EZ-CAL™ HIGH PRESSURE CUT-OUT TEST BLOCK & CALIBRATION KIT
OPERATION
Operation
OPERATION INSTRUCTIONS & TESTING
The Frick® EZ-CAL™ test block, 720B0129H01, is designed to
be installed between the compressor discharge connection
and the discharge pressure limiting device, (the high pressure
cut-out, or HPCO).
Figure 3. Test Block in Test & Run Position
Figure 4. Test Block in Run Position
The valve is lockable in the RUN position.
PRINCIPLES OF OPERATION
TEST BLOCK
The test block functions as a low pressure drop check valve,
not a stop valve, in the line from the discharge pressure
source to the HPCO. In the RUN position the HPCO is fully
open to the discharge pressure source.
In the TEST position an external pressure source is con-
nected to the test connection quick connect and when the
valve is switched to TEST position, the external source is
connected directly to the HPCO. This allows the function of
the HPCO and pressure setting to be conrmed by applica-
tion of external pressure while comparing the compressor
discharge pressure reading to a master gauge.
Once the HPCO is conrmed to trip the compressor at the
correct set point, the valve is switched back to run mode and
any high pressure trapped above the check valve is relieved
back to the system. Should an actual high pressure event
occur, even during testing, the check valve in the test block
will open and expose the HPCO to the high pressure level,
still allowing protection of the compressor during testing of
the HPCO.
One EZ-CAL™ test block should be installed permanently on
each compressor and only be used when the HPCO is to be
tested. They can be locked in the RUN position during normal
operation, but the compressor is still protected from a high
pressure event in either operational position.
NOTICE
Leaving the test block valve in the TEST position after
testing is complete can trap the external pressure be-
tween the HPCO and the test port.
The only risk by leaving the test block valve in the TEST posi-
tion after testing is complete is trapping the external pressure
between the HPCO and the test port. The discharge pressure
reading on the control panel would not see the decrease in
discharge pressure as the system is returned to normal op-
eration. Returning the test block valve to RUN position after
test opens a direct two-way connection between discharge
pressure and the HPCO transducer or switch.
During installation of the test block, care should be taken
to minimize total system volume from the test block to the
HPCO. Directly installing the HPCO on the test block will
keep the volume low, and be much easier to pressurize
during testing.
TEST PUMP CALIBRATION KIT (720B0129G01)
Figure 5. Calibration Kit in Hard Case with Hose
The test pump calibration kit comes complete with hydraulic
test pump, a 15 foot quick connect hose, oil reservoir, and
calibrated master gauge – all suitable for use with refrigera-
tion oil as the pressurizing media.
The pump is used to connect to the quick connect test port
on the test block. Once the test block is switched to the TEST
position, operation of the test pump will allow the technician
to raise the pressure measured at the HPCO until the run-
ning unit is proven to stop at the correct cut-out pressure.
The actual cut-out pressure can be compared between the
pressure display on the control panel and the master gauge
included with the test pump. If the reading is beyond the
permissible tolerance (generally 2.5% of cut-out pressure),
the control panel should be recalibrated to read correctly
at the set point.