Honeywell Home THX321WFS2001W/U Product information

Type
Product information
ADDENDUM
33-00439-02
T10 Pro Wi-Fi Wiring Diagrams
WIRING DIAGRAMS
Heat only: Gas or Oil Furnace
Cool only
1H/1C: Gas Furnace
W R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
M37552
1COMMON REQUIRED.
G USED FOR INDEPENDENT FAN CONTROL ONLY. MOST HEAT
ONLY, GAS OR OIL FORCED AIR SYSTEMS DO NOT USE A FAN
(G) WIRE.
2
12
FURNACE
R/Rc
SWITCH UP
O/B
HEAT ONLY.
GAS OR OIL FURNACE.
M37553
COOL ONLY.
1COMMON REQUIRED.
AIR-HANDLER
Y R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
1
O/B
R/Rc
SWITCH UP
M37554
1H/1C GAS FURNACE +
AIR-CONDITIONING.
1COMMON REQUIRED.
W R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
RW
Y
G
C
1
1
T10 PRO WI-FI WIRING DIAGRAMS
33-00439—02 2
2H/1C: Gas Furnace
2 Transformer System, 1H/1C: Oil
Furnace
2 Transformer System, Hot Water
Heat with Air-Conditioning (or Hot
Water Coil)
Hot Water Boiler, Heat Only
M37555
2H/1C GAS FURNACE +
AIR-CONDITIONING.
1COMMON REQUIRED.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
1
1
R
W
Y
G
CW2
M37556
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
OIL FURNACE
R/Rc SWITCH
DOWN
O/B
RW
Y
G
CR
1COMMON REQUIRED FROM COOL TRANSFORMER (AIR HANDLER).
1
AIR HANDLER
2 TRANSFORMER SYSTEM
1H/1C OIL FURNACE +
AIR-CONDITIONING.
M37557
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
DOWN
O/B
RW
Y
G
CR
1COMMON REQUIRED FROM COOL TRANSFORMER (AIR-HANDLER).
1
AIR HANDLER
2 TRANSFORMER SYSTEM
HOT WATER HEAT +
AIR-CONDITIONING (OR HOT
WATER COIL).
M37558
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
UP
O/B
R (T)W (T)
HOT WATER BOILER.
HEAT ONLY.
1COMMON REQUIRED.
1
1
C
T10 PRO WI-FI WIRING DIAGRAMS
333-00439—02
Hot Water Heat with Power Open
Zone Valve
2H/2C: Gas Furnace
1H/1C: Heat Pump without Aux
Heat
M37559
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
UP
O/B
R (T)
W (T)
HOT WATER HEAT WITH
POWER OPEN ZONE VALVE.
1COMMON REQUIRED.
C
HONEYWELL V8043
ZONE VALVES
1
TH
TR
TRANSFORMER
R
24 VOLTS
END SWITCH
M37560
2H/2C GAS FURNACE +
AIR-CONDITIONING.
1COMMON REQUIRED.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
1
RW
Y
G
CW2
Y2
M37561
1H/1C HEAT PUMP
WITHOUT AUX HEAT.
1COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINIAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
1
R
O
Y
G
CL
2
3
4
1
21
3
4
T10 PRO WI-FI WIRING DIAGRAMS
33-00439—02 4
2H/1C: Heat Pump with Electric
Aux Heat
2H/2C: Heat Pump without Aux
Heat
M367562
2H/1C HEAT PUMP WITH
ELECTRIC AUX HEAT.
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE
THROUGH ROUTER/INTERNET CONNECTION AND HOME APP OR WIRE
C7089U1006 TO THE TWO “S” TERMINALS.
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM
HEAT. IN THOSE CASES E ISN’T USED. THE TH320WF2006 MODEL CAN BE
CONFIGURED FOR SEPARATE AUX AND E. IF THIS IS DONE, WIRE ONE SET OF
STRIPS TO E TO BE ENERGIZED IN EM HEAT
AND A DIFFERENT SET OF
STRIPS TO AUX TO BE ENERGIZED IN AUX HEAT.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
RAUX
L
G
CO
Y
2
3
4
5
6
7
234
6
7
5
T10 PRO WI-FI WIRING DIAGRAMS
533-00439—02
3H/2C Heat Pump with Electric Aux
Heat
Dual Fuel, 2H/1C: Heat Pump
M37564
3H/2C HEAT PUMP WITH
ELECTRIC AUX HEAT.
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE
THROUGH ROUTER/INTERNET CONNECTION AND HOME APP OR WIRE
C7089U1006 TO THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS! THIS
CAN CAUSE HEAT TO RUN CONTINUOUSLY.
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM
HEAT. IN THOSE CASES E ISN’T USED. THE TH6320WF2006 MODEL CAN BE
CONFIGURED FOR SEPARATE AUX AND E. IF THIS IS DONE, WIRE ONE SET OF
STRIPS TO E TO BE ENERGIZED IN EM HEAT AND A DIFFERENT SET OF STRIPS
TO AUX TO BE ENERGIZED IN AUX HEAT.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
2
3
4
5
6
7
34
7
6
5
R
AUX
L
Y
GO
CY2
2
M37565
DUAL FUEL
2H/1C HEAT PUMP
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
THE HEAT PUMP AND FURNACE HAVE SEPARATE BOARDS. WE SHOW
THEM TOGETHER TO SIMPLIFY THE DIAGRAM. W IS FROM THE
FURNACE BOARD.
BALANCE POINT LOCKOUT CAN BE DONE THROUGH ROUTER/
INTERNET CONNECTION AND HOME APP OR WIRE C7089U1006
TO THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE/
HEAT PUMP
R/Rc
SWITCH UP
O/B
1
RW
L
G
CO
Y
2
3
4
5
6
234
6
5
T10 PRO WI-FI WIRING DIAGRAMS
33-00439—02 6
Dual Fuel, 3H/2C: Heat Pump
M36911A
DUAL FUEL
3H/2C HEAT PUMP
COMPATIBLE T6 MODELS:
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
THE HEAT PUMP AND FURNACE HAVE SEPARATE BOARDS. WE SHOW
THEM TOGETHER TO SIMPLIFY THE DIAGRAM. W IS FROM THE
FURNACE BOARD.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE
DONE THROUGH ROUTER/INTERNET CONNECTION AND HOME APP OR
WIRE C7089U1006 TO THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE/
HEAT PUMP
R/Rc
SWITCH UP
O/B
1
2
3
4
5
6
34
6
5
R
W
L
Y
GO
CY2
2
T10 PRO WI-FI WIRING DIAGRAMS
733-00439—02
Whole house humidifier, dehumidifier, or ventilator
Using U Slider Tab
WIRED TO HUMIDIFIER, DEHUMIDIFIER OR
VENTILATOR WITH BUILT-IN TRANSFORMER
WIRED TO FRESH AIR DAMPER POWERED BY
FURNACE TRANSFORMER
WIRED TO HUMIDIFIER, VENTILATOR, OR DAMPER
POWERED BY EXTERNAL TRANSFORMER
WIRED TO LOW SPEED FAN TERMINAL ON HVAC FOR
DEHUMIDIFICATION
HUMIDIFIER,
DEHUMIDIFIER,
OR VENTILATOR
M37567
M36777
C from furnace or air-handler
Damper
M37568
HUMIDIFIER,
DEHUMIDIFIER,
OR VENTILATOR
R FROM 24 VOLT
TRANSFORMER
C (COMMON) FROM
24 VOLT TRANSFORMER
DEHUMIDIFIER*
FURNACE OR AIR-HANDLER
* LABEL FOR THIS TERMINAL VARIES BY EQUIPMENT M37566
T10 PRO WI-FI WIRING DIAGRAMS
©2019 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International Inc.
www.resideo.com
Resideo Inc., 1985 Douglas Drive North,
Golden Valley, MN 55422
33-00439—02 M.S. Rev. 02-19 | Printed in United States