Installation & Maintenance Manual for FW***Series JB/LCU
Specifications
Types FW*** Series JB Junction Boxes
FWI-* Series LCU Local Control Units
FW2** Series LCU Local Control Units
Hazardous Area
ATEX certificate number SIRA 07ATEX1132X
IECEx certificate number IECEx TSA 07.0005X
Certification coding for ATEX/IECEx
FW*** Series JB/LCU ATEX II 2 G Ex d IIB T6
FW*** Series JB/LCU IEC Ex d IIC T6
Gas temperature class
FW*** Series JB/LCU ATEX T6 @ Ta+40°C
FW*** Series JB/LCU IEC T6 @ Ta+40°C / +55°C / +60°C
Minimum ambient temperature
FW***Series -20°C
IP Rating
FW*** Series IP66
Mechanical
Material Cast Aluminium
Finish Painted/Powder Coated Grey
Cover screw torque 3Nm
Entry threadform Metric/BSP/NPT
Refer to Customer Specific Drawing produced at time of ordering)
Electrical
Maximum voltage – see certification label
Maximum current – see certification label
Maximum Watts Dissipation terminal – see certification label
Conformity IEC 60079-0 EN 60079-0
IEC 60079-1 EN 60079-1
IEC 60529 EN 60529
Installation
To minimise the risk of ignition by electrical apparatus in hazardous areas efficient installation, inspection and maintenance of apparatus and
systems is essential and the work should be carried out by suitably trained personnel in accordance with the prevailing code of practice.
1) The enclosure should be mounted via the through-holes that are provided in the body. The enclosure should be used as a template when
marking fixing points, alternatively, the dimensions of the fixing centres are found on the enclosure drawing. Expanding bolts should be used
when mounting on concrete, or suitably sized bolts, nuts and anti-vibration washers when mounting to a steel framework.
2) This enclosure is suitable for common environments found in Petro-Chemical, On Offshore Oil & Gas Installations.
If any special environmental protection is required then P+F should be contacted to evaluate such conditions.
3) Ensure appropriate Hardware and supports are used for Mounting enclosure weight.
Remove lid/cover by un-screwing 6 x M6 Socket Hd. Cap screws.
Tool requirement– HEX. Allen Key.
4) Install incoming and outgoing cables using appropriately certified cable glands.
Any unused cable entries are to be plugged using suitably certified stopping plugs.
The stopping plugs shall maintain the enclosure IP66 Rating. This can be achieved by applying a liberal amount of suitable grease
such as "Fluid Film® Liquid AR" to the threads when installing the plugs.
5) Connect earthing to internal & external earth facility.
Ensure when using phase conductors over 10mmsq, appropriate sized rail mounted earth terminal is provided.
6) All terminals should be tightened to the torque specified by their manufacturer.
7) No Cables should be left floating and un-terminal.
8) Once the Lid/cover is fitted, ensure that all fasteners are fully tightened.
Secure cover with the body using 6 x M6 Socket HD. Cap screws.
Note- 1. Ensure gaskets (O-rings ) are positioned correctly.
Ensure cover screws are tightened.
9) Refer to Appropriate Selection Installation & Maintenance Standards for,
a) General Requirements. b) Flameproof Enclosure Ex d.