7620100 / 7621100 / 7622100 / 7623100
980035700 Rev.001
• Magnetic Latch (ML) - draws very low current in the ON or OFF states, and draws moderate current for very
short time when changing state
•StartIsolation(SI)—canbeconguredfortemporaryisolationofHouseloadsfromEnginecircuitduring
enginecrankingtoprotectsensitiveelectronics
•EngineIsolation(EI)—canbeconguredforisolationoftwoengineswhilebotharerunningtoprotect
engineelectronicsandmaximizealternatoroutput
• Senses charging on two battery banks
•LEDoutputtoremotelyindicatewhenbatteriesarecombinedorisolated
•Tin-platedcopperstudsformaximumconductivityandcorrosionresistance
•Labelrecessesforcircuitidentication
•Silveralloycontactsprovidehighreliabilityforswitchingliveloads
• Includes a Remote Control Contura Switch (2146)
• IncludesaDeutschDTMconnector(matingpartnotincludedbutrequired)
Specications 12VDC 24VDC
Wire Size and Current Ratings See table below See table below
ML-Coil Function Bi-stable Bi-stable
AmperageOperatingCurrent continuous <13mA@25°Cnominalvoltage <13mA@25°Cnominalvoltage
changingstage(20ms) <7A@25°Cnominalvoltage <4A@25°Cnominalvoltage
OperatingVoltage(contacts) 9-16VDC 18-32VDC
ControlVoltage 9-16VDC 18-32VDC
RelayContactPosition:
-Combine(30sec.) 13.5V 27.0V
-Combine(90sec.) 13.0V 26.0V
-OpenLow(10sec.) 12.35V 24.7V
-OpenLow(30sec.) 12.75V 25.5V
-OpenHigh 16.2V 32.4V
LiveCurrentSwitching 300A@12VDC-10,000Cycles 150A@24VDC-10,000Cycles
Terminal Stud Size 3/8"-16 3/8"-16
MaximumTerminalStudTorque 140in-lb(15.8N•m) 140in-lb(15.8N•m)
Ring Terminal Size 3/8" (M10) 3/8" (M10)
TerminalRingDiameterClearance 1.18" (30 mm) 1.18" (30 mm)
ControlCircuitCurrentDraw <40mA <40mA
RemoteControlConturaSwitch
Action SPDT,ON-OFF-ON
Seals Internal&ExternalGasketPanelSeal
MountingHole 0.83”x 1.45” (21.08 mm x 36.83 mm)
LEDRating 100,000hourshalf-life
HarnessConnector DeutschDTMSeriesDTM06-6S
MatingPartRequirements seeLADDIndustriesatwww.laddinc.com
RequiredReceptacleShell DTM-04-6P
*
Wedgelock WM-6P
Terminal Pins 1060-20-0122
†
Sealing Plugs 0413-204-2005
†
HandCrimpTooling DTT-20-0
‡
RegulatoryMeets ISO 8846 and SAE J1171 external ignition protection requirements, CE marked, Rated IP66
* Special modifications are available depending on customer requirements. No polarization on standard product.
† Quantity depends on optional wire connections. The total number of pins and sealing plugs is 6.
‡ Required for hand assembly of wires and terminal pins.
MarineElectricalProd
ucts
PN Termination
Manual
Control
Control
Circuit
7620100 DeutschConnector No 12VDC
7621100 DeutschConnector No 24VDC
PN Termination
Manual
Control
Control
Circuit
7622100 DeutschConnector Yes 12VDC
7623100 DeutschConnector Yes 24VDC
ML– ACR
Automatic Charging Relays
Guarantee
BlueSeaSystemsstandsbehinditsproductsforaslongasyouownthem.
Find detailed information at www.bluesea.com/about. For customer service, call 800.222.7617.
OverviewofApplication
The ML-Series ACR automatically combines batteries during charging, and isolates batteries when there is no
charging sensed on either battery bank.
ML-Series ACR Function 12 Volt DC Operation 24 Volt DC Operation
Automatically combines battery
banks when sensed voltage
levels are:
Above 13.5V for 30 sec.
Above 13.0V for 90 sec.
Above 27.0V for 30 sec.
Above 26.0V for 90 sec.
Automatically isolates battery
banks when sensed voltage
levels are:
Below 9.6V (undervoltage lockout)
Below 12.35V for 10 sec.
Below 12.75V for 30 sec.
Above 16.2V (overvoltage lockout)
Below 19.2V (undervoltage lockout)
Below 24.7V for 10 sec.
Below 25.5V for 30 sec.
Above 32.4V (overvoltage lockout)
StartIsolationorEngineIsolation.Theisolationinputsenableoneoftwofunctionsdependingon
howtheinputsarecongured.
NOTE: The ML-Series ACR can be congured for Start Isolation or Engine Isolation, but not both.
• StartIsolation-Temporaryisolation(3−5 minutes) of house loads from the engine circuit during engine
crankingtoprotectsensitiveelectronics.CongureStartIsolationwhenthereareheavycrankingloads
causingsagsandspikesthatmightdamageelectronicsintheHousecircuit.Seepage3.
• EngineIsolation-Isolatetwoengineswhilebotharerunningtoprotectengineelectronics,andto
maximizealternatoroutput.CongureEngineIsolationwhentheenginemanufacturerrequiresit,and
whenthereareseparatebatteriesforeachengine.Seepage3.
UndervoltageorOvervoltageLockout.
• Undervoltagelockoutpreventsbatteriesfrombeingcombinedwheneitherbatteryisbelow9.6V@12VDC
operationor19.2V@24VDCoperation.
• Overvoltagelockoutpreventsbatteriesfrombeingcombinedwheneitherbatteryisabove16.2V@12VDC
operationor32.4V@24VDCoperation.
ControlSwitchRemoteOperation. OptionalConturaControlSwitch—sustained(SPDT)ON-OFF-ON.
TheControlSwitchshouldbemountedinaconvenientlocationnearhelmcontrolstoallowforquickaccess.
NOTE: Alternatively use a momentary (SPDT) (ON)-OFF-(ON) or momentary push button switch to provide cross connect and/or battery isolation.
To cross connect
(combine) battery banks
Switchto“ON”combinesbatterybankstoprovidemorebatterypowerinhard
starting situations.
To isolate battery banks
Switch to “OFF”- when the battery banks are isolated using the Control
Switch, the battery banks remain isolated, and for at least 30 seconds after
thecontrolswitchisreturnedtothe“AUTO”position.
ControlSwitchRemoteIndicationorML-ACRStatus
NOTE: The remote switch has two LEDs (top and bottom). These LEDs operate simultaneously-either they are both ON or both OFF.
page1of4
LEDINDICATION ACRSTATEORCONDITION
RemoteSwitchSetto“AUTO”ornoRemoteSwitchInstalled
LEDsOFF Batteries are isolated
LEDsON Batteries are combined
LEDsslowsteadyblink,ON-OFF StartorEngineIsolationiscausingbatteriestobeisolated
LEDsquicksteadyblink,ON-OFF
Undervoltage lockout--either battery is below 9.6V@12V DC
operation or 19.2V@24V DC operation.
Overvoltage lockout--either battery is above 16.2V@12V DC
operation or 32.4V@24V DC operation.
RemoteSwitchSettoOVERRIDE“ON”or“OFF”—Automaticoperationissuspendedfor10minutes
afterremoteswitchisreturnedto“AUTO”
LEDsdoubleblink,
Blink-Blink-Pause,Repeat
Manual override--check ACR for switch states OR
ACR mechanical failure
WireSizeandCurrentRatings
Wire Size
Cranking
30 sec.
Intermittent
5 min.
Continuous
(UL 1107)
2/0AWG(70mm²) 1,000A 400A 225A
4/0AWG(120mm²) 1,100A 400A 300A
2×4/0AWG(2x120mm²) 1,450A 700A 500A