Altronix AL300XPD16CB220 Installation guide

Category
Electrical enclosures
Type
Installation guide

This manual is also suitable for

Rev. 062206
AL300X220 Series
Power Supply/Charger
Installation Guide
Models Include:
•AL300X220
- Single Output
•AL300PD4220 •AL300PD4CB220
- Four (4) Fused Outputs - Four (4) PTC Outputs
•AL300PD8220 •AL300PD8CB220
- Eight (8) Fused Outputs - Eight (8) PTC Outputs
•AL300XPD16220 •AL300XPD16CB220
- Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs
For a red enclosure, add an “R” suffix to the part # e.g. AL300PD8R220
For a larger enclosure, add an “X” suffix to the part # e.g. AL300XPD8220
- 2 - AL300220series
Overview:
The AL300X220 is a power supply that converts a nominal 220VAC (working range 198VAC - 256VAC) 50/60Hz input
to a 12VDC or 24VDC regulating output (see specifications below).
The AL300X220 is a base power supply unit for multi-output power supply/charger series:
AL300PD4220, AL300PD4CB220, AL300PD8220, AL300PD8CB220, AL300XPD16220, AL300XPD16CB220
(Refer to AL300X220 Series Power Supply Configuration Reference Chart below).
Input:
• Nominal 220VAC (working range 198VAC - 256VAC)
50/60Hz, 0.75 amp.
• ACinputandDCoutputLEDindicators.
Output:
• 12VDCor24VDCselectableoutput(s).
• 2.5amptotalsupplycurrent.
• Filteredandelectronicallyregulatedoutput(s).
• Shortcircuitandthermaloverloadprotection.
BatteryBackup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhenACfails.
• Maximumchargecurrent0.7amp.
BatteryBackup(cont’d):
• Zerovoltagedropwhenswitchedoverto
battery backup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Additional Features:
•Powersupply,enclosure,camlockandbatteryleads.
• Allmodelsareavailableinredenclosure
(addan“R”suffixtothepart#e.g.AL300PD8R220).
Specifications:
AL300X220 Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
Total Output
Rating (amp)
Output Rating (amp)
per Output
Power Supply Input
Fuse Rating
Power Supply
Output Fuse Rating
Enclosure
Dimensions
Accomodates
Stand-by Batteries
AL300X220
----- 1 ----- ----- 2.5 2.5
5A/
250V
15A/
32V
13.5”x13”x3.25”
(342.99mmx330.2mmx82.55mm)
Two (2)
12VDC/7AH
AL300XX220
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/12AH
AL300PD4220
PD4
4
x ----- 2.5 3.5
5A/
250V
15A/
32V
13.5”x13”x3.25”
(342.99mmx330.2mmx82.55mm)
Two (2)
12VDC/7AH
AL300XPD4220
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/12AH
AL300PD4CB220
PD4CB ----- x 2.5 2.5
5A/
250V
15A/
32V
13.5”x13”x3.25”
(342.99mmx330.2mmx82.55mm)
Two (2)
12VDC/7AH
AL300XPD4CB220
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/7AH
AL300PD8220
PD8
8
x ----- 2.5 3.5
5A/
250V
15A/
32V
13.5”x13”x3.25”
(342.99mmx330.2mmx82.55mm)
Two (2)
12VDC/7AH
AL300XPD8220
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/7AH
AL300PD8CB220
PD8CB ----- x 2.5 2.5
5A/
250V
15A/
32V
13.5”x13”x3.25”
(342.99mmx330.2mmx82.55mm)
Two (2)
12VDC/7AH
AL300XPD8CB220
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/12AH
AL300XPD16
Two (2)
PD8
16
x ----- 2.5 3.5
5A/
250V
15A/
32V
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/12AH
AL300XPD16CB
Two (2)
PD8CB
----- x 2.5 2.5
5A/
250V
15A/
32V
15.5”x12”x4.5”
(393.7mmx304.8mmx114.3mm)
Two (2)
12VDC/12AH
AL300220series - 3 -
Stand-by Specifications (total current shown):
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by=2.5amp
Alarm=2.5amp
Stand-by=1.0amp
Alarm=2.5amp
Stand-by=300mA
Alarm=2.5amp
24VDC / 12AH Battery --------
Stand-by=200mA
Alarm=2.5amp
--------
24VDC / 40AH Battery
Stand-by=2.5amp
Alarm=2.5amp
Stand-by=1.0amp
Alarm=2.5amp
Stand-by=300mA
Alarm=2.5amp
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
Battery connection
SwitchPosition:
24VDC=SW1OPEN
12VDC=SW1CLOSED
Wire
Strap
(from
Enclosure
to Door)
Battery & AC
Supervision
Circuit
-
For 12VDC Operation
use hook-up in the
inset on the right
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum 0.25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
220VAC
power mains
Earth
Ground
+ DC ---
+
BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
Opened - 24V
Closed - 12V
J1
SW1
Opened - 24V
Closed - 12V
SW1
5A 250V
15A 250V
AC Delay
15
L G N
NC C NO NC C NO AC Fail
Bat Fail
DCOutputtodevices
NC C NO NC C NO
Battery &
ACSupervision Circuit
Fig. 1
Fig. 1a
Fig. 1b
Power Supply Output Specifications:
Output Switch Position
12VDC SW1-CLOSED
24VDC SW1-OPEN
OPEN SWITCH
CLOSED SWITCH
- 4 - AL300220series
Installation Instructions:
WiringmethodsshouldbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSIandwithalllocal
codesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly.
1. Mountunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe
enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s
upperkeyholesoverthetwoupperscrews;levelandsecure.Markthepositionofthelowertwoholes.Removethe
enclosure.Drillthelowerholesandinstallthreefasteners.Placetheenclosure’supperkeyholesoverthetwoupper
screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 7,8).
Secureenclosuretoearthground.
2. SettheunittothedesiredDCoutputvoltagebysettingSW1 (Fig. 1b, pg. 3) to the appropriate position
(Power Supply Voltage Output Selections Chart, pg. 3).
3. Securecabinettoearthground.ConnectACpower(220VAC/60Hz)totheterminalsmarked[L,G,N](Fig. 1, pg. 3).
Use14AWGorlargerforallpowerconnections(Battery,DCoutput,ACinput).
Use22AWGto18AWGforpower-limitedcircuits(ACFail/LowBatteryreporting).
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
Whenservicingtheunit,ACmainsshouldberemoved.
5. Connectdevicestobepowered:
a. ForAL300X220PowerSupply:connectdevicestotheterminalsmarked[-DC+](Fig. 1, pg. 3).
b. ForotherPowerDistributionModels:connectdevicestobepoweredtotheterminalpairs1to4marked[1P&1N]
through[4P&4N](Fig. 2a & 2b, pg. 6)or1to8marked[1P&1N]through[8P&8N](Fig. 3a & 3b, pg. 6),
carefully observing correct polarity.
6. ForAccessControlapplicationsbatteriesareoptional.Whenbatteriesarenotused,alossofACwillresultinthe 
lossofoutputvoltage.Whentheuseofstand-bybatteriesisdesired,theymustbeleadacidorgeltype.
Connectone(1)12VDCbatterytotheterminalsmarked[+BAT-]for12VDCoperation.Usetwo(2)12VDC
batterieswiredinseriesfor24VDCoperation.
7. Connectappropriatesignalingnotificationdevicestotheterminalsmarked[ACFAIL&BATFAIL](Fig. 1a, pg. 3)
supervisory relay outputs.
Note:Whenusedinfirealarm,burglaralarmoraccesscontrolapplications,“ACFail”relaymustbeusedto
provideavisualindicationofACpoweron.
8. PleaseensurethatthecoverissecuredwiththeprovidedKeyLock.
AL300220series - 5 -
LED Diagnostics:
AL300XB220-PowerSupplyBoard
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC.Stand-bybatterysupplyingpower.
OFF ON No DC output.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
Red (Bat) Battery Status
ON Normaloperatingcondition.
OFF Battery fail/low battery.
Terminal Identification:
AL300XB220-PowerSupplyBoard
Terminal Legend Function/Description
L,G,N Connect220VAC50/60Hz.totheseterminals:Ltohot,NtoNeutral.Donotusethe[G]terminal.
+DC--- 12VDCor24VDC@2.5ampcontinuouspower-limitedoutput.
ACFail
NC,C,NO
IndicateslossofACpower,e.g.connecttoannunciator/alarmpanel.Relaynormallyenergizedwhen
ACpowerispresent.Contactrating1amp@28VDC.ACFailconditionwillreportapproximately
withinone(1)minuteafterlossofAC.Todelayreportfor6hours,cutjumperJ1onthePowerSupply
Board(ACtroubleoutputdelayoption).Ifthismodeisselected,thePowerSupplyBoardmustbe
resetbyremovingallpowertoitfor30seconds.
BatFail
NC,C,NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
powerispresent.Contactrating1amp@28VDC.Lowbatteryconditionswillreportapproximately
21VDC(24VDCoutputsetting)orapproximately10.5VDC(12VDCoutputsetting).Batterypresence
detectionwillreportapproximately1minuteafterbatteryremainsundetected(missingorremoved).
+BAT--- Stand-bybatteryconnections.Maximumchargecurrent0.7amp.
LED Diagnostics:
PD4/PD4CB/PD8/PD8CB-PowerDistributionModule
Green Power Distribution Module Status
ON Normaloperatingcondition.
OFF NoPowerOutput.
Terminal Identification:
PD4/PD4CB/PD8/PD8CB-PowerDistributionModule
Terminal Legend
Function/Description
PD4/PD4CB PD8/PDCB
1P to 4P 1P to 8P Positive DC power outputs.
1N to 4N 1N to 8N Negative DC power outputs.
- 6 - AL300220series
INPUT
LED
PD4
POWER DISTRIBUTING UNIT
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS
F1 F2 F3 F4
COMMON POWER OUTPUTS
1P
1N
2P
2N
3P
3N
4P
4N
From Power Supply
Board
(Factory Installed)
Non Power-Limited
DC Output to devices
1P-4P Power Outputs,
1N-4N Common Outputs
()
Fig. 2a
Fig. 3a
Power Distribution Module(s):
INPUT
LED
F1 F2 F3 F4
POWER OUTPUTS
1P
1N
2P
2N
3P
3N
4P
4N
Class 2 Rated Power-Limited
DC Output to devices
1P-4P Power Outputs,
1N-4N Common Outputs
From Power Supply
Board
(Factory Installed)
()
Fig. 2b
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Non Power-Limited
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
(
)
PD8
POWER DISTRIBUTING UNIT
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Class 2 Rated Power-Limited
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
()
Fig. 3b
AL300220series - 7 -
Wiring:
USE14AWGorlargerforallpowerconnections.
Note:Takecaretokeeppower-limitedcircuitsseparatefromnonpower-limitedwiring(220VAC,Battery).
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:UndernormalloadconditionstheDCoutputvoltageshouldbecheckedforpropervoltagelevel
(Power Supply Voltage Output Specifications Chart, pg. 3).
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged,checkspecifiedvoltagebothatthe
batteryterminalandattheboardterminalsmarked[+BAT-]toensurethatthereisnobreakinthebatteryconnectionwires.
Note:Maximumchargingcurrentunderdischargesis0.7amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
Enclosure Dimensions:
•AL300X220
•AL300PD4220 •AL300PD4CB220
•AL300PD8220 •AL300PD8CB220
13.5”x13”x3.25”(342.99mmx330.2mmx82.55mm)
1.40
(36mm)
1.40”
(36mm)
4.85
(123mm)
4.85
(123mm)
1.40
(36mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
13.0”
(330mm)
5.10”
(130mm)
6.5625”
(167mm)
1.20
(31mm)
1.20”
(31mm)
1.20”
(31mm)
3.25
(83mm)
3.25”
(83mm)
3.25
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
(
25mm
)
10.5
(
267mm
)
1.0”
(
25mm
)
1.0”
(25mm)
0.75
(19mm)
0.75”
(19mm)
0.9375”
(24mm)
0.9375”
(24mm)
11.0
(279mm)
12.5
(318mm)
- 8 - AL300220series
Altronixisnotresponsibleforanytypographicalerrors.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:[email protected],LifetimeWarranty,MadeinU.S.A.
IIAL300X220series F27N
MEMBER
Enclosure Dimensions:
•AL300XX220
•AL300XPD4220 •AL300XPD8220 •AL300XPD16220
•AL300XPD4CB220 •AL300XPD8CB220 •AL300XPD16CB220
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
1.75”
(44.45mm)
1.75”
(44.45mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.1”
(27.94mm)
1.1”
(27.94mm)
0.79”
(20.06mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
0.91”
(23.114mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
(393.7mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8