Network Room Modules
Network Room Modules
Installation Guide
Part No. 24-85638-1214, Rev. E
Issue Date June 14, 2010
I
Figure 1: Dimensions, mm (in.)
80 (3.15)
120
(4.72)
25 (0.98)
(6)
Display
in Celsius and
Fahrenheit units
80 (3.15)
35
(1.38)
(1)
LCD Display
with back-light
(2)
Dial for Temperature
Setpoint Adjustment
(3)
°C / °F Button
(4)
Fan Button for fan speed adjustment
(5)
Service tool socket
II
Figure 2: Removing the Cover from the Base
III
Figure 3: Wall Mounting Base Dimensions, mm (in.)
31 (1.22)
60 (2.36)
2 x Ø 4.2 (0.16)
66 (2.60)66 (2.60)
60 (2.36)
4,3 (0.17)
4,3 (0.17) 4,3 (0.17)
29 (1.14)
33
(1.30)
33
(1.30)
38
(1.50)
5.7 (0.22)
5.7 (0.22)
34 (1.34)
34 (1.34)
67 (2.64)
67 (2.64)
IV
Figure 4: Dual-Switch DIP Switch Block
Figure 5: Terminal Block Connection
V
Figure 6: Service Port (4-pin) for LP-NRM0xx-000C Series
Figure 7: Port (6-pin Modular Jack) for LP-NRM5xx-000C and
LP-NRM6xx-000C Series
1Network Room Modules Installation Guide
Network Room Modules
Installation Guide
READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS
CAREFULLY BEFORE INSTALLING, AND SAVE IT FOR FUTURE USE
General Features
Network Room Modules (NRMs) are designed for use with
Johnson Controls® Facility Explorer FX06, FX07, FX14, and FXVMA
Field Controllers.
The Liquid Crystal Display (LCD), along with a dial and push button(s) on
the front of the NRM, allow the occupant to view and adjust the setpoint
temperature in the controller, and to manually override the speed of the
fan in the controlled equipment.
The NRM connects to the Local Link Display Bus of the FX field
controller. Configure the NRM with the FX Builder programming tool,
which is part of the FX Tools Pro Software package.
The LP-NRM0xx-000C Series NRM requires a 15 to 24 VAC/VDC power
supply from the FX Controller or from an external power source, and has
a 4-pin service port (Figure 6).
The LP-NRM5xx-000C and LP-NRM6xx-000C Series NRMs require a
15 VDC power supply from the FX Controller or from an external power
source, and have a 6-pin Modular Jack service port (Figure 6).
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a
Class A digital device pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when this equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in
which case the user will be required to correct the interference at his/her
own expense.
Part No. 24-85638-1214, Rev. E
Issue Date June 14, 2010
2 Network Room Modules Installation Guide
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian
Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du
Règlement sur le matériel brouilleur du Canada.
Tools
Flat-head screwdrivers, 3 mm and 5 mm (1/8 to 5/32 in.)
Drill, bits, and appropriate 4 mm (3/16 in.) screws and plugs
Pointed tool (available from Johnson Controls, Ordering Code TM-9100-8900
in Europe, or T-4000-119 in North America)
Figure 1: Dimensions, mm (in.)
(1) LCD Display with backlight
(2) Dial for temperature set point adjustment
(3) °C/°F Button
(feature available in specific models, see Ordering Codes)
(4) Fan button for fan speed adjustment
(feature available in specific models, see Ordering Codes)
(5) Service port
(6) Display in Celsius and Fahrenheit units
Mounting
The NRM mounts directly on a wall surface in the room you want to control.
Choose a location for the NRM while considering the following information:
Place the room module where the occupant can easily read the LCD and
use the controls.
Place the module where the ambient temperature is representative of the
general room conditions if you want to use the built-in temperature
sensor to measure space temperature. For example, there should be a
sufficient amount of air circulation.
Avoid cold or warm air drafts, radiant heat, and direct sunlight.
Place some insulating material in the wiring access hole or conduit to
prevent the introduction of air from outside the room.
3Network Room Modules Installation Guide
Figure 2: Removing the Cover from the Base
1. Remove the retaining screw (if inserted) from the top of the module
enclosure.
2. Remove the module cover from the base by inserting a pointed tool into
the narrow slot at the center top of the cover. While pressing down
gently, pry the base away from the cover. As the two parts separate,
remove the tool and continue to pull the cover away from the base until
the cover is free.
Figure 3: Wall Mounting Base Dimensions, mm (in.)
1. Hold the module base on the wall to cover the electrical outlet and mark
the position of at least two holes. Drill the holes and insert the plastic
plugs (wall anchors) into the holes.
2. Mount the module base on the wall and secure with at least two screws.
For other mounting options, see Ordering Codes and refer to the
corresponding installation sheets.
Addressing
Figure 4: Dual-Switch DIP Switch Block
NRM models which are not addressable have a fixed physical address of
191. For those models which are addressable, the NRM's address must be
set using its dual-switch DIP switch block, located on the printed wiring
board. See Table 1 for details on addressing the NRM.
Note: You must cycle power to the NRM (disconnect/reconnect the NRM
or cycle power to the field controller) for the address change to take
effect.
Table 1: NRM Addressing
DIP Switch
Address
Switch 2 Switch 1
191 OFF OFF
192 OFF ON
193 ON OFF
194 ON ON
4 Network Room Modules Installation Guide
Wiring
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
IMPORTANT: The Complementary Metal Oxide Semiconductor
(CMOS) circuits in the controller are sensitive to static electricity.
Take suitable precautions.
IMPORTANT: The LP-NRM0xx-000C Series NRM accepts VAC or
VDC power. The LP-NRM5xx-000C and LP-NRM6xx-000C Series
accept VDC power only.
IMPORTANT: Use this NRM Room Command Module only as an
operating control. Where failure or malfunction of the NRM could
lead to personal injury or property damage to the controlled
equipment or other property, additional precautions must be
designed into the control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against failure or
malfunction of the NRM.
IMPORTANT: The installation of electrical wiring must conform to
local codes and should be carried out by authorized personnel only.
Users should ensure that all Johnson Controls products are used
safely and without risk to health or property.
5Network Room Modules Installation Guide
Figure 5: Terminal Block Connection
Terminations are made on the terminal block in the base of the module,
which is accessible after removing the cover from the base.
The screw terminals accept up to 1.5 mm
2
(16 AWG) wires.
Keep low-voltage wiring separated from power line voltage wiring.
Do not run wiring close to transformers or high frequency generating
equipment.
Complete and verify all wiring connections before applying power to the
module.
Use screw terminals RT+, RT-, and COM to connect to the FX controller
display (local ink) bus terminals (LL+, LL-, and COM, respectively).
Note: RT+ and RT- are polarity sensitive and are not interchangeable.
If shielded cable is used, connect the shield to a clean earth ground at
one end only.
Connect the power supply voltage to the terminals as marked:
- 15-24 VAC/VDC and COM (common) for the LP-NRM0xx-000C
Series NRM
- 15 VDC and COM (common) for the LP-NRM5xx-000C and
LP-NRM6xx-000C Series NRMs
Service Port
The service port is located on the lower edge of the module. There are two
different types of service ports, depending on the NRM Series you are
using:
4-Pin Service Port
See Figure 6 for service port wiring for LP-NRM0xx-000C Series NRM.
Use the 4-pin service port to download applications into the connected FX
Controller using the Programming Key (pass-through feature). The NRM
supplies power to the Programming Key.
6-Pin Modular Jack Service Port
See Figure 7 for service port wiring for LP-NRM5xx-000C and
LP-NRM6xx-000C Series NRMs.
Use the 6-pin Modular Jack service port to connect a Medium User
Interface (MUI) for monitoring and adjusting parameters in the control
application of the connected FX controller. The NRM supplies power to the
MUI from the FX controller through the 6-pin Modular Jack service port.
6 Network Room Modules Installation Guide
Ordering Codes
Table 2: Network Room Modules (Available in Europe)
Table 3: Network Room Modules (Available in North America)
Product Code Features/Options
Size (mm)
Service Port Type
LCD Display
Temperature
Adjust Dial
Fan Speed
Selector Button
°F/°C
Addressable
LP-NRM001-000C 80 x 80 Program
Key
No No No No No
LP-NRM002-000C Yes Yes No No No
LP-NRM003-000C Yes Yes Yes No No
LP-NRM511-000C MUINoNoNoNoYes
LP-NRM502-000C Yes Yes No No No
LP-NRM503-000C Yes Yes Yes No No
Product Code Features/Options
Size, mm (inch)
Service Port Type
LCD Display
Temperature
Adjust Dial
Fan Speed
Selector Button
°F/°C
Addressable
LP-NRM511-000C 80 x 80
mm
(3.15 x
3.15 in.)
MUINoNoNoNoYes
LP-NRM552-000C Yes Yes No Yes No
LP-NRM553-000C Yes Yes Yes Yes No
LP-NRM611-000C 120 x 80
mm
(4.72 x
3.15 in.)
MUINoNoNoNoYes
LP-NRM652-000C Yes Yes No Yes No
LP-NRM653-000C Yes Yes Yes Yes No
7Network Room Modules Installation Guide
Table 4: NRM Mounting Kits and Accessories
Table 5: Recommended FX Controller and MUI/NRM
Configuration Limits
1. One addressable NRM is required.
Ordering Codes Description
TM-1100-8931 Plastic Base for Surface Mounting - White
TM-9100-8941-W Recessed Wall Box Mounting Kit - White
TM-9100-8951-W Panel Mounting Kit - White
NS-WALLPLATE-0 Wall plate kit used to mount an 80 x 80 mm (3.15 x 3.15 in.)
NRM onto a 2 x 4 in. wall box.
TM-9100-8900 Special Tool (to open module) - Europe
T-4000-119 Special Tool (to open module) - North America
LP-KIT100-000C Programming Key
FX Controller Type MUI/NRM Configuration Limits
FX06 One MUI and one NRM
FX06 Rev A One MUI and one NRM
FX07 One MUI and one NRM
FX07 Rev A One MUI and one NRM
FX14 One MUI and two NRMs
1
FX14 Rev A One MUI and two NRMs
1
FX14 Rev B One MUI and two NRMs
1
FX15 Universal NRM is not supported
FX15 NRM is not supported
FX15 Rev A NRM is not supported
FX16 NRM is not supported
FX16 Rev A NRM is not supported
FX16 Rev B NRM is not supported
FXVMA One MUI and one NRM
FXVMA Rev A One MUI and one NRM
8 Network Room Modules Installation Guide
Technical Specifications
NRM Technical Specifications (Part 1 of 2)
Product Network Room Module
Power Requirements
LP-NRM0xx-000C
Series
14.3 to 27.6 VDC at 500 mW maximum or
24 VAC ±15%, 50/60 Hz,
at 1 VA maximum
Class 2 or Safety Extra-Low Voltage (SELV)
Power Requirements
LP-NRM5xx-000C and
LP-NRM6xx-000C
Series
9.8 to 16.5 VDC (15 VDC nominal)
at 35 mA maximum
Class 2 or SELV
Ambient Operating
Conditions
0 to 50°C (32 to 122°F)
10 to 90% RH noncondensing
(and max. 30°C [86°F] dew point)
Ambient Storage
Conditions
-20 to 70°C (0 to 160°F)
5 to 95% RH noncondensing
(and max. 30°C [86°F] dew point)
Terminations Terminal block with screw terminals in base for
1.5 mm
2
/ 16 AWG (max.) wires.
Recommended tightening torque 0.5 Nm.
Temperature Sensor RTD Platinum element, PTC, 1k ohm at 0°C (32°F),
Pt1000 Class A, DIN EN 60751
Suitable for residential and commercial office
environments only.
Display and Controls LCD display with three digits and seven symbols.
Dial and push button(s).
Communications
Interface
N2 Open Protocol communication
Service bus RS485 at 9600
baud
Service Port Model LP-NRM0xx:
4-pin service port for FX Programming Key with
9 VDC power
Models LP-NRM5xx and LP-NRM6xx:
6-pin Modular Jack service port for MUI with
15 VDC power
Mounting Direct surface mount.
Plastic base for surface mount with wiring conduits.
Recessed wall box and panel mounting kits
available on request (see
Ordering Codes).
Dimensions
(H x W x D)
80 x 80 x 35 mm (3.15 x 3.15 x 1.4 in.)
120 x 80 x 35 mm (4.72 x 3.15 x 1.4 in.)
9Network Room Modules Installation Guide
Housing Material ABS + polycarbonate, self-extinguishing UL94-HB
Housing Protection IP30 (EN60529)
Shipping Weight 0.2 kg (7 oz), 80 x 80 mm (3.15 x 3.15 in.) housing
or 0.25 kg (9 oz), 120 x 80 mm (4.72 x 3.15 in.)
housing
Compatible FX
Controllers and
Firmware Versions
FX06, V 2.32 and higher
FX07, V 3.01 and higher
FX14, V 2.32 and higher
FXVMA, all versions
Compliance Europe
CE Mark – Johnson Controls, Inc., declares that the
Network Room Modules (NRMs) are in compliance
with the essential requirements and other relevant
provisions of the EMC Directive 2004/108/EC.
Canada
UL Listed (PAZX7), C22.2 No. 205,
Signal Equipment Industry Canada, ICES-003
United States
UL Listed (PAZX), UL 916, Energy Management
Equipment
FCC compliant to CFR 47, Part 15, Subpart B,
Class A
Agency Listings UL916 and CUL Listed
This document is subject to change without notice.
NRM Technical Specifications (Part 2 of 2)
10 Network Room Modules Installation Guide
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls® is a registered trademark of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI