ICM Controls ICM220B Installation guide

  • Hello! I am an AI chatbot trained to assist you with the ICM Controls ICM220B Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ICM
220
LOCKOUT RELAY
SPECIFICATIONS
Input
•Voltage: 18-30 VAC
•Frequency: 50-60 Hz
Output
• Relay: SPDT
• RelayContacts: 2 amps maximum
@ 30 VAC resistive
• PowerConsumption:
2 watts maximum during lockout
MODE OF OPERATION
Upon application of power with the safety
switches closed, the load will energize. If any of
the safety switches open for longer than
600 ms, the fault light will come on and the load
will stay de-energized regardless of the state
of the safety switches. Power must then be
removed for 100 ms and safety switches must
be closed in order to reenergize the load, upon
which the fault light will be off.
INSTALLATION
1. Disconnect power.
2. Connect terminals as shown in the wiring diagram below.
3. Reapply power, check operation.
•Helpstoeliminatenuisancelockouts
•Replacesimpedancerelays83and93
WIRING DIAGRAM
24 VAC RC
3 1
2
4
Safety Switches
Load
Contactor
Fault
Light
Low cost lockout relay helps
eliminate nuisance lockouts
due to impedance relay failure