Buderus Logalux LTD550 Installation Instructions For Contractors

Type
Installation Instructions For Contractors
Read carefully before carrying out installation and maintenance.
Installation instructions for contractors
DHW cylinder
Logalux
6 720 817 906-00.1T
LTN, LTD, LTH, LF 400...3000
L2TN, L2TD, L2TH, L2F 800...6000
L3TN, L3TD, L3TH, L3F 1200...2250
6 720 818 806(2015/12)GB
Table of Contents
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
2
Table of Contents
1 Explanation of symbols and safety instructions . . . . . . . . . . . . 3
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Information on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Determined use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3.1 DHW cylinders in the LTN/LTH/LTD series . . . . . . . . . . . 4
2.3.2 DHW cylinders in the LF series . . . . . . . . . . . . . . . . . . . . . 4
2.4 Product data for energy consumption . . . . . . . . . . . . . . . 4
2.5 CE Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . 4
2.6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.7 Tools, materials and assembly aids . . . . . . . . . . . . . . . . . 5
2.8 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.8.1 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.8.2 Dimensions and specifications for LT . . . . . . . . . . . . . . . 6
2.8.3 Dimensions and specifications for LF . . . . . . . . . . . . . . . 7
2.8.4 Safety limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1.1 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1.2 Positioning the DHW cylinder . . . . . . . . . . . . . . . . . . . . 10
5.2 Hydraulic connection . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.3 Fitting the manhole cover gasket . . . . . . . . . . . . . . . . . 13
5.4 Fitting the thermal insulation, control unit
and immersion heaters . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.1 Fitting thermal insulation to the back panel . . . . . . . . . 14
5.4.2 Fitting the control unit . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.3 Fitting the immersion heater (accessories) . . . . . . . . . 17
5.4.4 Fit the thermal insulation to the front panel
and attach it with fixing straps . . . . . . . . . . . . . . . . . . . . 17
5.4.5 Fitting the thermal insulation, control units and
immersion heaters for double and triple cylinders . . . .18
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1 Filling the DHW cylinder and checking for leaks . . . . . 20
6.2 District heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.1 Shutting down the DHW cylinder . . . . . . . . . . . . . . . . . 21
7.2 Shutting down the DHW cylinder if there is a
risk of frost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.1 Operating the control unit . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Control of steam-heated DHW cylinders . . . . . . . . . . . 21
9 Cleaning and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.1 Preparing the DHW cylinder for cleaning . . . . . . . . . . . 22
9.2 Cleaning the DHW cylinder . . . . . . . . . . . . . . . . . . . . . . 22
9.3 External current anode . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.4 Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10 Environmental protection/disposal . . . . . . . . . . . . . . . . . . . . 23
1 Explanation of symbols and safety instructions
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
3
1 Explanation of symbols and safety instructions
1.1 Key to symbols
Warnings
The following signal words are defined and can be used in this
document:
NOTICE indicates that material damage may occur.
CAUTION indicates that minor to medium personal injury may occur.
WARNING indicates that severe to life-threatening personal injury
may occur.
DANGER indicates that severe to life-threatening personal injury will
occur.
Important information
Additional symbols
1.2 Safety instructions
Installation, conversion
Fire risk!
Soldering and welding can lead to a risk of fire, as the thermal
insulation is combustible.
Only permit an authorised contractor to install or convert this DHW
cylinder.
Risk to life from electric current!
Ensure that electrical work is only carried out by an authorised
electrician.
Before beginning electrical work, isolate the heating system from the
mains power supply using the heating system emergency stop switch
and by removing the mains fuse. Secure it against unintentional
reconnection.
Using suitable means, test that the mains voltage is disconnected.
After the complete cylinder installation has been finished, carry out
an earth lead test in accordance with IEC/EN 60335 (also include
metallic screw connection fittings).
Function
In order to ensure trouble-free operation, these installation and
maintenance instructions must be observed.
Risk of scalding!
When the DHW cylinder is in operation, hot water temperatures
> 60 °C can occur.
Maintenance
Customer recommendation: Arrange a maintenance and inspection
contract with an approved contractor. Have the DHW cylinder
inspected in accordance with tab. 9, page 22 and serviced if
required.
Only use genuine spare parts!
Instructing the customer
Inform the user about how to operate the DHW cylinder and draw
attention in particular to points concerning safety.
Hand over the installation and maintenance instructions to the user
for safekeeping near the heating system.
Using the immersion heater
Observe the following points for operation with an immersion heater in
order to maintain corrosion protection and to adhere to the rules on
electrical safety:
Operate a DHW cylinder with immersion heater and external
current anode only with a 30 mA fault current switch!
Use only metal connection fittings in potable water heating systems
with plastic pipes.
Never use plastic threads for immersion heaters.
Only use immersion heaters fitted with insulation.
Warnings in this document are identified by a warning
triangle printed against a grey background.
Keywords at the start of a warning indicate the type and
seriousness of the ensuing risk if measures to prevent
the risk are not taken.
This symbol indicates important information where there is
no risk to people or property.
Symbol Explanation
Step in an action sequence
Cross-reference to another part of the document
List entry
List entry (second level)
Table 1
2 Information on the device
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
4
2 Information on the device
2.1 Determined use
The Logalux LTN/LTD/LTH/LF DHW cylinders are intended for heating
and storing potable hot water. The potable water supply must comply
with the requirements of the local Drinking Water Ordinance.
2.2 Scope of delivery
Check that the delivery is complete and undamaged.
The scope of delivery varies depending on the product type:
Storage cylinder unpackaged (up to 3 units)
Control unit and mounting casing (up to 3 cartons)
Cylinder size 400 l – 950 l:
Thermal insulation made of 2 sections
Split back panel
Front panel with cover
Fixing straps
Cylinder size 1500 l – 3000 l:
Thermal insulation made of 4 sections
Split back panel
Front panel with cover
Fixing straps
2.3 Product description
The DHW cylinders in the Logalux LTX/LF series are supplied as single,
double and triple cylinders.
2.3.1 DHW cylinders in the LTN/LTH/LTD series
The DHW cylinders in the Logalux LTN/LTH/LTD series are available as
LTN for standard output, LTH for high output and LTD for steam
operation.
The main components of the Logalux LTN DHW cylinder are:
Horizontal DHW cylinder with corrosion protection and thermometer
as single, double or triple cylinder
The cathodic corrosion protection consists of the hygienic Buderus
DUOCLEAN MKT thermal glaze and one (or 2, depending on the
version) external current anode(s) with integral control unit
potentiometer. The DHW cylinder is suitable for heating via district
heating or via boilers.
Up to 3 control units (depending on the version) with thermometer
for activation of one (or 2, depending on the version) external
current anode(s)
Smooth-tube heat exchanger (number depending on cylinder
capacity)
Thermal insulation made of 2 (4) 90 mm thick, CFC-free high-
performance insulation sections
If required, joining bracket to connect the individual cylinders
Manhole opening for cleaning and inspections
2.3.2 DHW cylinders in the LF series
The main components of the DHW cylinders in the Logalux LF series are:
Horizontal DHW cylinder with thermometer and corrosion protection
The DHW cylinder is suitable for heating with an external heat
exchanger.
The cathodic corrosion protection consists of the hygienic Buderus
DUOCLEAN MKT thermal glaze and one external current anode, as
well as a loading port for external heat exchanger.
Up to 3 SPI 1010 control units (depending on the version), each one
for activation of an external current anode
Thermal insulation made of 2 (4) 90 mm thick, CFC-free high-
performance insulation sections
If required, joining bracket to connect the individual cylinders
2.4 Product data for energy consumption
The following product data satisfies the requirements of EU Regulations
No. 811/2013 and No. 812/2013, which supplement Directive
2010/30/EU.
2.5 CE Declaration of Conformity
The design and operation of the LTN, LTH, LTD and LF DHW cylinders
conform to the European Directives and supplementary national
requirements. Compliance is demonstrated by the CE marking.
You can view the Declaration of Conformity for the product on the
Internet at www.buderus.de/konfo or request a copy from your local
Buderus office.
2.6 Accessories
Immersion heater
Logamatic 4126 control unit and FM445 function module for
domestic hot water supply
SLP heat exchanger set (only LF)
Salt water resistant version, comprising an additional coating;
required where water conductivity is > 150 mS/m
Article number Product type
Cylinder
volume
[l]
Heat losses
[W]
Energy efficiency
class
Domestic hot
water supply
7 747 303 255 LF400 360.0 106.7 D
7 747 303 256 LF550 550.0 125.8 D
7 747 303 257 LF750 750.0 160.7 D
7 747 303 258 LF950 950.0 175.3 D
7 747 303 259 LF1500 1500.0 243.8 E
7 747 303 260 LF2000 2000.0 252.2 E
7 747 302 758 LTD400 360.0 106.7 D
7 747 302 759 LTD550 550.0 125.8 D
7 747 302 760 LTD750 750.0 160.7 D
7 747 302 761 LTD950 950.0 175.3 D
7 747 302 762 LTD1500 1500.0 243.8 E
7 747 303 213 LTD2000 2000.0 252.2 E
7 747 302 753 LTH400 360.0 106.7 D
7 747 302 754 LTH550 550.0 125.8 D
7 747 302 755 LTH750 750.0 160.7 D
7 747 3027 56 LTH950 950.0 175.3 D
7 747 302 757 LTH1500 1500.0 243.8 E
7 747 303 227 LTH2000 2000.0 252.2 E
7 747 302 748 LTN400 360.0 106.7 D
7 747 302 749 LTN550 550.0 125.8 D
7 747 302 750 LTN750 750.0 160.7 D
7 747 302 751 LTN950 950.0 175.3 D
7 747 302 752 LTN1500 1500.0 243.8 E
7 747 303 241 LTN2000 2000.0 252.2 E
Table 2 Product data for energy consumption
2 Information on the device
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
5
2.7 Tools, materials and assembly aids
In order to install the DHW cylinder, you need standard tools as used for
gas and water installations.
In addition to this, transport by crane or two pallet trucks may also be
useful.
2.8 Specifications
2.8.1 Connections
Fig. 1 LT/LF connections
AW DHW outlet
EK/EL Cold water inlet/drain
EW DHW inlet (external heat exchanger)
EZ Circulation
IA
1
First external current anode
IA
2
Second external current anode, from a cylinder capacity of 2000 l
RS Boiler return
VS Flow
MROH Test point for controller without auxiliary energy
EH Immersion heater (2, 3 or 4 heaters)
MW Test point for domestic hot water temperature
MSTB Test point for high limit safety cut-out
MTR Test point for temperature control
6 720 817 906-01.1T
To ensure that the cylinder can be drained quickly, use
the same connection diameter for the tee on the cold
water inlet and drain connector (EK/EL).
2 Information on the device
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
6
2.8.2 Dimensions and specifications for LT
Fig. 2 Dimensions of LT
Cylinder type 400 550 750 950 1500 2000 2500 3000
Individual cylinder capacity I 400 550 750 950 1500 2000 2500 3000
Diameter D Ø 650 800 800 900 1000 1250 1250 1250
Width B mm 810 1000 1000 1100 1200 1450 1450 1450
Length L mm 1600 1510 1910 1910 2405 2150 2570 2970
Height H
1
mm 830 1010 1010 1110 1210 1460 1460 1460
H
2
mm 1680 2030 2030 2230 2430 2930 2930 2930
H
3
mm 2530 3050 3050
Adjustable feet A
LT/L2T
mm 400 470 470 520 560 680 680 680
A
L3T
mm 600 700 700
A
2
mm 410 400 400 420 445 505 505 505
A
3
mm 535 470 865 820 1270 890 1310 1710
Cylinder flow Ø VS DN 50 50 50 50 65 80 80 80
H
VS
mm 540 550 550 550 585 725 990 990
H2
VS
mm 1390 1570 1570 1670 1805 2195 2460 2460
H3
VS
mm 2240 2590 2590
Cylinder return Ø RS DN 50 50 50 50 65 80 80 80
H
RS
mm 240 250 250 250 285 285 290 290
H2
RS
mm 1090 1270 1270 1370 1505 1755 1760 1760
H3
RS
mm 1940 2590 2590
Cold water inlet Ø EK DN R 1 1/2 R 1 1/2 R 1 1/2 R 1 1/2 R 2 R 2 R 2 1/2 R 2 1/2
H
EK
mm 145 160 160 160 165 165 175 175
H2
EK
mm 995 1180 1180 1280 1385 1635 1645 1645
H3
EK
mm 1845 2200 2200
DHW circulation inlet Ø EZ DN R 1 1/4 R 1 1/4 R 1 1/4 R 1 1/4 R 1 1/2 R 1 1/2 R 2 R 2
H
EZ
mm 470 570 570 620 690 835 835 835
H2
EZ
mm 1310 1590 1590 1740 1910 2305 2305 2305
H3
EZ
mm 2160 2610 2610
Table 3 Dimensions and connections
6 720 817 906-02.1T
2 Information on the device
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
7
2.8.3 Dimensions and specifications for LF
Fig. 3 Dimensions of LF
DHW inlet Ø AB DN R 1 1/2 R 1 1/2 R 1 1/2 R 1 1/2 R 2 R 2 R 2 1/2 R 2 1/2
H
AB
mm 705 860 860 960 1055 1300 1295 1295
H2
AB
mm 1555 1880 1880 2080 2275 2770 2765 2765
H3
AB
mm 2405 2900 2900
Weight, net
(incl. thermal insulation)
LTN kg 330 367 470 517 875 1145 1300 1460
LTH kg 363 400 520 567 957 1254 1436 1596
LTD kg 330 367 439 486 819 1068 1204 1364
L2TN kg 682 762 968 1066 1784 2331 2641 2961
L2TH kg 748 828 1068 1156 1948 2549 2913 3233
L2TD kg 682 762 906 1004 1672 2177 2449 2769
L3TN kg 1034 1157 1466
L3TH kg 1133 1256 1616
L3TD kg 1034 1157 1373
Cylinder type 400 550 750 950 1500 2000 2500 3000
Individual cylinder capacity I 400 550 750 950 1500 2000 2500 3000
Diameter D Ø 650 800 800 900 1000 1250 1250 1250
Width B mm 810 1000 1000 1100 1200 1450 1450 1450
Length L mm 1600 1510 1910 1910 2405 2150 2570 2970
L
SP
mm 1355 1265 1665 1665 2160 1905 2325 2725
Height H
1
mm 830 1010 1010 1110 1210 1460 1460 1460
H
2
mm 1680 2030 2030 2230 2430 2930 2930 2930
H
3
mm 2530 3050 3050
Adjustable feet A
LF/L2F
mm 400 470 470 520 560 680 680 680
A
L3F
mm 600 700 700
A
2
mm 410 400 400 420 445 505 505 505
A
3
mm 535 470 865 820 1270 890 1310 1710
Table 4 Dimensions and connections
Cylinder type 400 550 750 950 1500 2000 2500 3000
Table 3 Dimensions and connections
6 720 817 906-03.1T
2 Information on the device
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
8
2.8.4 Safety limits
Loading port Ø AL DN 50 50 50 50 65 80 80 80
H
AL
mm 240 250 250 250 285 285 290 290
H2
AL
mm 1090 1270 1270 1370 1505 1755 1760 1760
H3
AL
mm 1940 2590 2590
Cold water inlet Ø EK DN R 1 1/2 R 1 1/2 R 1 1/2 R 1 1/2 R 2 R 2 R 2 1/2 R 2 1/2
H
EK
mm 145 160 160 160 165 165 175 175
H2
EK
mm 995 1180 1180 1280 1385 1635 1645 1645
H3
EK
mm 1845 2200 2200
DHW circulation inlet Ø EZ DN R 1 1/4 R 1 1/4 R 1 1/4 R 1 1/4 R 1 1/2 R 1 1/2 R 2 R 2
H
EZ
mm 470 570 570 620 690 835 835 835
H2
EZ
mm 1310 1590 1590 1740 1910 2305 2305 2305
H3
EZ
mm 2160 2610 2610
DHW outlet Ø AB DN R 1 1/2 R 1 1/2 R 1 1/2 R 1 1/2 R 2 R 2 R 2 1/2 R 2 1/2
H
AB
mm 705 860 860 960 1055 1300 1295 1295
H2
AB
mm 1555 1880 1880 2080 2275 2770 2765 2765
H3
AB
mm 2405 2900 2900
Weight, net
(incl. thermal insulation)
LF kg 290 327 367 414 708 923 1022 1182
L2F kg 602 685 762 860 1450 1887 2085 2405
L3F kg 914 1040 1157
Cylinder type 400 550 750 950 1500 2000 2500 3000
Table 4 Dimensions and connections
NOTICE: Exceeding the limits can damage the cylinder!
In order not to damage the DHW cylinder, observe
the limits given below for technical safety reasons.
Permitted maximum
values
Temperature
[ °C]
Operating pressure
[bar]
Heating water
1)
1) Only Logalux LTN, LTH, LTD
160 16
Domestic Hot Water 95 10
Table 5 DHW cylinder safety limits
3 Regulations
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
9
3 Regulations
Standards and directives
Supplementary or other requirements (e.g. mains
connection requirements) may apply depending on the
installation location (e.g. in different countries or regions).
Observe the country-specific or regional regulations,
directives and standards (e.g. those of the power supply
utility) during the installation and operation of the DHW
cylinder and immersion heater.
Germany
Installation and equipment of heating and DHW supply
systems
Electrical connection Product standards
DIN 1988-100: Technical Regulations for Drinking
Water Installations (TRWI)
DIN 4701: Regulations for calculating the heat demand
(heating load) of buildings
DIN 4708: Central water heating systems
DIN 4747-1: District heating systems - Part 1:
Technical safety equipment for substations, domestic
stations and domestic systems for connection to
district heating water networks
DIN 4751: Water heating systems
DIN 4753-1: Potable water heaters, potable water
heating systems and potable water cylinder heaters -
Part 1: Containers with a volume > 1000 l
DIN 18380: VOB
1)
; heating systems and central water
heating systems
DIN 18381: VOB
1
); gas, water, and waste water
installation work within buildings
DIN 18421: VOB
1)
; insulation work on technical
systems
AVB
2)
Water
DIN EN 1717: Protection of potable water against
contamination ...
DIN EN 806-5: Technical rules for potable water
installations
DVGW W 551: Potable water heating systems and pipe
systems; technical measures to inhibit the growth of
legionella in new systems
Code of Practice W 553: Measurement of DHW
circulation systems ...
VDI 2036: Technical building systems with district
heating
Technical rules for steam (TRD)
Pressure Equipment Directive (DGRL)
German Health & Safety at Work regulation (BetrSichV)
1) VOB: German contract procedures for building work – Part C: General technical conditions of contract for building work (ATV)
2) Invitation to tender templates for building work in overground construction, particularly with regard to residential buildings
DIN VDE0100: Installation of
HV systems with rated voltages of
1000 V
VDE0190: Equipotential bonding of
electrical systems
DIN 18 382 VOB
1)
: Electrical
cabling and wiring installations in
buildings
IEC/EN 60335: Safety of electrical
devices for household use and
similar purposes
DIN 4753: Water heaters and DHW heating systems for
potable water and heating water
DIN 4753, Part 3: Water heaters and water heating
systems for potable water and heating water; enamel
coating for corrosion protection on the water side;
requirements and testing
DIN 4753, Part 6: Water heating systems for potable
water and heating water; cathodic corrosion protection
for enamelled steel containers; requirements and
testing
DIN 4753, Part 7: Containers with a volume of
1000 l, requirements for the manufacture, thermal
insulation and corrosion protection
DIN 4753, Part 8: Thermal insulation of water heaters
of 1000 l rated content – Requirements and testing
DIN EN 12897: Water supply – Specification for
indirectly heated and unventilated DHW cylinders
Table 6 Technical rules for the installation of DHW cylinders (selection) in Germany
4 Transport
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
10
4 Transport
The DHW cylinder can be transported with a pallet truck or a crane.
Transport by crane
Hook the lifting hooks on the cables into the two eyelets [1].
Hook the lifting hook of the crane into the cable.
Set the DHW cylinder down gently.
Fig. 4 Eyelets on the DHW cylinder
[1] Eyelets
5 Fitting
5.1 Installation
5.1.1 Installation location
5.1.2 Positioning the DHW cylinder
Position the DHW cylinder on a level floor that has adequate load-
bearing capacity.
Observe the minimum clearances in the installation location for
maintenance, fitting and repair ( Fig. 5).
Ensure that the clearance from the top edge of the DHW cylinder to
the ceiling is not less than 500 mm.
Align the DHW cylinder so that it is horizontal and stable.
Insert metal shims underneath if necessary.
In the case of double and triple cylinders, fasten the storage cylinders
together before fitting the thermal insulation.
In the case of triple cylinders, ensure that the cylinder feet are
secured.
Fig. 5 Minimum clearances
DANGER: Risk to life through falling load!
Only use lifting cables that are in a faultless condition.
Only hook the lifting hooks into the eyelets provided.
NOTICE: Risk of damage from inappropriate securing
during transport!
Use only suitable means of transport for handling the
load.
NOTICE: Risk of system damage due to frost!
The system can freeze up during frost, if it is not in
operation.
Only install the DHW cylinder in a frost-proof room,
or drain a cylinder that is not in use, if there is a risk
of frost.
Rated content Wall clearance
[l] A, [mm] B, [mm]
400...550 900 1100
750...3000 1200 1700
Table 7 Minimum clearances
> 1m
6 720 817 906-04.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
11
5.2 Hydraulic connection
So that later damage to the DHW cylinder is prevented:
Use metal connectors in potable water heating systems with plastic
pipes.
Use installation material that is temperature-resistant at 95 °C.
Use only screw fittings, and with shut-off valves if required, for all
connection pipes to the cylinder.
Install an air vent valve in the DHW line upstream of the shut-off valve.
Install the drain provided by the customer to the bottom cylinder
connection.
In order to facilitate blow-down, never install elbows in the drain
pipe.
Fit all connection pipes in such a way that they are free of tension.
Seal off all cylinder connections that are not used.
Fig. 6 Connection diagram for hydraulic connection
[1] Storage cylinder
[2] Air vent valve
[3] Shut-off valve with drain valve
[4] Pressure relief valve
[5] Non-return valve
[6] Shut-off valve
[7] DHW circulation pump
[8] Pressure reducer (if required)
[9] Test valve
[10] Non-return component
[11] Pressure gauge connector
[12] Drain
If there is an arrangement of several DHW heaters, make the
connections for both domestic hot water and heating water in
parallel in accordance with the Tichelmann system ( Fig. 7,
page 12).
DANGER: Risk of fire from soldering and welding!
As far as possible, carry out any soldering and welding
work before fitting the thermal insulation.
Take appropriate safety measures when soldering and
welding, since the thermal insulation is combustible;
for example, cover the thermal insulation.
Check the integrity of the thermal insulation after
completing work.
DANGER: Risk to health through contaminated water!
Fitting work carried out without due care for cleanliness
can result in contamination of the potable water.
Install and equip the DHW cylinder hygienically and in
accordance with national standards and guidelines.
Flush the DHW cylinder and pipework thoroughly with
potable water after fitting.
To ensure that the cylinder can be drained quickly, use
the same connection diameter for the tee on the cold
water inlet and drain connector (EK/EL).
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
12
Fig. 7 Connection diagram for hydraulic connection with 2 water heaters
AW DHW outlet
EK Cold water inlet
EZ DHW circulation inlet
[1] Diaphragm safety valve, component-tested in accordance
with DIN 4753-1 (1 piece per cylinder, if these can be shut
off individually)
[2] Drain valve
[3] Shut-off device
[4] Air vent valve
[5] Shut-off valve with drain valve
[6] DHW circulation pump with timer
[7] Non-return valve
[8] Pressure reducer; if the line pressure is higher than 80 % of
the response pressure of the pressure relief valve
[9] Test valve
[10] Non-return component
[11] Pressure gauge connector in accordance with DIN 4753-1
< 1000 litres cylinder capacity; pressure gauge in
accordance with DIN 4753-1 > 1000 litres cylinder capacity
[12] Tee and drain valve (important for quicker flushing/draining)
[13] Temperature sensor; high limit safety cut-out with flow
temperature > 110 °C
[14] Temperature sensor for temperature controller
[17] Water filter
[18] Setting element
[19] Thermometers
[1...19] All parts provided by the customer.
Pressure relief valve (provided by the customer)
Attach a notice with the following text to the pressure relief valve:
"Never close the discharge pipe. Water may escape for safety
reasons during heating."
Design the cross section of the discharge pipe in such a way, that it at
least matches the outlet cross section of the pressure relief valve
( Tab. 8).
Test the standby status of the pressure relief valve from time to time
by venting it.
Checking for leaks
Check all connections and the cover of the inspection aperture for leaks.
6 720 817 906-05.1T
13
1
17
19
18
VHF
RHF
2
3
3
12
81011
9
14
4
5
3
6
7
3
AW
EZ
EK
3
3
3
3
Connection diameter
at least
Rated content of the
water vessel
Maximum
heat output
1)
1) Output information in accordance with DIN 4708 in the case of Tv = 80 °C or steam positive pressure = 1 bar. Observe the relevant max. heating output for other flow
temperatures and steam pressures.
Series
I kW LT...N LT...H LT...D LF
DN20 200...1000 150 400...950 400...550
DN25 1000...5000 250 1500 750...950 400...1500 400...950
DN32 > 5000 1000 2000...3000 1500...3000 2000...3000 1500...3000
Table 8 Sizing the discharge pipe
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
13
5.3 Fitting the manhole cover gasket
Release the nuts and remove the manhole cover.
Position the manhole cover gasket on the manhole cover.
The curved radius of the manhole cover and the formed radius of the
manhole cover gasket should lie precisely on top of each other.
Fig. 8 Fitting of manhole cover gasket
[1] Manhole cover gasket
[2] Manhole cover
Fig. 9 Manhole cover gasket positioned precisely on the manhole
cover
[1] Manhole cover gasket
[2] Manhole cover
Insert the manhole cover with the manhole cover gasket into the
manhole and tighten it.
5.4 Fitting the thermal insulation, control unit and
immersion heaters
The thermal insulation consists essentially of the insulation around the
edge, plus the front and back panel sections.
With the exception of the covers for the front panel and back panel, all
thermal insulation sections are marked with numbers for better
definition ( Fig. 10).
Fig. 10 Numbering schedule for thermal insulation sections
6 720 817 906-36.1T
1
2
6 720 817 906-37.1T
1
2
We recommend fitting the thermal insulation only after
installation and leak test.
In the case of the 400 l cylinder size, the thermal insulation
consists of only 2 sections.
No fixing strap in the centre is required.
In the case of the 2000 l cylinder size and larger, a second
external current anode is fitted in the back panel (apart from
the LF series).
Before fitting the thermal insulation sections C and D,
route the anode cable on the storage cylinder to the
control unit.
Fit the control unit and carry out all electrical work before
fitting the front panel.
6 720 817 906-06.1T
1
3
4
2
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
14
5.4.1 Fitting thermal insulation to the back panel
The thermal insulation is shown fitted to a single cylinder.
Remove the fabric plugs from the hole devices in the back panel.
Fig. 11 Removing the fabric plugs from the hole devices
Lay the thermal insulation sections for the back panel onto the back
panel.
Fig. 12 Fitting the thermal insulation sections for the back panel
Lay the bottom/back thermal insulation section ( Fig. 10, [1],
page 13) under the cylinder and insert the slits into the cylinder feet.
Fig. 13 Laying the thermal insulation section under the cylinder
Push the top/back thermal insulation section ( Fig. 10, [2],
page 13) against the bottom section, so that the bottom hook locking
bracket latches into place.
Fig. 14 Push the top thermal insulation section against the bottom
thermal insulation section
If required, attach the assembly aids.
Fig. 15 Attaching the assembly aids
Wind the joined thermal insulation sections around the cylinder.
Fig. 16 Winding the thermal insulation around the cylinder
6 720 817 906-18.1T
6 720 817 906-16.1T
6 720 817 906-07.1T
6 720 817 906-19.1T
6 720 817 906-21.1T
6 720 817 906-20.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
15
Join thermal insulation sections 1 and 2 ( Fig. 10, page 13) by
means of the top hook locking bracket.
Fig. 17 Joining the thermal insulation with hook locking bracket
Attach thermal insulation sections 3 and 4 ( Fig. 10, page 13) in
the same way as sections 1 and 2 ( Fig. 10, page 13).
Fig. 18 Attach thermal insulation sections 3 and 4
( Fig. 10, page 10).
Close the gaps on the bridge and feet with the fabric strips.
Fig. 19 Close the gaps with the fabric strips.
[1] Gap
[2] Fabric strips
Attach the adhesive rosettes on the bridge/feet.
Fig. 20 Attaching the adhesive rosettes on the bridge/feet
5.4.2 Fitting the control unit
Remove the recess cylinder of the cable hole from the thermal
insulation with a cutter blade.
Fig. 21 Removing the recess in the thermal insulation
6 720 817 906-22.1T
6 720 817 906-23.1T
6 720 817 906-32.1T
1
2
6 720 817 906-25.1T
6 720 817 906-26.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
16
Fasten the mounting casing with 4 self-tapping screws.
Fig. 22 Screwing the mounting casing in place
Route all cables and sensor leads from the control unit through the
cable hole to the sensor pocket and external current anode.
Fig. 23 Routing the cable through the cable hole
Place the control unit in the mounting casing and screw it into place.
( Fig. 22, page 16).
Fig. 24 Fitting the control unit
Screw the tab for the earth conductor ( Fig. 25, [1]) to the tab on
the storage cylinder.
Push the blade terminal of the anode cable (fitted to control unit)
onto the lug of the external current anode ( Fig. 25, [2]).
Route the temperature sensor, temperature controller and high limit
safety cut-out with a dummy into the sensor pocket ( Fig. 25, [3])
in the manhole cover and secure them with the threaded pin.
Fig. 25 Fitting the temperature sensor, temperature controller and
high limit safety cut-out
[1] Tab for earth conductor
[2] External current anode
[3] Sensor pocket
Make the electrical connection in accordance with the wiring
diagram.
Ensure that the cables and leads are routed correctly, e.g. under the
cover of the hook locking bracket.
Connect the power supply.
In the case of a cylinder size > 2000 l, attach the second anode as
follows ( Fig. 26).
Fig. 26 Making the electrical connection to the control unit
[1] Tab for earth conductor
[2] Second external current anode
6 720 817 906-11.1T
6 720 817 906-27.1T
6 720 817 906-11.1T
1.
2.
Connect the second external current anode (2000 l
cylinder size) in the same way.
6 720 817 906-09.1T
6 720 817 906-10.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
17
5.4.3 Fitting the immersion heater (accessories)
If operating with an immersion heater, observe local regulations (e.g.
switch-on times).
Connect the immersion heater with 2 rows of contactors to the
SPI 1030 and SPZ 1030 (2000 l) control units in accordance with
the wiring diagram.
Unscrew the plug from the connector in the front panel of the
cylinder.
Seal in the immersion heaters ( Fig. 27, [2], page 17) in such a
way, that the cable entry is arranged at the bottom.
Route all the cables and sensor leads through the cable hole
( Fig. 23, page 23) in the thermal insulation section from the
control unit to the sensor pocket, external current anode and
immersion heaters.
Make the electrical connection in accordance with the wiring
diagram.
Ensure that the cables and leads are routed correctly.
Further fitting of the control unit ( Fig. 24... 26, page 16)
Fig. 27 Cabling the immersion heaters
[1] Connections for immersion heaters
Close the cable hole in the thermal insulation section with a flexible
foam plug.
Connect the power supply.
Place the control unit in the mounting casing and screw it into place.
( Fig. 24, page 16).
5.4.4 Fit the thermal insulation to the front panel and attach it
with fixing straps
Check whether the external current anode and earth conductor are
connected.
Fit the thermal insulation with manhole recess to the front panel.
Fig. 28 Fitting the thermal insulation for the front panel
Attach the manhole cover.
Fig. 29 Attaching the manhole cover
DANGER: Risk to life from electric current!
Before beginning electrical work, isolate the heating
system from the mains power supply using the
emergency stop switch and by removing the mains
fuse. Secure it against being switched on again
unintentionally.
The first row of contactors is switched by the temperature
controller, and the second row of contactors by the high
limit safety cut-out as required.
The casing of the immersion heaters can be rotated in every
position.
6 720 817 906-12.1T
1
In the case of the 400 l cylinder size, no thermal insulation
sections are required for the front panel.
6 720 817 906-28.1T
6 720 817 906-29.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
18
Place the fixing straps around the front and back panels and tension
them.
Fig. 30 Tensioning the front and back panels
Place the middle tensioning wheel around the front and back panels
in the same way and tension it, so that the position where they butt
together is covered.
Fig. 31 Placing the middle tensioning wheel around the front and back
panels
Attach the cover of the hook locking bracket.
Fig. 32 Attaching the cover of the hook locking bracket
Press the foam wedges into the feet.
Fig. 33 Pressing the foam wedges into the feet
5.4.5 Fitting the thermal insulation, control units and
immersion heaters for double and triple cylinders
To ensure greater stability, screw 4 cylinder feet [2] to all triple
cylinders, using 2 screws [2] and nuts [3] for each foot.
Fasten each foot to the floor with a screw and rawl plug.
Fig. 34 Fixing triple cylinders to the floor
[1] Screw
[2] Cylinder foot
[3] Nut
[4] Washer
[5] Connecting screw
In the case of double and triple cylinders and in contrast to the single
cylinder, particularly close attention must be paid to the joining of the
storage cylinders and the arrangement of the different thermal
insulation sections.
Align the bottom storage cylinder.
Place the top storage cylinder with the cylinder feet onto the bridge
of the bottom storage cylinder in such a way, that the fastening holes
are exactly aligned.
6 720 817 906-30.1T
6 720 817 906-31.1T
6 720 817 906-34.1T
6 720 817 906-24.1T
5 Fitting
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
19
Screw each cylinder foot and bridge together using 2 screws,
washers and nuts.
Fig. 35 Joining a double cylinder
[1] Top storage cylinder
[2] Bottom storage cylinder
[3] Connecting screw
[4] Washer
[5] Nut
[6] Foam wedges
[7] Wooden strip
[8] Fixing strap
Fit thermal insulation sections according to their marking.
Fig. 36 Numbering of thermal insulation sections for double and triple
cylinders
Carry out all further installation steps as with the single cylinder.
6 720 817 906-17.1T
6 720 817 906-33.1T
2 x 400...950 l 2 x 1500...3000 l
3 x 400...750 l
1
1
2D
2
1
1
2D
2D
1
2
1
3
2
4
1
3
5
6
6 Commissioning
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
20
6 Commissioning
Initial commissioning must be carried out by a contractor.
6.1 Filling the DHW cylinder and checking for leaks
Before commissioning, check all pipework connections and screw
fittings for leaks.
After the cylinder has heated up and due to the associated pressure
rise, tighten the screws in the manhole cover by hand.
6.2 District heating
Adjust the pump in a cylinder combination to the pump rate
corresponding to the continuous DHW output.
Make this adjustment via an adjusting valve downstream of the
pump.
If the adjustment is made at minimum flow temperature (summer
mode), open the temperature control valve fully (highest set value
setting on the thermostat).
While making the adjustment, open the draw-off positions; the total
discharge volume must not however exceed the maximum DHW
output.
Open the draw-off positions.
Open the DHW shut-off valve [3].
Adjust the discharge volume according to the continuous DHW
output.
Mark the valve spindle position on the adjusting valve [5].
Close the DHW shut-off valve [3].
Heat the domestic hot water temperature in the stratification
cylinder up to 50 °C.
Close the adjusting valve [5] to 50...70 %.
Switch on the pump [6].
Open the DHW shut-off valve [3] to the factory default.
Measure the discharge volume.
Adjust the temperature control valve [4] to its highest set value.
Measure the domestic hot water temperature at the DHW outlet or
draw-off positions.
If the domestic hot water temperature drops (< 50 °C), close the
adjusting valve [5].
If the domestic hot water temperature rises (> 50 °C), open the
adjusting valve [5].
When the outlet temperature is constant, mark the valve spindle of
the adjusting valve [5].
Adjust the set value for the domestic hot water temperature, e.g.
50 °C, at the temperature control valve [4].
Close the draw-off positions.
Fig. 37 DHW cylinder connection diagram
[1] Sensor pocket for return temperature limiter
[2] Sensor pocket for thermometer - domestic hot water
temperature
[3] DHW shut-off valve
[4] Temperature control valve without auxiliary energy
[5] Adjusting valve
[6] Pump
DANGER: Danger to life through electrical shock!
Protect all electrical connections and cables against
contact!
NOTICE: Operate a DHW cylinder with immersion heater
and external current anode only with a 30 mA fault current
switch!
When commissioning, observe the operating instructions
for the floor-standing boiler and DHW cylinder.
In addition to operation with district heating, the LTN/LTH/
LTD cylinders can be heated with immersion heaters and
floor-standing boilers, while the LF cylinders can be heated
via external heat exchangers. Observe the documents for
the relevant heat source.
6 720 817 906-15.1T
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Buderus Logalux LTD550 Installation Instructions For Contractors

Type
Installation Instructions For Contractors

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI