  • Hello! I am an AI chatbot trained to assist you with the ProMinent DULCOMARIN DXMaR Series Assembly And Operating Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DULCOMARIN
®
, R Module
Control unit for chlorine gas metering device,
DXMaR
Assembly and operating instructions
A0448
These operating instructions are only valid in conjunction with the "Operating instructions for the DULCOMARIN
®
”.
EN
986539 Version: BA DC 090 03/19 EN
Please carefully read these operating instructions before use. · Do not discard.
The operator shall be liable for any damage caused by installation or operating errors.
The latest version of the operating instructions are available on our homepage.
Table of contents
1 Identity code.......................................................................... 3
2 Safety and responsibility....................................................... 4
3 Handling the device.............................................................. 5
4 Wiring diagram...................................................................... 6
Table of contents
2
1 Identity code
The identity code describes the external modules
for the DULCOMARIN
®
.
DXMa
External modules for the DULCOMARIN
®
Module:
M M module, measuring module: pH, ORP, temperature
A A module, control module: 3 pumps and 4 analogue outputs
R
R module, control module: Chlorine gas metering device with feedback
1) 2)
N
N module, power supply module without relay
1) 2)
P
P module, power supply module without relay, only mounting type
‘0’
2)
I I module, current input module, 3 mA inputs, 2 digital inputs
Mounting type:
0 Without housing, only P-module (IP 00)
W Wall mounted (IP 65)
H Mounting rail (IP 20)
E Upgrade module (insert module for DXCa, IP 20)
Design:
0 With controls
2 Without controls
3 Without controls (only mounting type
‘E’
)
Application:
0 Standard
S Swimming pool (only M module)
Language:
00
No controls
2)
EN German
EN English
ES Spanish
FR French
IT Italian
Certification:
00 No certification, only P module without housing
01 CE certification
1)
only mounting type W wall mounting /
2)
only in version
‘2’
without operation
Identity code
3
2 Safety and responsibility
NOTICE!
Further applicable documents
These operating instructions are only valid in con‐
junction with the "Operating instructions for DUL‐
COMARIN
®
”.
All the safety information and explanations con‐
tained therein must be observed without exception.
NOTICE!
Intended use
You many only use the DXMaR R module to
control a servomotor.
You many only use the DXMaR R module as
part of a DULCOMARIN
®
.
Any other uses or modifications are prohibited.
WARNING!
Danger of malfunctions
Only trained personnel may install the DXMaR R
module. Only then can it be ensured that all com‐
ponents of the control circuit are matched to each
other and operating correctly.
Safety and responsibility
4
3 Handling the device
CAUTION!
Protect the module against moisture and the
effects of chemicals, even while still packaged.
Store and transport the module it its original packaging.
Ambient conditions for storage and transport:
n Temperature: -10 °C ... 70 °C.
n Max. permissible relative humidity: 95%, non-condensing (DIN
IEC 60068-2-30).
WARNING!
Danger of malfunctions
Only trained personnel may install the DXMaR R
module. Only then can it be ensured that all com‐
ponents of the control circuit are matched to each
other and operating correctly.
The wiring diagram can be found at the end of these operating
instructions, see
Ä Chapter 4 ‘Wiring diagram’ on page 6
.
Create the CAN connection in accordance with the operating
instructions for the DULCOMARIN
®
.
Storage and transport
Assembly and installation
Wiring diagram
Handling the device
5
4 Wiring diagram
WARNING!
Danger to life due to chlorine gas
Chlorine gas can escape if a chlorine gas metering
device is accidentally set to
‘OPEN’
.
Possible consequence: Fatal or very serious inju‐
ries.
Measure: Lock the power supply to the chlorine
gas metering device in the event of a failure of the
chlorine gas metering device, doing the same with
the power supply to the booster pump and the cir‐
culating pump to shut the booster pump and the
circulating pump down or take appropriate meas‐
ures to prevent the uncontrolled escape of chlorine
gas.
Leistungsrelais-Ausgänge
Stellungsrückmelde-Eingang
Intern
Extern
Speisespannung
schließen
öffnen
offen
geschlossen
A0449
Fig. 1: Wiring diagram
Wiring diagram
6
Tab. 1: Terminal assignment
Name Terminal identifier Terminal no. Pole Function
Output relay output
1
P1 1 C Shut the servomotor.
2 NO
3 NC
Output relay output
2
P2 4 C Open the servomotor.
5 NO
6 NC
Response signal
input
XR 7 - Feedback servomotor
position.
8 S
9 +
Output relay output (P1, P2):
n Type of contact: Changeover contact with interference-sup‐
pressed varistors
n Load capacity: 250 V AC, 3 A max., 700 VA
n Contact lifespan: > 20 x 10
5
switching operations
Position feedback input: XR
n Galvanically isolated from the power relay contacts
n Insulation voltage: 500 V
n Potentiometer to be connected: 0 Ω ... 1 kΩ
n Accuracy (without potentiometer errors): 1% of input range
n Dissolution: 0.5 % of input range
n Manipulating time: min.: 25 s / max.: 180 s
Electrical data
Wiring diagram
7
986539, 2, en_GB