Potter S-24 and HS-24 Selectable Candela Strobe and Horn/Strobes Owner's manual

Category
Fire protection
Type
Owner's manual
PAGE 1 OF 4
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
S3247
Features
• 24VDCunitshaveeldselectablecandelaoptionsof15,30,60,
75&110
• Super-Slide®Bracket-EaseofSupervisionTesting
• Checkmate®-InstantVoltageVerication
• Synchronizestrobeand/orhornwithAVSMControlModule
• Prewireentiresystem,installmountingbracket,theninstall
signals
• Documentedlowerinstallationandoperatingcosts
• SwitchselectionforhighorlowdBA
• Switchforchime,whoop,mechanicaland2400Hztone
• Tamperproofre-entrantstylegrill
• Switchforcontinuousortemporal3tone(notavailableon
whooptone)
• Silenceaudiblewhilevisualappliancewillremainashing(for
useinacceptedjurisdictions)
• Faceplateavailableinredoroff-white
Description
TheS-24/HS-24Seriesisalowprolestrobeandhorn/
strobecombinationthatoffersdependableaudibleandvisual
alarmsandtheabsolutelowestcurrentavailable.TheS-24
&HS-24Series24VDCofferstamperproofeldselectable
candelaoptionsof15,30,60,75,and110candela.The
StrobeandHorn/Strobeoffersacontinuousorsynctemporal
threein2400Hzandmechanicaltone,achimeandwhoop
tone.Alltonesareeasyfortheprofessionaltochangeinthe
eldbytheuseofswitches.TheS-24&HS-24Serieshasa
minimaloperatingcurrentandhasaminimumashrateof
1Hzregardlessofinputvoltage.
ThisSeriesisshippedwithastandard4”metalmounting
platewhichincorporatesthepopularSuper-Slide®feature
thatallowstheinstallertoeasilytestforsupervision.The
productalsofeaturesalockingmechanismwhichsecuresthe
producttothebracketwithoutanyscrewsshowing.
TheS-24/HS-24alsofeaturesthepatentedCheckmate®-
InstantVoltageVericationfeaturewhichallowstheinstaller
tocheckthevoltagedropdrawandmatchittotheblueprint.
TheS-24&HS-24SeriesappliancesareANSI/UL464and
ANSI/UL1971,listedforusewithreprotectivesystems
andarewarrantedforthreeyearsfromdateofpurchase.
Technical Specications
MountingOptions
SingleorDoublegang,4”
squarebox,andAVBBsurface
mountbackbox
Terminals Screw-ClampType
WireGauge 18 – 12 AWG
OperatingTemp 32°F–120°F(0°–49°C)
Dimensions
Height–5”
Width–4.5”
Depth–2.5”
ShippingWeight 1.05lbs
firealarmresources.com
PAGE 2 OF 4
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
8830054-REV C 6/17
TONE SWITCHPOSITION
345
MechanicalTemporal3 ON ON ON
MechanicalContinuous OFF ON ON
2400HzTemporal3 ON OFF ON
2400HzContinuous OFF OFF ON
ChimeTemporal3 ON ON OFF
ChimeContinuous OFF ON OFF
Whoop ON OFF OFF
Whoop OFF OFF OFF
NOTE:
•SwitchPositions1Theand2intheOFFpositiontoselect
isolatedhornandstrobepowerinputs
•SwitchPosition6ON=HIGHdBA
•SwitchPosition6OFF=LOWdBA
Candela selection
slider switch. Depress
center and slide switch to
desired brightness level.
Break off pin and insert into
hole at the bottom of the
selector to lock candela
setting. Signal must be
removed from bracket and
pin pushed forward from
backside out of hole to
change candela.
The access holes are provided in the back of the terminal
block to allow the voltage to be measured directly without
removing the device. Typically this would be done at the
end of the line to confirm design criteria. Most measure-
ments will be taken using the S+ and S- locations although
access is provided to other locations. NOTE: Care should
be taken to not short the test probes.
Super Slide® Mounting Bracket
Allows the installer to pre-wire the system, test for system
supervision, remove the signal head until occupancy, switch
out signals without changing mounting brackets and has
locking edge connector for snap-in-place installation.
To remove bezel,
grip both sides of
bezel and pull in
a downward and
outward motion.
Candela Selection Checkmate™ - Instant Voltage Verication
Switch Locations
firealarmresources.com
PAGE3OF4
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
8830054-REV C 6/17
S-24 24 VDC Selectable Candela, Low
Prole Evacuation Strobe
Model
Number PartNumber Nominal
Voltage
Candela(ANSI/UL
1971)
S-24WR 4890010 24 VDC 15,30,60,75,110
S-24WW 4890011 24 VDC 15,30,60,75,110
HS-24 24 VDC Selectable Candela,
Low Prole Evacuation Strobe
ModelNumber PartNumber NominalVoltage Candela(ANSI/
UL1971)
ReverberantdBAat10
ft,perANSI/UL464
InAnechoicRoomat
10ft
HS-24WR 4890030 24 VDC 15,30,60,75,110 62-82 100
HS-24WW 4890031 24 VDC 15,30,60,75,110 62-82 100
S-24 & HS 24 Strobe Current Ratings
24 VDC (16 - 33 Volts)
Candela 24 VDC UL Max
15 cd 30 mA 42 mA
30 cd 35 mA 58 mA
60 cd 66 mA 97 mA
75 cd 80 mA 116 mA
110 cd 103 mA 161 mA
Model Designations:
W=Wallmount
R=RedFaceplate W=WhiteFaceplate
Allunitsareavailableinplain(nolettering)
Plainunitsarenon-returnable.
“ALERT”bezelavailablefororder.
“AGENT”bezelavailablefororder.
S-24 & HS-24 Horn Ratings
HornMode
HornDecibelLevels HornCurrentRatings
MinimumSPLat10ft,per
ANSI/UL464(HIGH)
MinimumSPLat10ft,
perANSI/UL464(LOW)
Regulated24VDCMax
Operating@HighSetting(mA)
Temp3(2400Hz) 78dBA 71*dBA 28mA
Temp3(Mechanical) 76dBA 70*dBA 25mA
Temp3(Chime) 70*dBA 66*dBA 15mA
Continuous(2400Hz) 81dBA 74*dBA 28mA
Continuous(Mechanical) 80dBA 72*dBA 25mA
Continuous(Chime) 70*dBA 66*dBA 15mA
Whoop 82dBA 69*dBA 56mA
NOTES:
•FornominalandpeakcurrentacrossANSI/ULregulatedvoltagerangeforlteredDCpowerandunltered(FWR[FullWave
Rectied])powerseeinstallationmanual.
•Potterdoesnotrecommendusingacodedorpulsingsignalingcircuitwithanyofourstrobeproducts.
•Thesoundoutputforthetemporal3toneisratedlowersincethetimethehornisoffisaveragedintothesoundoutputrating.While
thehornisproducingatoneinthetemporal3modeitssoundpressureisthesameasthecontinuousmode.
*OperatingthehorninthismodeatthisvoltagewillresultinnotmeetingtheminimumANSI/UL464reverberantsoundlevel
requiredforpublicmodereprotectionservice.Thesesettingsareacceptableonlyforprivatemoderealarmuse.UsethehighdBA
settingforpublicmodeapplication(notapplicablewhenusingthechimetone.Thechimetoneisalwaysprivatemode).
firealarmresources.com
PAGE 4 OF 4
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
8830054-REV C 6/17
S-24 & HS-24 Series Wiring Diagram
Notes:
Allstrobesaredesignedtoashasspeciedwithcontinuousappliedvoltage.Strobesshouldnotbeusedoncodedorpulsingsignalingcircuits.
However,useofthePotterAVSMcontrolmoduleorGentexsynchronizationprotocolispermittedtosynchronizethestrobe,horn,and/ormutethehorn.
•FORSYNCHRONIZATIONWIRINGINFORMATION,REFERENCEAVSMCONTROLMODULEDATASHEET(8830050)AND/ORAVSM
CONTROLMODULEMANUALFORSYNCHRONIZATIONMODULEWIRINGDIAGRAMS.AVSMCONTROLMODULEDATASHEETAND
MANUALCANBEOBTAINEDAThttp://pottersignal.comORCALLPOTTERELECTRICTECHNICALSUPPORTAT1-866-956-1211
Architect & Engineering Specications
Theaudibleand/orvisiblesignalshallbePotterS-24strobeandPotterHS-24horn/strobeSeriesorapprovedequalandshallbe
listedbyUnderwritersLaboratories,Inc.perANSI/UL1971and/orANSI/UL464.Thenoticationapplianceshallalsobelistedwith
FactoryMutualListingService(FM)andtheCaliforniaStateFireMarshal(CSFM).
Thenoticationappliance(combinationaudible/visible)shallproduceapeaksoundoutputof100dBAorgreaterat24VDCas
measuredinananechoicchamber.Thesignalingapplianceshallalsohavethecapabilitytosilencetheaudiblesignalwhileleavingthe
visiblesignalenergizedwiththeuseofasinglepairofpowerwires.Additionally,theusershallbeabletoselecteithercontinuousor
temporaltoneoutputwiththetemporalsignalhavingtheabilitytobesynchronized.
Unitshallbecapableofbeinginstalledsothatanyunauthorizedattempttochangethecandelasettingwillresultinatroublesignalat
therealarmcontrolpanel.
Theaudible/visibleandvisiblesignalingapplianceshallalsomaintainaminimumashrateof1Hzorupto2Hzregardlessofpower
inputvoltage.Thestrobeapplianceshallhaveanoperatingcurrentof42mAorlessat24VDCforthe15Cdstrobecircuit.
Theapplianceshallbepolarizedtoallowforelectricalsupervisionofthesystemwiring.Theunitshallbeprovidedwithamounting
bracketwithterminalsandbarriersforinput/outputwiringandbeabletomounttoasinglegangordoublegangboxordouble
workboxwithouttheuseofanadapterplate.Theunitshallhaveaninputvoltagerangeof16-33voltswitheitherdirectcurrentorfull
waverectiedpowerfor24VDCmodels.
Theapplianceshallbecapableoftestingsupervisionwithoutdisconnectingwires,verifyvoltagewithoutremovingunitandbe
capableofmountingtoasurfacebackbox.
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4