7
Icon General alarm
The icon, displays the respective
code, and fault.
Icon Defrosting status
The icon(lights up) displays
that the defrosting cycle in the
fin condenser is active. When
blinking the controller is calcu-
lating the necessary defrosting
time.
Icon Frost protection heating
The LED provides information
about the operating status for
the frost protection heating
medium.
Icon "Fault"
The LED shows that there is a
fault.
Icon Compressor 1
The illuminated LED indicates
that compressor 1 is in ope-
ration. The LED blinks if the
compressor is in safety mode.
Icon Compressor 2
See description point .
Icon Compressor 3
See description point .
Icon Compressor 4
See description point .
Value display
The value display shows current
values.
Operating the controller µC2SE
The controller has 3 modes:
1. Summer mode (cooling mode)
In cooling mode, the warmer me-
dium temperature is cooled to the
preset cooler temperature.
2. Transition mode (heating mode)
In heating mode, the cooler me-
dium temperature is heated to the
preset warmer value.
3. Standby mode (Stand-by)
In the Stand-By mode, safety
equipment is active but no operat-
ing mode is set.
Key-Pad " "
Using this key-pad, the current-
menu can be exited.
Key-Pad " "
This key-pad is used for se-
lecting open/close, a selected
value or parameter.
Key-Pad " "
Prolonged pressing (5 sec.)
allows switching between the-
operating modes „Cooling“and
„Stand-By“.Short pressing,
displaysof the current values
for the temperature probes B1
to B3 and the pressure trance-
ducer B4. A value can also be
increased.
Key-Pad " "
Prolonged pressing (5 sec.)
allows switching between the-
operating modes „Heating“and
„Stand-By“. Short pressing
displaysthe current values for
the temperature probes B1 to
B3 and the pressure trance-
ducer B4. A value can also be
reduced.
Key-Pad " and " together
Pressing long (5 sec.)and
together and on entering a
password, the parameter level is
opened.
Key-Pad " and " together
Pressing long (5 sec.) and
together allows the acknow-
ledgement of a pending faults
or operating hours.
Key-Pad " and " together
in heating mode
Longer pressing together
triggers manual defrosting in
heating mode.
Icon cooling mode
The icon displays the selected
cooling mode.
Icon heating mode
The icon displays the selected
heating mode.
Icon "Fan"
The icon lights up, if the con-
denser fan is activated.
Icon "Pump"
The icon lights up, if the circula-
ting pump is activated.
+
+
+
Controller control panel
µC2SE
During the initialization of the
controller (after starting the
unit and displaying the soft-
ware version, e.g. “H 99”) do
not push the key-pad “Prg”
to avoid reprogramming the
controller!
! CAUTION
REMKO RVS...H (INOX)
8
External operation
Key-Pad functions
External operating contact C / H
Standard means of switching on or off of the system is done manually
using the controller or using the cabled remote control available as an
accessory. Parameters must be changed if the system is to be activated
externally by means of an electrical switch.
Parameter H 07 activates the external Controller.
With regard to the subject of switching, please read the respective chap-
ter under “electrical connection”.
Operating using the controller is no longer possible once the parameter-
shave been changed.
Standard means of switching between the heating and cooling modes
is done manually using the controller or using the cabled remote control
available as an accessory. A parameter must be changed if the operating
mode is switched externally by an electrical switch.
Parameter H 06 activates the external switching.
With regard to the subject of switching, please read the respective chap-
ter under “electrical connection”.
Operating using the controller is no longer possible once the parameters
have been changed.
External enabling contact
Activate or deactivate the unit with the or key-pad by pressing
for more than 5 seconds. The set operating mode appears in the display
(cooling or heating icon).
The unit has three modes: Stand-By mode, Summer mode (cooling mode)
and Transition mode (heating mode only for systems with HP function). In
Stand-By mode no symbol is shown only the current value is displayed. All
fault reports and frost protection resistors are active.
Note: Other functions can be programmed for the icon by changing the
parameters.
Setting the operating mode
Cooling mode
Heating mode
Operating mode Stand-By
HEATING
MODE
COOLING
MODE
5 sec.
5 sec.
min. 5 sec.
min. 5 sec.
Operating the unit is carried out using the controller’s key-pads. Checking current value or putting in the target
value for the summer mode (cooling mode) and the transition mode (heating mode) only for systems with (HP-
function) is done without the use of a password.
Qualified personnel who are authorised to use a passwords, can access submenus to change the systems con-
figuration. All changes to the parameters must be documented and kept permanently by the system.
The following diagrams provide simplified illustrations of the operating functions.
9
Target value cooling mode
Programming target values
The target value cooling (r 01) and the actual (hysteresis) cooling (r 02)
can be displayed and changed under the menu item “-r-” without the
use of a password.
With the Key-Pad or the value can be changed within limits.
r 01 = 12.0 °C Target value cooling mode (factory setting)
r 02 = 2.0 °C Hysteresis cooling mode (factory setting)
Minimum target value cooling mode 10.0 °C
Maximum target value cooling mode 28.0 °C
Target value heating mode The target value heating (r 03) and the hysteresis heating (r 04) can be
displayed and changed under the menu item “-r-” without the use of
a password.
With the Key-Pad or the value can be changed within the limits set
in the factor (r15 + r16).
r 03 = 40.0 °C Target value heating mode (factory setting)
r 04 = 2.0 °C Hysteresis heating mode (factory setting)
Minimum target value heating mode 30.0 °C
Maximum target value heating mode 45.0 °C
Password
Password
Display
Display
Submenu
Submenu
Submenu
Submenu
short-term short-term
min. 5 sec.
+
...
repeated short-term
short-term
short-term short-term
Target value cooling
Target value cooling
old target value
old target value
new target value
new target value
short-term short-term
min. 5 sec.
+
...
...
repeated short-term
short-term
short-term short-term
REMKO RVS...H (INOX)
10
Display of Operating Time Go to menu for operating hours. A clock display will appear.
c10 = Operating time compressor 1 in hours x 100
c11 = Operating time compressor 2 in hours x 100
c15 = Operating time circulation pump in hours x 100
Circulation pump 1
Operating Status
Working time can be reset at the menu level by pressing the Key-Pad
and for 5 seconds.
Compressor 1920 operating hours0 operating hours
if necessary
for mainte-
nance
if necessary
for mainte-
nance 1670 operating hours0 operating hours
short-term short-term
min. 5 sec.
min. 5 sec.
min. 5 sec.
+
+
+
...
...
repeated
repeated
repeated
repeated
short-term
short-term
short-term
Display of the operating values The normal display shows the medium intake temperature.
Additional values can be called up by briefly pressing the key-pad or
.
automatic
automatic
automatic
automatic
automatic
short-term
/
repeated
Current value probe b01
medium intake
Current value probe b02
medium outlet
Current value probe b03
condenser temperature cooling cycle
Current value tranceducer b04
high pressure side cooling cycle
short-term
short-term
short-term
11
Fault reset
To protect the system from damage, the controller checks the tempera-
ture, pressure, configuration, etc. of the relevant safety components by
means of sensors and inputs. The controller’s display shows a series of
letters as a coded fault report. A fault code given corresponds with a
cause (see table “Coded fault reports”).
The controller shows the current faults one after the other.
Simultaneously pressing key-pad and can, after the fault has been
corrected, be used to confirm the correction.
Faults are saved in a fault list. A password must be used to delete the list.
Call up of fault reports
(See chapter on trouble-shooting and customer service)
Differential pressure monitor
Fault deleted
High pressure
High pressure
min. 5 sec.
min. 5 sec.
+
+
automatic
2 sec.
automatic
2 sec.
automatic
2 sec.
short-term short-term
min. 5 sec.
+
REMKO RVS...H (INOX)
12
Overview of the operating structure
H01: Configuration unit
H02: Number of cycles
H03: Number of evaporators
H04: Number of compressors per cycle
H05: Configuration circulation pump
H06: Digital input cooling/heating
H07: Digital input On/Off
H08: Configuration controller
H09: Key lock controller
H10: serial address controller
H11: Configuration digital outlets
H12: Configuration 4-way reversing valve
r01: Target value cooling
r02: Hysteresis cooling
r03: Target value heating
r04: Hysteresis heating
r05: Rotation compressor 1/2
r06: Configuration compressor mode
r08: max. activation time compressor
r09: min. activation time compressor
r10: max. deactivation time compressor
r11: min. deactivation time compressor
r12: Hysteresis deactivation compressor
r24: Target value autom. Switching
r25: Target value AT deactivation compressor
r26: Target value dehumidification cooling
r27: Regulation medium volumes
r28: Minimum mode compressor medium K
r29: Hysteresis compressor medium K
r30: Minimum mode compressor medium H
r31: Hysteresis compressor medium H
r32: Target value "Hot start"
r33: Hysteresis "Hot start"
t01: Real time setting hour
t02: Real time setting minute
t03: Real time setting day
t04: Real time setting month
t05: Real time setting year
t06: Setting hour start cooling
t07: Setting minute start cooling
t08: Setting hour stop cooling
t09: Setting minute stop cooling
t10: Setting hour start heating
t11: Setting minute start heating
t12: Setting hour stop heating
t13: Setting minute stop heating
t14: Setting hour start LN cooling
t15: Setting minute start LN cooling
t16: Setting hour stop LN cooling
t17: Setting minute stop LN cooling
t18: Setting hour start LN heating
t19: Setting minute start LN heating
t20: Setting hour stop LN heating
t21: Setting minute stop LN heating
P01: Delay flow monitor before start
P02: Delay flow monitor mode
P03: Delay ND
P05: Fault reset
P06: Icon cooling/heating /
P08: Configuration dig. Input 1
P09: Configuration dig. Input 2
P13: Configuration input B4
P15: Configuration ND
P16: Fault excess temperature
P17: Delay excess temperature
P19: Fault insufficient temperature
P20: Configuration operating start
P21: Configuration fault relay
P22: Delay ND heating
P23: Delay ND defrosting
P25: Configuration dig. Output 2
P26: Configuration dig. Output 3
P27: Configuration dig. Output 4
P28: Configuration dig. Output 5
P34: Configuration dig. Input 5
P35: Deactivation fault relay via
P36: Configuration HD
01: sensor type B1
02: sensor type B2
03: sensor type B3
04: sensor type B4
13. Calibration B1
14. Calibration B2
15. Calibration B3
16. Calibration B4
21: Digital filter
22: Input limit
23: Unit of measurement °C/°F
A01: Target value frost protection
A02: Hysteresis frost protection
A03: Time delay frost protection
A04: Target value medium heating
A05: Hysteresis medium heating
A06: Sensor medium heating
A07: min. frost protection setting
C01: min. working time compressor
C02: min. down time compressor
C03: Time delay On-On compressor
C04: Time delay On-On compressor 1/2
C05: Time delay Off-Off compressor 1/2
C06: Switch-on delay compressor
C07: Switch-on delay pump-compressor
C08: Switch-off delay compressor-pump
C09: max. working time compressor step 1-2
C10: Working time compressor 1
C11: Working time compressor 2
C12: Working time compressor 3
C13: Working time compressor 4
C14: Maintenance fault compressor
C15: Working time circulation pump 1
C16: Working time circulation pump 2
C17: min. stop time before operation circulation pump
C18: min. working time circulation time
C19: Delay 4-way valve - compressor
d01: Function mode defrosting
d02: Input parameter °C/P
d03: Target value defrosting start
d04: Target value defrosting end
d05: min. working time defrosting start
d06: min. defrosting duration
d07: max. defrosting duration
d08: Delay defrosting interval cycle 1
d09: Delay defrosting interval cycle 1-2
d10: external contact defrosting start
d11: Frost protection heating
d12: Wait time before defrosting
d13: Wait time after defrosting
d14: Defrosting cycle 2
d15: Defrosting start cycle 2
d16: Forced ventilation time after defrosting
d17: Target value air circulation defrosting
d18: max. exterior temperature (slid. defr.)
d19: Hysteresis defrosting start (slid. defr.)
d20: Hysteresis exterior temperature (slid. defr.)
F01: Configuration fan output
F02: Operating mode fan
F03: min. initial speed
F04: max. initial speed
F05: Target value cooling mode °C/P
F06: Hysteresis value cooling mode °C/P
F07: Hysteresis min speed cooling
F08: Target value heating mode °C/P
F09: Hysteresis heating mode °C/P
F10: Hysteresis min speed heating
F11: Fan start-up period start with 100%
F12: Pulsing fan start-up period
F13: Function mode fan defrosting
F14: Pre-ventilation cooling
F15: Low noise activation
F16: Hysteresis low noise mode cooling
F17: Hysteresis low noise mode heating
b01: Current value sensor medium intake B1
b02: Current value sensor medium output B2
b03: Current value sensor condenser B3
b04: Current value HD-pressure transducer B4
Configuration
Password
Display Display
Parameter value Display
Password level
Current values
sensors
Compressor
Defrost
Fan
Units
Faults
Controller
Software
version
Real time clock
(not usable)
Frost protec-
tion
min. 5 sec. short-term short-term
+ / Password level Display
Direct / without PW _d_
User / partly special _U_
Superuser / special _S_
Factory / manufacturer _F_
13
Care and maintenance Shut-down
Temporary shut-down
1. Shut down the interior of the
system using the remote
control.
2. Shut the unit down either by
the internal controller or by us-
ing the remote.
3. Check the proportion (percent-
age) of glycol.
4. Check the unit for visible signs
of damage and clean it as
described in the chapter “Care
and maintenance”.
5. As much as possible, cover the
unit with a plastic foil to protect
it against the weather.
If only water and not a mix-
ture of water and glycol
is used, in regions subject
to freezing, water must be
drained from system when
it is not in operation The
drained water volume must be
replaced when system is put
back into operation!
! CAUTION
Permanent
shut-down
Ensure that equipment and com-
ponents are disposed of in accord-
ance with local regulations, e.g.
using certified firms and recycling
specialists or at collection points.
REMKO GmbH & Co. KG or your
contractual partner will be pleased
to provide a list of certified firms in
your area.
Regular care and maintenance of
the system will ensure trouble-free
operation and a long service life.
Prior to performing any work,
The system must be switched
off and isolated from the
power supply and secured to
prevent accidental switch-on!
! CAUTION
Wearing appropriate protec-
tive clothing is necessary when
working on the system.
! CAUTION
Care
Ensure the unit is protected
against dirt, mould and other
deposits.
Clean the unit using a damp
cloth. Do not use a jet (high
pressure).
Do not use any caustic, abra-
sive or solvent-based cleaning
products.
Clean the fins on the unit prior
to long shutdown periods.
Maintenance
We recommend an annual
maintenance contract with an
approved specialist company.
This ensures the operational
reliability of your system!
TIP
List of task
Checks / maintenance / inspection
Commis-
sioning
Monthly
Half-yearly
Yearly
General
Clean dirt traps • •
Check medium charge • •
Check circulation pump • •
Dirt / damage condenser • •
Check quality of the glycol • •
Measure voltage and current • •
Check direction of rotation • •
Check compressor • •
Check fan • •
Check refrigerant charge • •
Check condensation drain • •
Test insulation • •
Leak test for refrigerant cycle 1)
The local law can require a
leak test of the cooling system
and the quantity of cooling
medium to be checked. In-
spection and documentation is
to be carried out by qualified
personnel.
NOTE
1) see note
REMKO RVS...H (INOX)
14
The system has been manufactured using state-of-the-art production methods and in house tested many times to
ensure the system is 100% in working order. If malfunctions should occur, please check the system as detailed in
the list below. For installations with an indoor-outdoor system, observe the chapter “Trouble-shooting and customer
servicein both operating manuals.
Please inform your dealer if the system is still not working correctly after all the function checks have been per-
formed.
Touble-shooting and customer service
Malfunctions
Please note that this trouble-shooting table continues on the next page
Fault Possible cause Check Remedial measures
The unit
does not
start
Display is not illuminated.
No power supply
Check the power connections at the mains
and the voltage values.
Check breaker switches/fuses at the second-
ary side of the supplemental transformer.
Incorrect phase sequence.
The KA3 phase sequence relay
did not enable.
Replace power supply phase conductorat the
at the terminal strip on the switch panel.
The display is illuminated but
the unit does not start.
Unit in STAND BY See paragraph "Key functions" for the acti-
vation of the unit.
No external enabling contact
is shortened
Check connection to the GND - ID5 termi-
nals.
The unit does not start, the
compressor icon in the display
is blinking.
Start-up delay Wait out the start-up delay (max 360 sec.),
the compressor should then start.
The display blinks and
alternately shows an
alphanumeric code and the
temperature value.
One or more protective
devices have responded
Check which safety device has responded,
correct the cause of the fault and reset the
safety device (see "Fault display by code")
Compressor overload switch is
activated.
Does the compressor icon light
up and does the switch have
voltage?
Have specialist replace switch or compressor.
The unit
is work-
ing with
reduced
cooling/
heating
capacity
Thermal load was increased. Have there been any structural
changes? Maintain safety clearances.
Supply temperature too high
(cooling) / too low (heating).
If the medium outlet tempera-
ture is approx. 5 ... 10 °C /
35 ... 40 °C?
Increase/reduce medium intake temperature.
Air in the medium cycle. Are automatic bleeders in-
stalled at the highest point? Bleed manually or install automatic bleeders.
Condenser / evaporator tem-
peratures too high (cooling) /
too low (heating).
Are the fins clean / free of ice
and the operating limits
complied with?
Comply with operating limits
Cooling: Clean fins, provide shade for the
unit, heating: Reduce supply temperature
Incorrect parameter setting. Check setting. Change setting.
Pulse mode because of too
little demand. Is the system oversized?
Increase medium flow with the installation of
a storage tank.
Medium
discharge
Leak in the lines or insulation
defective.
Are there leaks and are all of
the lines insulated? Seal and insulate.
Defrosting phase in heating
mode. Heating mode set? Normal operating status.
15
Fault Code Possible cause check Remedial measures
The unit
does not
start or
switches
itself
off.
Mains failure Does all other electrical equip-
ment function correctly?
Check voltage and if necessary
wait until turned on again.
Unit's breaker/mains switch
turned off Is voltage available to the unit? Switch on unit's breaker/ main
cycle breaker.
Wait time too short Is the compressor icon flashing? Plan for longer wait period.
Mains current has incorrect
direction of rotation.
Has the phase sequence relay
switched? Change direction of rotation.
Controller is not working
Is the icon for cooling mode, heating
mode or Stand-By mode illuminated?
Energise and
select operating mode.
Medium intake temperature or
parameter setting wrong Check setting. Change setting.
No alarm / fault Check the contact "external
enable"
Open / close
the contact being used.
E1 Medium intake probe defective Check resistance at B1 Replace defective probe.
E2 Medium outlet probe defective Check resistance at B2 Replace defective probe.
E3 Condenser probe defective Check resistance at B3 Replace defective probe.
E4
Outdoor temperature probe
Cooling cycle pressure transducer
defective
Check resistance/voltage at B4 Replace defective tranceducer.
HP1
High pressure fault Compressor relay switched on? Have checked by a specialist.
High pressure fault
Are the fans turning?
Is the condenser's air intake free
of obstacles?
Have checked by a specialist.
High pressure fault at pressure
tranceducer PT
Is the value at B4 greater than
40 bar? Have checked by a specialist.
LP1 Low pressure fault Is the pressure in the cooling
cycle OK? Have checked by a specialist.
Ht Excessive temperature medium
intake
Is the return temperature greater
than 50°C?
Reduce temperature of the
medium
Excessive temperature con-
denser
Are the fans turning?
Is the condenser's air intake free
of obstacles?
Have checked by a
specialist.
Excess temperature condenser Have the operating temperatures
been exceeded? Shut down the system.
A1
Antifreeze alarm has
responded
Is the supply temperature greater
than or less than 4°C?
Increase return temperature,
Increase medium flow volume,
Set frost protection temp.
.
Medium volume in the system
too low
Has the minimum medium vol-
ume been complied with?
Comply with minimum medium
volume e.g. in the reservoir.
FL
Differential switch /
Flow switch
has responded
Are the following points OK:
- Medium flow volume
- No air in the medium lines
- Output of the circulation pump
- Does the flow switch operate
- Shut-off devices open
- Medium pressure to low
Have checked by a
specialist.
D1 Fault defrosting Maximum defrosting duration
exceeded Have checked by a specialist.
Hc1 Compressor 1 maintenance Maintenance interval compressor
1 has been reached.
After maintenance by a special-
ist reset of the operating hours
see chapter "Querying the
operating status".
Malfunctions
REMKO RVS...H (INOX)
16
Fault indicated by code
Code Fault type Re-set Intake type Cut-off
Intake value
Automatic
Manual
Digital
Analog
Compressors
Condenser fan
Circulation pump
A1 Antifreeze alarm medium cycle
B2 P05 OWT 13/11 x x
AHt Excess temperature at start
B1 / P16 x IWT 10 x x
ALt Insufficient/or excess temperature at start C/H
B1 / P19 x IWT 10 x x
CP1 Compressor 1
x x
E1 Temperature sensor medium intake defective
B1 x IWT 10 x x x
E2 Temperature sensor medium output defective
B2 x OWT 13/11 x x x
E3 Temperature sensor condenser defective
B3 x PT 14/12 x x x
E4 Pressure tranceducer cooling cycle defective
Bn/V+ x PS Bn/V+
EHS High supply voltage controller
x x x x
ELS Low supply voltage controller
Tr x x x x
EP1 EEPROM driver defective
x x x x
EPb EEPROM fault at start
Config. x x x x
EPr EEPROM fault during operation
Config. x x x x
FL Flow monitor has responded
ID1 x FS 6/9 x x x
Hc1 Maintenance interval compressor 1
C14 x
Ht Excessive temperature medium cycle
B1 / P16 x IWT 10
HP1 Pressure switch HD cooling cycle
ID3 <3/hrs <3/hrs HP 2 x on 1 min.
HP1 Tranceducer cooling cycle excess pressure
Bn/V+ x PS Bn/V+ x x x
LP1 Pressure switch ND cooling cycle
ID4 <3/hrs <3/hrs LP 3 x x
tC1 Overload cycle 1
P08-13 x x x
tEr Communication cabled remote control
x x x x
tP General overload
P08-13 x x x x
Reports
LA General reports
P08 x
D1 Report defrosting
x
dF1-2 Defrost cycle exceeded
Defrosting
period
x x x
Reset
1. Faults with automatic reset: The reset is carried out automatically.
2. Faults with manual reset: The reset can only be carried out by a specialist after the fault has been corrected.
3. Faults with semi-manual reset: The reset is first carried out automatically, afterwards only a manual reset is possible
by a specialist, after the fault has been corrected.
Fault Code Possible cause check Remedial measures
The unit
does not
start or
switches
itself
off.
ELS/EHS Low/High supply voltage
controller
Initial voltage transformer, or mains
inlet voltage
Have checked by a
specialist.
EP1 EEprom controller error Does the controller operate properly? Have specialist check regulation or
parameters.
EPr EEprom controller error Does the controller operate properly? Have specialist check regulation or
parameters.
Malfunctions
17
Installation instructions for qualified personnel
To install the system it is impor-
tant to follow the installation
instructions for both the chiller
and the chilled water system
(indoor system) or heating
system when installing the
entire system.
The indoor system and the
chiller work independently. A
connection between the two is
not necessary.
Transport the unit in its original
packaging as close as possible
to the installation location to
avoid damage.
The units may only be moved
upright (installed position) using
appropriate transport equipment
(Figure 1).
Secure against tipping!
The unit must be kept upright
when transporting to a higher
elevation (Figure 2).
Check that the packaged con-
tents are complete and inspect
the system for any visible signs
of transport damage.
Report any damage immediate-
ly to your contract partner and
the shipping company.
Select an installation location
with free air movement both
for the inlet and outlet. See
section “Minimum clearances”.
Do not install the unit in the
immediate vicinity of devices
with intensive thermal radia-
tion, this will reduce the cooling
capacity.
Lift the unit only at intended
lifting points. Never stress the
medium or refrigerant pipings.
The medium connection lines,
valves and connections must be
insulated against vapour
density. If necessary, also insu-
late the condensate line (only
units with HP-function). In dual
systems with cooling and
heating modes, the
requirements of the current or
other local law (EnEV) are to be
complied with.
Seal off open lines against dirt
and never kink or crimp the
lines.
Avoid unnecessary bending.
Establish all electrical connec-
tions connections in accordance
with the relevant DIN- and VDE
or other local standards.
Always fasten electric wiring
properly to the terminals,
otherwise there is a risk of fire.
Comply with all regulations
governing structural and build-
ing requirements and conditions
with regard to the installation
site.
In the selection of the installa-
tion site, pay attention to the
site itself and to any possible
noise reflexion from the sur-
roundings.
To avoid the transmission of
vibrations the units must be
installed on vibration absorbing
material or on vibration iso-
lated foundations. In doing so,
make sure that the lines are also
vibration isolated.
If the installation site must fulfil
special noise emission require-
ments, this must be done on
site where appropriate adjust-
ments can be made. In this
cases, please consult a noise
level expert.
Important information
before installing
1 Correct way to move
2 Correct way to lift
Lifting point
REMKO RVS...H (INOX)
18
Wall openings
We recommend that the inside
of the opening be padded or
lined for example with a PVC
pipe to prevent damage to the
pipe lines
.
After installation, the wall
opening should be sealed off
with a suitable sealant. Do not
use materials containing cement
or lime!
Installation material
The system is secured on vibration
absorbers (accessories) to the floor
by means of bolts. The carrying ca-
pacity of the console and the wall
must be taken into account when
fastening to the wall.
Selection of the installation
location
The unit is designed for horizontal
installation on a base in outdoor
areas. The installation site must be
level and firm. The unit should be
secured to prevent toppling.
The unit can be installed outside as
well as inside a building.
In the case of outdoor installation,
please follow the instructions given
below to protect the unit against
the weather.
Rain
The unit should be at least 10 cm
off the ground when mounted on
the roof or ground.
For cooling and heating systems
(only HP-function) elevated instal-
lation increases the heating
capacity.
Sun
The finned condenser gives off
heat in the cooling mode.
Exposure to sunlight further in-
creases the temperature of the fins
and reduces the heat released by
the finned heat exchanger.
The unit should, whenever pos-
sible, be installed on the north side
of the building.
If necessary, take measures to pro-
vide sufficient shade (responsibility
of customer).
This can be done by building a
small roof covering.
However, the discharging warm air
flow must not be affected by this.
Wind
If the system is being installed
where it is windy, care must be
taken that the discharged warm air
(cooling mode) is carried off in the
prevailing wind direction. If this is
not possible, it may be necessa-
ry to install a windbreak on-site
(Figure 3).
Ensure that the windbreak does
not adversely affect the air intake-
to the unit.
Snow
The system should be wall-mounted
in areas where there is heavy snow-
fall. Mounting should be at least 20
cm above the expected snow level
to prevent snow from getting into
the system (Figure 4).
Installation inside buildings
Ensure that heat can dissipate
adequately when placing the
outdoor unit in cellars, attics,
adjoining rooms or halls
(Figure 5).
Install an additional fan with
the same air flow as that of the
outdoor unit being installed in
the room which can compen-
sate any additional pressure
losses. (Figure 5, Page 20).
Ensure a continuous and unob-
structed air flow from outside,
preferably using sufficiently
large air openings (Figure 5,
Page 20).
Cooling or heating perform-
ance changes as a conse-
quence of the ambient condi-
tions influenced by rain, sun,
wind, and snow.
NOTE
Wind
3 Windbreak
20 cm
Snow
4 Minimum clearance to snow
19
RVS 60H RVS 75H RVS 100H RVS 150H
A 250 250 350 350
B 250 300 350 400
C 1000 1200 1500 1500
D 600 600 800 800
E 600 600 700 700
All values in mm
Comply with any regulations
and conditions affecting the
structure of the building. If
necessary, use sound reducing
material.
Warm air Cold
fresh air
Light
well
Chiller
Warm air
Light
well
Additional
fan
5 Installation inside buildings (cooling mode)
Minimum clearances
The following illustration indicates
the minimum clearances for trou-
ble-free operation of the system.
These protection zones serve to
ensure unrestricted air intake and
discharge, as well as providing suf-
ficient room for performing main-
tenance and repairs and prevent-
ing the unit from being damaged.
Minimum clearances
RVS 60H / RVS 75H RVS 100H / RVS 150H
C
B
AD
E
C
B
AD
E
REMKO RVS...H (INOX)
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Remko RVS75H User manual

Category
Heat pumps
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI