  • Hello! I am an AI chatbot trained to assist you with the Socomec DIRIS Digiware M Quick Start. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DIRIS Digiware M-50 & M-70
Multi-protocol communication gateways
CORPORATE HQ CONTACT: SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE. Non contractual document
548749B
DIRIS Digiware M-50
Ref. 4829 0221
DIRIS Digiware M-70
Ref. 4829 0222
www.socomec.com
This symbol indicates that the full instruction
manual, declaration of conformity EU-type
examination certicate are available on the
Socomec website:
www.socomec.com/operating-instructions
Please consult safety
warning (ref. 546660)
before installing the
devices.
1
b Dimensions (in/mm)
3.52
89.5
3.5
89
Ø 0.24
Ø 6
0.24
6
1.97
50
1.77
45
2.56
65
4.49
114
3.52
89.5
3.5
89
Ø 0.24
Ø 6
0.24
6
1.97
50
1.77
45
2.56
65
4.49
114
1
a Mounting
L
1
0.29 or 0.59
7,5 or 15
1.38
35
2
DIN rail mounting with access to front face only
2
Technical characteristics DIRIS Digiware M-50 DIRIS Digiware M-70
Communication characteristics
Default IP address 192.168.0.4 192.168.0.4
Ethernet RJ45 10/100 Mbs
Gateway: MODBUS TCP / RTU
BACnet IP / SNMP v1 v2 v3
Embedded software - WEBVIEW-M
Max connected devices 32
RJ45 Digiware bus Input
RS485 2-3 wires Input (Master) / Output (Slave)
Speed 9600 bds (10 devices max) / 38400 bds - 115200 bds (32 devices max)
RJ9 port Not used yet
Micro USB For conguration
Bluetooth Low Energy
Use No feature implemented yet
Operating frequency 2402 to 2480 MHz
EIRP Power 6.23 dBm (measured max. average)
Electrical characteristics
Power supply 24 VDC +/- 10%, 20 W max
Supply protection Integrated into SOCOMEC supply (ref. 4829 0120) or use 24 VDC 1 A gG/Am fuse
Consumption 2.5 VA
Environmental characteristics
Use Indoor
Storage temperature -25 ... +70 °C
Operating temperature -10 ... +55 °C
Humidity 95 % at +40 °C without condensation
Maximum operating altitude 2000 m
Pollution degree 2
Protection class IP 40 (front face)
7
SPECIAL WARNING FOR USA AND CANADA
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
(2) this device must accept any interference received,
including interference that may cause undesired opera
-
tion. (§15.19 (3)).
FCC ID: 2AT66-DIRISDGWM
Canada, Industry Canada (IC) Notices
This device complies with Industry Canada license-
exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause
interference, and (2) this device must accept any interfe
-
rence, including interference that may cause undesired
operation of the device.
IC ID: 25318-DIRISDGWM
Le présent appareil est conforme aux CNR d’ ISED appli-
cables aux appareils radio exempts de licence. L’exploi-
tation est autorisée aux deux conditions suivantes : (1) le
dispositif ne doit pas produire de brouillage préjudiciable, et
(2) ce dispositif doit accepter tout brouillage reçu, y compris
un brouillage susceptible de provoquer un fonctionnement
indésirable.
6
LEDs and push buttons
Launch Bluetooth pairing process
Start auto-discovery and auto-addressing of slave devices
USB port for conguration
Not used
ALARM
ON
COM
ADDR.
ETHETH
EXT.
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
LED OFF Stable Flashing
ON
(Green)
Device is off Product ON
- 10 sec During
startup
- Manual blinking
command
ALARM
(Red)
No active alarm
Measurement
alarm active on a
slave device
System alarm
active on a
device
COM
(Orange)
No
communication
-
Product
communicating
(Blue)
Bluetooth is
deactivated
Bluetooth is
activated
Ongoing
Bluetooth pairing
process
®
®
5
Communication architectures
*
24 VDC
(20 W max)
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
RS485
DIRIS Digiware M-50/M-70
Digiware Bus
Ethernet
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
MASTER
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
*
24 VDC
(20 W max)
RS485
DIRIS Digiware M-50/M-70
DIRIS B
Digiware Bus
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
SLAVE
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
a. RS485 Master
b. RS485 Slave
* If the 24 VDC power supply is not provided by Socomec, a 1 A / 24 VDC fuse must be used. For North America, the use of recognized fuses is mandatory.
4
Conguration via Easy Cong software
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
Ethernet
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
USB
Ethernet USB
3
System wiring
DIRIS
DigiwareU
Voltage
Inputs (U)
DIRIS
DigiwareI
Current
Inputs (3I)
Digiware Bus
Com
Ethernet
RJ45
U
Voltage inputs
50-300VAC PH/N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
4 positions
screw 0.25 Nm max.
L1
L2
L3
N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
2 positions - screw 0.25 Nm max.
Supply
24VDC SELV
(**)
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
3 positions - screw 0.25 Nm max.
Com
RS485 Modbus
I
Current
inputs
Sensors 3x
Micro
USB
type B
(*)
Only use a SOCOMEC Digiware bus cable
(UTP RJ45 straight, twisted pair, unshielded,
AWG24, 600V CAT V -10 ... +70°C).
When wiring, make sure you separate the
low voltage (LV) section and the very low
voltage (SELV) section to prevent any risk of
electric shock.
Maximum 1200 m for RS485 bus
Max. length for Digiware bus = 300 m
(witha maximum of 2 C-32 repeaters)
(*) Functional Earth
(**) SELV = Saftety Extra Low Voltage
When installed close to uninsulated live parts, use
personal protective equipment to manipulate the device
(push buttons and ports).
/