Overview:
Altronix LPS3C24X220 Linear Power Supply/Charger is specifically designed to provide the power needed by the most
demanding security and access control applications. It converts a 220VAC 60Hz input to a 2.5 amp 24VDC continuous
power-limited output.
Specifications:
Input:
• 220VAC50/60Hz0.5amp.
Output:
• 24VDCoutput.
• 2.5ampcontinuoussupplycurrent.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent500mA.
• Automaticswitchovertostand-bybatterywhen
AC fails (zero voltage drop).
• Fusedbatteryprotection(circuitbreakeravailable).
• Batteryleadsincluded.
Visual Indicators:
• AC/DCpowerLEDindicator.
Enclosure:
• Enclosuredimensions(HxWxDapproximate):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
• Combinationknockoutsare1/2”and3/4”.
• Accommodatesuptotwo(2)12VDC/12AHbatteries.
Installation Instructions:
TheLPS3C24X220shouldbeinstalledinaccordancewithTheNationalElectricalCodeandallapplicableLocalRegulations.
1. MountLPS3C24X220inthedesiredlocation.
2. ConnectACpowertotheblackandredflyingleadsofthetransformer(Fig. 1).
Use18AWGorlargerforallpowerconnections(Battery,DCoutput).
3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Connectdevicestobepoweredtotheterminalsmarked[-DC+](Fig. 1).
5. Connectbatterytotheterminalsmarked[-BAT+](Fig.1)asmarkedontheunit(batteryleadsincluded).
Note:Whenbatteriesarenotused,alossofACwillresultinlossofoutputvoltage.
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel
(see power supply voltage output specifications chart).
Battery Test: Undernormalloadconditions,checkthatthebatteryisfullycharged,checkspecifiedvoltagebothatbattery
terminalandattheboardterminalsmarked-BAT+toensurethatthereisnobreakinthebatteryconnectionwires.
Note:Maximumchargingcurrentunderdischargeis500mA.
Note: Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
LPS3C24X220
Linear Power Supply/Charger
XFMR
AC
DC
AC AC
--- DC +
--- BAT +
ALTRONIX CORP. "LPS3 POWER SUPPLY"
Red
Lead
Black
Lead
Input 220VAC
50/60Hz
0.7 amp
24V Open
SW2
Fig. 1