14077287.01 09/2017 EN/DE
WIKA operating instructions model CS4R 17
EN
5. Commissioning, operation / 6. “Transmitter” functionality
5.3 Operation
After mounting the controller on the DIN rail and performing wiring, put the controller into
operation as follows:
■
Switch on the power supply for the controller.
Once the power supply has been switched on, the input configuration is displayed on the
actual value display (PV display) for about 3 seconds and, on the set point display, the
assigned end value can be seen.
During this time, all outputs and control displays are switched off.
Subsequently, the actual value display will show the current measured value, the set
point display will show the selected set point (SV1 or SV2) and it will start to control.
■
Input of the setting parameters
To enter one or more setting parameters, follow the procedure in accordance with
chapter 8 “Configuration”.
■
Switch on the load circuit
The control loop is now in operation and the control system will try to maintain the
selected set point.
6. “Transmitter” functionality
The “transmitter” functionality is only possible for controllers with the monitoring output
analogue current signal 4 … 20 mA. The transmitter function of CS4R converts each
input signal (thermocouples, resistance thermometers, current and voltage signals) into a
4 ... 20 mA signal and outputs it via the monitoring output.
WARNING!
■
When using the controller as a transmitter, there is a delay time of
approx. 1 s between the input and output signals.
■
When switching from the “transmitter” functionality to the “controller”
functionality, the settings from the transmitter mode are applied. After
switching to the controller mode, always check the settings required for
controlling and adjust them where necessary.
When operating the CS4R as a transmitter, proceed as follows:
1. Connect the controller (power supply, input and output).
2. Switch on the power supply for the controller.
3. Call the auxiliary parameter level 2 by pressing
- and MODE button
(for approx. 3 seconds).
4. Select the connected sensor in the menu item “Sensor selection (En)”.
5. Set the end value of the measuring range (measured value at which 20 mA are output) in
the menu item “Lettering end value (FLH)”.