Installation
10
Fuel/Gas System
All gas service must comply with local codes; if local codes do not apply, install the fuel gas service in accordance with the
National Fuel Gas Code ANSI 7233.1-1988
In Canada install the fryer in accordance with CAN1-B149.1 and CAN1-B149.2 and/or local codes
Contact the local gas company to determine the correct size for the gas supply line; the fryer will not operate properly if
the gas line is too small
When making the gas supply connections, use a pipe joint compound resistant to liquified petroleum gases
Be certain that all gas-supply piping to the fryer allows for the proper minimum clearance at the side, rear and floor level—refer
to the data plate inside the front door
Level the fryer in accordance with the instructions provided in this manual
Field-attached piping assemblies must not interfere with filter module travel or, if equippped with casters, the caster-swivel
radius
gNOTE: ALWAYS provide gas-supply connection lines that have been sized to be equivalent to the supply connection on the
fryer
g NOTE: NEVER use adaptors to make a smaller line fit, as an inadequate line size may not allow sufficient gas
volume for proper burner operation, resulting in poor fryer performance
Low gas volume/pressure can also cause "lazy" flames, which do not travel through the tank properly; this can cause high
temperatures on tank areas and create carbon monoxide
The fryer is equipped to work with one specific type of fuel gas—this information is given on the data plate inside the fryer door
gNOTE: NEVER supply the fryer with any kind of fuel other than the type indicated
Flexible hose quick-disconnect installation shall be made with a connector which complies with the "Standard for Connectors
for Moveable Gas Appliances", ANSI Z21.69-1987, and a quick-disconnect device which complies with the "Standard for
Quick-Disconnect Devices for Use with Gas Fuel", ANSI Z21.41-1978 and Addenda Z21.41a-1981 and Z21.41b-1983
The restraining device must be shorter than the gas connector, to prevent strain on the gas connector
A fryer restraining loop must be provided to limit the movement of the fryer without depending on the connector and the
quick-disconnect device, or its associated piping-to limit the fryer's movement
It is recommended that the attachment for the fryer restraining loop be installed in the rear center of the fryer cabinet (between
the two tanks) at approximately 30" above floor level
Use caution when drilling and installing attachment
Do not locate in such a manner that the mounting screws will perforate either of the fryer flues.
Fire Detection/Extinction System
gNOTE: We STRONGLY ADVISE you to install an approved fire detection and extinguishing system.
Exhaust temperatures from the fryer may run as high as 1200°F; therefore, select a fire-extinguishing system and a
sensing device that activates your system with this in mind, in order to reduce the possibility of false alarm.