Socomec DIRIS Digiware M Quick Start

Type
Quick Start

Socomec DIRIS Digiware M is a multi-protocol communication gateway that seamlessly integrates with various energy meters and devices using Ethernet, RS485, and Digiware bus protocols. It acts as a central hub, enabling real-time monitoring, data acquisition, and control of electrical installations. With its embedded webserver, the DIRIS Digiware M provides a user-friendly interface for remote access, configuration, and data visualization. It supports industry-standard protocols like Modbus TCP/RTU, BACnet IP, and SNMP, ensuring seamless integration with existing building management systems.

Socomec DIRIS Digiware M is a multi-protocol communication gateway that seamlessly integrates with various energy meters and devices using Ethernet, RS485, and Digiware bus protocols. It acts as a central hub, enabling real-time monitoring, data acquisition, and control of electrical installations. With its embedded webserver, the DIRIS Digiware M provides a user-friendly interface for remote access, configuration, and data visualization. It supports industry-standard protocols like Modbus TCP/RTU, BACnet IP, and SNMP, ensuring seamless integration with existing building management systems.

DIRIS Digiware M-50 & M-70
Multi-protocol communication gateways
CORPORATE HQ CONTACT: SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE. Non contractual document
548749B
DIRIS Digiware M-50
Ref. 4829 0221
DIRIS Digiware M-70
Ref. 4829 0222
www.socomec.com
This symbol indicates that the full instruction
manual, declaration of conformity EU-type
examination certicate are available on the
Socomec website:
www.socomec.com/operating-instructions
Please consult safety
warning (ref. 546660)
before installing the
devices.
1
b Dimensions (in/mm)
3.52
89.5
3.5
89
Ø 0.24
Ø 6
0.24
6
1.97
50
1.77
45
2.56
65
4.49
114
3.52
89.5
3.5
89
Ø 0.24
Ø 6
0.24
6
1.97
50
1.77
45
2.56
65
4.49
114
1
a Mounting
L
1
0.29 or 0.59
7,5 or 15
1.38
35
2
DIN rail mounting with access to front face only
2
Technical characteristics DIRIS Digiware M-50 DIRIS Digiware M-70
Communication characteristics
Default IP address 192.168.0.4 192.168.0.4
Ethernet RJ45 10/100 Mbs
Gateway: MODBUS TCP / RTU
BACnet IP / SNMP v1 v2 v3
Embedded software - WEBVIEW-M
Max connected devices 32
RJ45 Digiware bus Input
RS485 2-3 wires Input (Master) / Output (Slave)
Speed 9600 bds (10 devices max) / 38400 bds - 115200 bds (32 devices max)
RJ9 port Not used yet
Micro USB For conguration
Bluetooth Low Energy
Use No feature implemented yet
Operating frequency 2402 to 2480 MHz
EIRP Power 6.23 dBm (measured max. average)
Electrical characteristics
Power supply 24 VDC +/- 10%, 20 W max
Supply protection Integrated into SOCOMEC supply (ref. 4829 0120) or use 24 VDC 1 A gG/Am fuse
Consumption 2.5 VA
Environmental characteristics
Use Indoor
Storage temperature -25 ... +70 °C
Operating temperature -10 ... +55 °C
Humidity 95 % at +40 °C without condensation
Maximum operating altitude 2000 m
Pollution degree 2
Protection class IP 40 (front face)
7
SPECIAL WARNING FOR USA AND CANADA
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
(2) this device must accept any interference received,
including interference that may cause undesired opera
-
tion. (§15.19 (3)).
FCC ID: 2AT66-DIRISDGWM
Canada, Industry Canada (IC) Notices
This device complies with Industry Canada license-
exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause
interference, and (2) this device must accept any interfe
-
rence, including interference that may cause undesired
operation of the device.
IC ID: 25318-DIRISDGWM
Le présent appareil est conforme aux CNR d’ ISED appli-
cables aux appareils radio exempts de licence. L’exploi-
tation est autorisée aux deux conditions suivantes : (1) le
dispositif ne doit pas produire de brouillage préjudiciable, et
(2) ce dispositif doit accepter tout brouillage reçu, y compris
un brouillage susceptible de provoquer un fonctionnement
indésirable.
6
LEDs and push buttons
Launch Bluetooth pairing process
Start auto-discovery and auto-addressing of slave devices
USB port for conguration
Not used
ALARM
ON
COM
ADDR.
ETHETH
EXT.
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
LED OFF Stable Flashing
ON
(Green)
Device is off Product ON
- 10 sec During
startup
- Manual blinking
command
ALARM
(Red)
No active alarm
Measurement
alarm active on a
slave device
System alarm
active on a
device
COM
(Orange)
No
communication
-
Product
communicating
(Blue)
Bluetooth is
deactivated
Bluetooth is
activated
Ongoing
Bluetooth pairing
process
®
®
5
Communication architectures
*
24 VDC
(20 W max)
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
RS485
DIRIS Digiware M-50/M-70
Digiware Bus
Ethernet
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
MASTER
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
*
24 VDC
(20 W max)
RS485
DIRIS Digiware M-50/M-70
DIRIS B
Digiware Bus
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
SLAVE
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
a. RS485 Master
b. RS485 Slave
* If the 24 VDC power supply is not provided by Socomec, a 1 A / 24 VDC fuse must be used. For North America, the use of recognized fuses is mandatory.
4
Conguration via Easy Cong software
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
Ethernet
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ADDR.
ALARM
ON
COM
DIRIS M-xx
USB
Ethernet USB
3
System wiring
DIRIS
DigiwareU
Voltage
Inputs (U)
DIRIS
DigiwareI
Current
Inputs (3I)
Digiware Bus
Com
Ethernet
RJ45
U
Voltage inputs
50-300VAC PH/N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
4 positions
screw 0.25 Nm max.
L1
L2
L3
N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
2 positions - screw 0.25 Nm max.
Supply
24VDC SELV
(**)
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
3 positions - screw 0.25 Nm max.
Com
RS485 Modbus
I
Current
inputs
Sensors 3x
Micro
USB
type B
(*)
Only use a SOCOMEC Digiware bus cable
(UTP RJ45 straight, twisted pair, unshielded,
AWG24, 600V CAT V -10 ... +70°C).
When wiring, make sure you separate the
low voltage (LV) section and the very low
voltage (SELV) section to prevent any risk of
electric shock.
Maximum 1200 m for RS485 bus
Max. length for Digiware bus = 300 m
(witha maximum of 2 C-32 repeaters)
(*) Functional Earth
(**) SELV = Saftety Extra Low Voltage
When installed close to uninsulated live parts, use
personal protective equipment to manipulate the device
(push buttons and ports).
  • Page 1 1
  • Page 2 2

Socomec DIRIS Digiware M Quick Start

Type
Quick Start

Socomec DIRIS Digiware M is a multi-protocol communication gateway that seamlessly integrates with various energy meters and devices using Ethernet, RS485, and Digiware bus protocols. It acts as a central hub, enabling real-time monitoring, data acquisition, and control of electrical installations. With its embedded webserver, the DIRIS Digiware M provides a user-friendly interface for remote access, configuration, and data visualization. It supports industry-standard protocols like Modbus TCP/RTU, BACnet IP, and SNMP, ensuring seamless integration with existing building management systems.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI