Munters ComDry-M190Y Owner's manual

  • Hello! I am an AI chatbot trained to assist you with the Munters ComDry-M190Y Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Originalinstructions
Usermanual
ComDryM190Y
Desiccantdehumidier
190TEN-1082-E1404©MuntersEuropeAB2014
Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthe
faulthasoccurredwithinthewarrantyperiodand
thattheunithasbeenusedinaccordancewiththe
specications.Allclaimsmustspecifytheunittypeand
fabricationnumber.Thisinformationisstampedonthe
identicationplate,seesectionMarking.
Itisaconditionofthewarrantythattheunitforthe
fullwarrantyperiodisservicedandmaintainedas
describedinsectionServiceandmaintenance.Theservice
andmaintenancemustbedocumentedforthewarranty
tobevalid.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,theLowVoltageDirective2006/95/EC,
theRoHSDirective2011/65/ECandtheEMC
Directive2004/108/EC.Thedehumidieris
manufacturedbyanISO9001:2008accredited
manufacturingorganisation.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Pleasesendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
iiImportantuserinformation190TEN-1082-E1404
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
ii
Warranty...............................
ii
Safety..................................
ii
ConformitywithDirectives............
ii
Copyright..............................
ii
Tableofcontents...........................iii
1Introduction.................................1
1.1Aboutthismanual.....................
1
1.2Unintendeduse........................
1
1.3Safety..................................
1
1.4Marking................................
3
2Principleofoperation......................4
3Transport,inspectionandstorage.......5
3.1Transport..............................
5
3.2Inspectionofdelivery..................
5
3.3Storingtheequipment................
5
4Installation...................................6
4.1Safety..................................
6
4.2Closedsystem.........................
6
4.3Opensystem..........................
7
4.4Siterequirements.....................
7
4.5Ductsandhoses.......................
8
4.5.1Ductworkforoutdoorairinlet..
8
4.5.2Ductworkforwetairoutlet.....
8
4.5.3Connectingthewetairhose...
9
4.6Electricalconnections................
10
4.7Expandingthesystem................
11
4.8Accessories...........................
12
5Controlpaneloverview....................13
6Operation....................................14
6.1Safety..................................
14
6.2Introduction............................
14
6.2.1Humiditycontrol................
14
6.2.2Fanmodes.....................
14
6.2.3Fanspeed......................
14
6.3Initiationandstart.....................
15
6.3.1Bootthecontrolsystem........
15
6.3.2Startthedehumidier..........
15
6.4Stopthedehumidier.................
16
6.5Emergency............................
16
6.6Automaticstartafterpowerfailure....
16
6.7Navigatethemenus...................
17
6.8Accessthecontrolsystem............
18
6.9Changethesystemsettings..........
19
6.10Resetanalarm........................
20
6.11Resetthecounters....................
21
6.12Serviceintervalalarm.................
22
6.13Restorethedefaultsettings...........
23
6.14Accesslevels..........................
23
7Menusandparameters....................24
7.1Humidity...............................
24
7.1.1Internalcontrollingsensor.....
25
7.1.2Externalcontrollingsensors..
25
7.2Runtime...............................
26
7.3Power..................................
27
7.4Temperature...........................
28
7.5Functions..............................
30
7.5.1Processfanspeed.............
30
7.5.2Processfanmode..............
30
7.5.3Humiditycontrolandunits.....
30
7.5.4Displayinformation............
31
7.6Alarm...................................
33
7.7Min,maxanddefaultvalues..........
34
7.7.1Humidity........................
34
7.7.2Servicetime....................
34
7.7.3Functions.......................
34
8Serviceandmaintenance.................35
8.1General................................
35
8.2Maintenanceschedule................
35
8.3Processairlterchange..............
36
9Faulttracing.................................37
10Technicalspecication....................39
10.1Dimensionsandservicespace.......
39
10.2Capacitydiagram.....................
40
10.3Fancurveprocessair.................
40
10.4T echnicaldata.........................
41
11Scrapping....................................42
12ContactMunters............................44
190TEN-1082-E1404Tableofcontentsiii
ComDryM190Y
1Introduction
1.1Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforethedehumidieris
installedandused.
ContactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationortheuseofyour
dehumidier.
Thismanualmustbestoredinapermanentlocationclosetothedehumidier.
1.2Unintendeduse
Thedehumidierisnotintendedforoutdoorinstallation.
Thedehumidierisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipment
isrequired.
Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
1.3Safety
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualshallinnowaytakeprecedenceoverindividualresponsibilitiesorlocal
regulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
ThetypesofdangersthatareindicatedinthismanualaredescribedinsectionImportantuserinformation.
1Introduction190TEN-1082-E1404
ComDryM190Y
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbesplashedwithorimmersedinwater.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Theunitmustbeconnectedtoanearthedelectricaloutlet.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
-Donotoperatetheunitifthepowerplugorcordisdamaged,riskofelectricalshock.
-Donotpulltheplugwithwethands,riskofelectricalshock.
-Donotinsertngersoranyotherobjectsintotheairvents,rotatingfansareinside.
-Donotcovertheunitasthatcanblockairintakeoroutletandcauseare.
-Iftheunithasoverturned,cutthepowerimmediately.
-AlwayscontactMuntersforserviceorrepair.
190TEN-1082-E1404Introduction2
ComDryM190Y
1.4Marking
Figure1.1Identicationplateposition
Type
Fa br. No.
Fa br. ye a r
0,09 kW
Ma x 0,93 kW
1015 170XXX XXXXX
2010
ComDry M190Y
0
0
·
·
230V 50/60 Hz
Ma de in S we de n
Munters Europe AB
Isa fjords ga ta n 1
164 26 Kista , Swe de n
Weight: 11,5 kg
IP 33
0,84 kW
R
oHS
M
Figure1.2Identicationplate,anexample
Explanationof"Fabr.No."ontheidenticationplate:
10:Yearofmanufacture
15:Weekofmanufacture
170XXX:Articlenumber
XXXXX:Serialnumber
3Introduction190TEN-1082-E1404
ComDryM190Y
2Principleofoperation
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
ComDryM190Yusesoneinletairowforprocessairandforreactivationoftherotor.
1.Processair/Reactivationair
2.Dryair
3.Wetair
2
1
3
Figure2.1Principleofoperation
190TEN-1082-E1404Principleofoperation4
ComDryM190Y
3Transport,inspectionandstorage
3.1Transport
Transportthedehumidierbycarryingitbyitshandleorintheoriginalpackaging.Theunitmustalwaysbe
placedinanuprightpositionduringtransport.Failuretocomplywiththiscancausetheunittomalfunction.
Thepowercordshouldberolledupandplacedunderthehandlewhencarryingthedehumidier,see
Figure3.1.
Figure3.1Powercordplacement
3.2Inspectionofdelivery
1.Inspectthedeliveryandcomparewiththedeliverynote,orderconrmationorotherdelivery
documentation.Makesurethateverythingisincludedandnothingisdamaged.
2.ContactMuntersimmediatelyifthedeliveryisnotcompleteinordertoavoidinstallationdelays.
3.Iftheunitistobeputintostoragepriortoinstallation,seesectionStoringtheequipment.
4.Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasoccurredduring
transportation.
5.AnyvisibledamagemustbereportedinwritingtoMunterswithin5daysandpriortoinstallationof
theunit.
6.Disposeofthepackagingmaterialaccordingtolocalregulations.
3.3Storingtheequipment
CA CA
CA
UTION! UTION!
UTION!
Alwaysunplugtheunitfromthepowersupplywhennotinuse.
Followtheseinstructionsifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Re-usethepackagingmaterialtoprovideprotectionfortheunit.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
5Transport,inspectionandstorage190TEN-1082-E1404
ComDryM190Y
4Installation
4.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
Theunitmustbeconnectedtoanearthedelectricaloutlet.
Donotoperatetheunitifthepowerplugorcordisdamaged.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
4.2Closedsystem
Thedehumidierisplacedinthespacetobedehumidied.Thewetairistransportedoutdoorswith
ducting.Theprocess/reactivationairistakenfromthespacetobedehumidied.Toensurethatthedry
airisdistributedevenlyinthespacetobedehumidiedaductingcanbeconnectedtothedryairoutletof
thedehumidier.
Aclosedsystemispreferablewhenthereisaneedfordehumidicationtoaverydryclimate.Itismore
economicaltoruncomparedtoanopensystem.
1
2
3
Figure4.1Closedsystemprinciple
1.Process/Reactivationair
2.Dryair
3.Wetair
190TEN-1082-E1404Installation6
ComDryM190Y
4.3Opensystem
Thedehumidierisplacedoutsidetheareatobedehumidied.Dryairistransportedwithductingtothe
spacetobedehumidiedandthewetairisdischargedinthevicinityoftheunitormovedoutdoors,see
Figure4.2.Theinstallationisusedtosolvethefollowingproblems:
-Whenmoisturedamagedobjectsaretobedehumidied.
-Dustorcorrosioncausingparticlesarepresentinaspacewheredryairwillbesupplied.
-Topreventmoisturefromenteringthedehumidiedspace/object.
2
1
3
Figure4.2Opensystemprinciple
1.Process/Reactivationair
2.DryAir
3.Wetair
4.4Siterequirements
Thedehumidierisonlyintendedforindoorinstallation.Avoidinstallingthedehumidierinadamp
environmentwherethereisariskofwaterenteringtheunitorinaverydustyenvironment.Ifindoubt,
seekadvicefromMunters.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandtrouble-free
operation.Forspacerequirements,seesection10.1,Dimensionsandservicespace.
Ifthedehumidierisintendedtobeplacedonabracketwerecommendourspeciallydesignedwallbracket,
see4.8,Accessories.Alwaysleaveminimum10cmspacebetweentheunitandthewall.
7Installation190TEN-1082-E1404
ComDryM190Y
4.5Ductsandhoses
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
Ductlengthmustbekeptasshortaspossibletominimisestaticpressureloss.
Allductandhoseconnectionsmustbeairtightandvapourtighttoensurefullperformance.
Theductingmustalwaysbeinsulatedwhenthereisariskoffreezing.
Thetotalresistanceintheductworkmustnotexceedtheperformanceratingofthefansttedinthe
dehumidier.
NOTE!Maximumlengthofdryairhoseis25metres.
4.5.1Ductworkforoutdoorairinlet
Whenbringingoutsideambientairintothedehumidier,theopeningtotheinletductshouldbelocated
sufcientlyhighabovegroundleveltopreventthepickupofdustanddebris.Theductingshouldbe
designedtopreventrainandsnowfrombeingdrawnintothedehumidier.Theairinletmustbelocated
awayfrompossiblecontaminantssuchasengineexhaustgases,steamandharmfulvapours.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
4.5.2Ductworkforwetairoutlet
Wetairductingmustbeincorrosion-resistantmaterialandmustbecapableofwithstandingtemperaturesof
upto70°C.
Thewetairductingmustalwaysbeinsulatedifthereisariskoffreezing.Thewetairleavingthedehumidier
willeasilycausecondensationontheinsideoftheductwallsduetothehighmoisturecontent.
Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainpossible
condensation.Thedeclinemustbeatleast2cm/metreofduct.Drainageholes(5mm)shouldbemadeat
lowpointsoftheducttopreventwateraccumulation.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
Wetairhosesareusuallyguidedoutdoors.Inlargepremiseswherethedehumidierisoutsideofthespace
tobedehumidied,thewetairmustbeductedawayfromtheunitwithahoseofminimumlength2metres.
Makesurethatthewetairisnotsuckedbackintotheunitandthatthewetairdoesnotblowagainstmoisture
sensitiveobjects.
190TEN-1082-E1404Installation8
ComDryM190Y
4.5.3Connectingthewetairhose
Step
ActionIllustration
1
Thewetairoutletishiddenfortransportationpurposes.Pullout
theoutletatthejobsite.
2
Twisttheoutletinthedirectionofthearrowtolockandsecureit
inposition.
3
Connectthehose.Outletdiameteris50mm.
NOTE!Maximumlengthofwetairhoseis6metres.
9Installation190TEN-1082-E1404
ComDryM190Y
4.6Electricalconnections
Thedehumidierisdeliveredwitha2,7metrepowercable,equippedwithanearthedplug.Themain
electricalcomponentsareinstalledintheupperpartoftheunit.
CA CA
CA
UTION! UTION!
UTION!
Donotconnecttheunittoothermainsvoltagethanspeciedontheunit’sidenticationplate.
Themainsfrequencycanbeadjusted,seeTable7.5.
NOTE!Incaseofaxedinstallationwheretheplugisreplacedbyacircuitbreaker,checkthatthefuserating
inthecircuitbreakeriscorrect.
190TEN-1082-E1404Installation10
ComDryM190Y
4.7Expandingthesystem
CA CA
CA
UTION! UTION!
UTION!
NeverconnectComDrydirectlytoastandardEthernetnetwork,eveniftheconnectortypeisthesame(RJ45-8,
modularconnector).DoingsomightdamageboththeComDrycontrolsystemand/orthecomputernetwork.
AllComDrydehumidiersareequippedwithtwoCANBUSports,locatedbehindacovernexttothe
applianceinlet.Anindoorremotecontrol,externalhumidity/temperaturesensorsoranexternalsignalbox
canbeconnectedtotheseCANBUSports.Itdoesnotmatterwhichoftheabovedeviceswillbeconnected
towhichport.Whennoportisusedthetwoemptyterminationplugsmustbettedtotheports.
Figure4.3RemovethecoverFigure4.4,2CANBUSportswithemptyplugstted
11Installation190TEN-1082-E1404
ComDryM190Y
4.8Accessories
Therearesomeaccessoriesavailableasoptionstothedehumidier.
WallBracket.Theunitcanbemountedonthewall.
StubPipeKitisusedwhenthereisaneedtoconnectaninletductorhosetothedehumidier.
RemoteControlmakesitpossibletocontroltheunitfromdistance,deliveredwitha10metrecable.
Externalsignalboxisusedwhenthereisaneedtoconnecttoanexternalcontrolsystem.
RemoteRH/Tsensorforexternalmeasuringofhumidityandtemperature.
WallBracket
StubPipeKit
kWh
C
f
X
RemoteControl
Externalsignalbox
RemoteRH/Tsensor
190TEN-1082-E1404Installation12
ComDryM190Y
5Controlpaneloverview
C
f
X
kWh
1
2
3
4
5
6
A
B
C
RH1 55%
*
Menuindicators1-6
1.Humiditymenu4.T emperaturemenuA.Alarmindicator
2.Timemenu5.FunctionsmenuB.Operationindicator
3.Powermenu6.AlarmmenuC.On/Offbutton
MenubuttonFunction
Up/Rightbutton
Enter/Conrmationbutton
Down/Leftbutton
Table5.1Menubuttonfunctions
13Controlpaneloverview190TEN-1082-E1404
ComDryM190Y
6Operation
6.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotoperatetheunitifthepowerplugorcordisdamaged.
Donotinsertngersoranyotherobjectsintotheairvents.
Theunitcanrestartautomaticallywithoutwarningfollowingapowerfailure.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
6.2Introduction
6.2.1Humiditycontrol
TheComDrydehumidierisequippedwithasophisticatedmicroprocessorbasedcontrolsystem.This,in
combinationwiththebuilt-inhumidity/temperaturesensorintheprocessairinlet,makesitpossibletoset
boththecontrolandpresentationofthehumiditytoeitherrelativehumidity(RH%),dewpoint(Dp°C)or
absolutehumidity(Xgr/kg).Thecontrolsystemadditionallychecksthetemperaturesbeforeandafterthe
heater,aswellasinthewetairaftertherotor.Ahighsafetylevelisobtainedbyvarioustemperaturesensors.
Toohightemperaturesgivesareductionoftheheaterpower,whileexcessivetemperatureswillmakethe
systemissueanalarmandshutthedehumidierdowninacontrolledway.Forfurtherexplanation,see
7.1,Humidityand7.5,Functions.
NOTE!Thedehumidieralwaysoperatesinautomaticmode(moisturebasedoperation).Asdefaultitwilluse
thebuilt-inhumidity/temperaturesensor,asoptionanexternalsensor.
6.2.2Fanmodes
Dependingontheapplication,ifxedortemporarilyinstalledetc.,thedehumidiercanberunindifferent
processfanmodes:Fan“ON”(continuous),“INT”(INTermittent)or“DEM”(onDEMand).Forfurther
explanation,see7.5,Functions.
6.2.3Fanspeed
Therearethreeprocessfanspeedsettingsavailable:“HIGH”,“NORM”and“LOW”.Thespeedis
manuallysetbytheoperator.Forfurtherexplanation,see7.5,Functions.
190TEN-1082-E1404Operation14
ComDryM190Y
6.3Initiationandstart
6.3.1Bootthecontrolsystem
Connectthedehumidiertomains.Result:ThecontrolsystemwillinitiatebyashingallLEDsforafew
seconds,andthedisplayrstshowstheComDrymachinetype[[M190Y],thenthesetfrequency,e.g.
[50Hz]andnallythesoftwareversionnumber,e.g.[VER:1.00]andthecurrenthumiditylevel,e.g.[*RH1
46%].
NOTE!Thebootsequencetakesabout10seconds.Letthecontrolsystemnishthebootingbeforeattempting
tostartthedehumidier.
6.3.2Startthedehumidier
Followthesestepstostartthedehumidier:
StepActionIllustration
1PresstheOn/Offbutton(C)oncetostartthedehumidier.
Result:IfthemeasuredhumidityislowerthantheSetValue,
thegreenoperatingindicator(B)willstarttoashinalong
on/shortoffsequence.Dependingonfanmodesetting,the
processfanwillrunornot.Theunitisnowinstand-bymode.
C
B
2Thedehumidierstartstodehumidifywhenthemeasured
humidityisequalorgreaterthantheSetValue,andthe
operatingindicator(B)willshifttocontinuouslylit.
B
15Operation190TEN-1082-E1404
ComDryM190Y
6.4Stopthedehumidier
CA CA
CA
UTION! UTION!
UTION!
Donotunplugthedehumidierwhileitiscoolingdown.Ifunpluggeditmightleadtopermanentunitdamage.
Followthesestepstostopthedehumidier:
Step
Action
Result/Illustration
1
PressOn/Offoncetostopthedehumidier.Thegreenoperatingindicatorstartsashing
withequallylongandshortonandoffperiods.
2
Theunitcontinuestorunforawhileinordertocooldownand
thenstops.
6.5Emergency
CA CA
CA
UTION! UTION!
UTION!
Onlyquickstopthedehumidierinthecaseofanemergency.Thefanstopsandtheheatercanbeveryhot,which
canresultindamagetotheheaterandothercomponentsclosetoit.
Incaseofemergency,stopthedehumidierbypullingthemainsplugor,ifitispermanentlyconnected
tomains,byusingtheexternalswitch.
6.6Automaticstartafterpowerfailure
Ifthedehumidierisswitchedonitwillreverttooperationafterapowerfailure,regardlessofifitwas
runningorinstand-by.
190TEN-1082-E1404Operation16
ComDryM190Y
6.7Navigatethemenus
Thethreebuttons,andonthecontrolpanelmakeitpossibletonavigatethemenus.
Followthesestepstonavigatethemenus:
Step
Action
Result/Illustration
1
Toselectamenu,pressor.untiltheselectedmenuappears.
Theselectedmenuindicatorislit.
2
Toenterthemenu,press.
Themenuindicatorstarts
ashing.
f
X
3
Useortoscrollthroughthemenu.
4
Leavethemenubyusingandgoto[EXIT].
Press.
Themenuindicatorstops
ashing.
NOTE!Allmenulistsarecircular.Attheendofeachmenuyouwillnd
[
EXIT
]
.Thequickestwayofnavigating
thereistopress
onetimeafterhavingenteredamenu.
17Operation190TEN-1082-E1404
/