2.3 Mechanical Installation
The EPIV is recommended to be installed on the outlet side of the CRV CW unit, as close to the unit as possible.
Figure 2.8 Installation location of the EPIV
NOTE: According to the connection thread specifications of the EPIV, the connection thread specifications and copper
pipe specifications of the CRV CW units, select the appropriate threaded fittings, adapters, or reducers for
connection. These accessories are not included with the CW units and EPIV kits. These fittings and reducers will be
provided by installer based on the piping and EPIV used on site.
2.4 Standard Valves Adjustment of CRV CW Units
If the EPIV kit is selected and installed in the CRV CW unit, the three-way valve and manual shut-off valve that comes
standard with the CW unit will need to be adjusted.
lCheck and confirm that the manual shut-off valve is fully closed. The manual shut-off valve is closed when the handle
is perpendicular to the piping line. If the manual shut-off valve is open, rotate the handle in clockwise direction to the
closed position. Please see the figure 2.9 for the location of the manual shut-off valve.
lCheck and confirm that the electric three-way valve is fully open. The three-way valve is open when the handle is
parallel to the piping line. If the electric three-way valve is closed, press the button and rotate the handle in
counterclockwise direction to the open position. Please see the figure 2.9 for the location of the electric three-way
valve.
NOTE: Manual operation of the handle of the electric three-way valve must be evenly and slowly, and make sure it
takes more than 10s to switch the whole process, otherwise it will be possible to damage the actuator.
NOTE: Do not supply power to the electric three-way valve after the valve is opened manually, otherwise the valve
may be reset to the closed state.