Lumin LSP Installation Overview

Type
Installation Overview
Surface-mounted installation Flush-mounted installation
Surface-mounted installation Flush-mounted installation
PART ONE: MOUNTING THE LUMIN SMART PANEL (LSP) TO THE WALL
REMOVE ELECTRICAL PANEL COVER INSERT LSP WIRES INTO ELECTRICAL PANEL
1 3
Turn o the main electrical feed and remove the cover of
the existing electrical panel.
Guide the LSP’s wire whips through the two 2” holes in the
electrical panel.
Knock out two 2” holes in the bottom of the electrical panel
to accommodate the LSP’s 2” conduit. Remove drywall
(ush-mounted installations only) for access if needed.
Secure the LSP to the wall and electrical panel utilizing the
LSP’s mounting hardware and conduit bushings.
KNOCK OUT 2” HOLES IN ELECTRICAL PANEL SECURE LSP TO WALL & ELECTRICAL PANEL
2 4
LUMIN SMART PANEL INSTALLATION OVERVIEW V2.0
WARNING: HIGH VOLTAGE. THE LUMIN SMART PANEL MUST BE INSTALLED BY A LICENSED ELECTRICIAN
LUMINSMART.COM
QUESTIONS? Please refer to Lumin’s Installation Manual or contact Lumin
Support at 1-888-421-0616 or [email protected]
Line #A
PART TWO: WIRING THE LUMIN SMART PANEL (LSP) TO THE ELECTRICAL PANEL
LUMIN SMART PANEL INSTALLATION OVERVIEW V2.0
CONNECT TWO LSP GROUND WIRES
CONNECT LSP POWER CABLE HARNESS
CONNECT LSP WIRE “LINE #B” TO LOAD
CONNECT CURRENT TRANSFORMERS (CTs)
CONNECT LSP WIRE “LINE #A” TO BREAKER REPLACE ELECTRICAL PANEL COVER
Surface-mounted installation Flush-mounted installation
Disconnect Load
Turn O Circuit
Neutral
(white)
Line B
(red)
Line A
(black)
200A CTs on main service lines 50A CTs on PV generation output
WARNING: HIGH VOLTAGE. THE LUMIN SMART PANEL MUST BE INSTALLED BY A LICENSED ELECTRICIAN
Ground x 2
Connect the LSP’s two ground wires to the existing ground
bar in the electrical panel.
Connect LSP wire “Neutral” to the neutral bar; connect LSP
wires “Line A” and “Line B” to phase A and phase B breakers
via a double-tap (or a three-way wire nut or a new breaker).
Turn o circuit breaker and disconnect the existing load.
Connect LSP wire “Line #A” to the circuit breaker.
Connect LSP wire “Line #B” to the load with a wire nut.
Record circuit name and LSP line number in the table
provided. Repeat Steps 3-4 until all LSP lines are connected.
Connect CTs “Line A/B CT” (200A) to their corresponding LSP
connector and attach to main service lines; connect CTs
“Aux A/B CT” (50A) to their corresponding LSP connector
and attach to PV generation output lines (if applicable).
Turn all circuit breakers and the main electrical feed back
on and replace the electrical panel cover.
1
2
3
4
5
6
Line #B
Line A/B
CT
Line A/B
CT
Aux A/B
CT
Aux A/B
CT
LUMINSMART.COM