9
WIRE FUNCTIONS
SECTION 3. WIRE FUNCTIONS
1. Outdoor Sensor (2-Light Green Wires) are connected to the main controller on the Munchkin.
Route wires from the Munchkin control to the external junction box, to your outdoor sensor, which will
allow the user to change the temperature going to the Central Heating loop automatically. Place the
outdoor sensor preferably to the north or northwest or to the side which will be affected by changing
weather conditions outside. NOTE: Do not locate the sensor in the direct sunlight.
Outdoor Sensor Function: The user can program the desired supply temperature based on
the heat transmitter (Baseboard, Radiant Floor, Air Handler) that will be used in the installation.
Once the outdoor sensor (Light Green Wires) is connected to the heater, the water temperature
of the heater will adjust to run the heater more efficiently and provide greater comfort to the liv-
ing space. See section 4: “P
rogramming the Controller”.
Connection Specification – Wire 22 A
WG maximum to 100 feet or 18 AWG up to 150
feet. Length of wire run cannot exceed 150 feet.
22..
Indirect Sensor (2-Light Blue Wires) are connected to the main control on the Munchkin.
Route wires from the Munchkin control to the external junction box to the sensor (Included in
The Vision I Package) or the mechanical control Honeywell Part # L4080b-1395 (Not included in
Vision I Package) into the control well located in the front of the Super Stor Ultra Indirect Fired
Water Heater. This will allow the installer to control the temperature of the indirect from the
Munchkin and give the Super Stor Indirect Fired Water Heater priority over the Central Heating
Circuit. Once the Water Heater is satisfied, the Munchkin will then switch back to the Central
Heating Circuit only if there is a call for heat, otherwise the Munchkin will then shut down.
Indirect Sensor Function
: The Maximum run time on priority function for the Super Stor Ultra
Indirect Fired Water Heater is from 1-60 minutes. The Super Stor Ultra tank temperature can only be
adjusted when using a sensor (not a mechanical control). Temperature adjustments are from 95 to
185 degrees, plus a differential 1-18 degrees (Note: It is recommend that you do not exceed 5 min-
utes on the DHW pump post purge cycle to avoid cooling down your DHW tank). See section 4,
“P
rogramming the Controller”.
Connection Specification – Wire 22 A
WG maximum to 100 feet or 18 A
WG up to 150
feet. Length of wire run cannot ex
ceed 150 feet.
3. Indirect Circulator Lead (1-P
ink Wires/1-Purple Wires/1-Green Wires)
are
connected to the main controller on the Munchkin. Route wires from the Munchkin control to
the external junction box. Run the wire and connect it directly to the Super Stor Ultra Indirect
circulating pump. The purple wire will be your neutral lead
and the pink wire will be your hot.
This will supply 120 volts to the Super Stor Ultra Indirect Water Heater Circulator directly (The
Circulator is not supplied in the Vision-1 the Package).
Indirect Circulator P
rogram function: The Super Stor Ultra Indirect circulator program function
will automatically start when the Super Stor Ultra sensor reads a call for heat, the installer can also
program the post purge function on the circulator. The Post purge circulator function ranges from 1-
30 minutes.
Connection Specification – Wire 18 A
WG maximum. Length of wire run cannot exceed
100 feet.
CAUTION
The wire to outdoor sensor must not be laid closer than 6' to line voltage wiring
(120/240 V) and must never be in the same conduit.