4.3 Outdoor installation
Base
The base should project approx 50 mm beyond all sides of the heat pump and be sufficiently
high enough to account for snow and water ingress.
Prior to installation
Fig. 3: Dimensions of air inlet
1 Heating flow Ø 1" (16), Ø 1¼" (AMBIFLO
20) flexible. The hydraulic and electrical
connections can all be located on the left
or right of the heat pump.
10
Pump base, minimum height 300 mm,
taking the depth of local snow falls into
account
2 Heating flow Ø1" (16), Ø 1¼" (20)
flexible.
12
Wall aperture with seal tilted towards the
inside (made of PE, internal diameter
150 mm)
3
4
Condensation water outlet Ø ¾", flexible
Air inlet (ZA AMBIFLO accessory)
13
Control unit for wall installation (included
in delivery), siphon for condensation
water at a minimum height of 100 mm.
5
6
7
8
Air outlet (ZA AMBIFLO accessory),
either right
or left
Internal electrical control panel
Hydraulic and electrical connections,
electrical cables – extra-low voltage
shielded from 400V and 230V cables.
Adjustable legs, absorbing structure-
borne noise
A minimum distance of 800 mm must be
maintained at the front of the heat pump
for maintenance purposes. A minimum
distance of 700 mm (o 500 mm for Set
AAS) must be kept at the back (on the
suction side). A minimum distance of
500 mm is required on the free side
opposite the air outlet, while a minimum
distance of 2 000 mm is required on the
outlet side.
9 Protective roof (ZA AMBIFLO accessory)
Table 1: Dimensions
Pump base AMBIflo Width a Height without
protective roof
b
Depth
c
Bottom
height
d
Top height without
protective roof e
a1 c1 h1
Legs
q
16
1195 1675 750 575 1060 1295 850 300 40
20
1195 1695 880 670 975 1295 980 300 50
AMBIFLO accessory: incl. 2 weather protection grids, control panel cover and protective roof