Danfoss Massive wooden planks on battens (direct load) User guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss Massive wooden planks on battens (direct load) User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Application Sheet
SpeedUp Eco
Massive wooden planks on battens
Direct load
VAEUG102 © Danfoss 10/2009
1 Wooden planks ≤ 22 mm
2 SpeedUp Eco heat panel + FH composite pipe 30 mm
3 Support batten (30 mm)
4 SpeedUp Eco perimeter insulation
5 If necessary, moisture barrier
6 Support batten (30 mm) c/c 550 mm
Technical Data
Floor finish
≤ 22 mm Massive wooden planks or parquet
Construction height
≤ 52 mm Height including floor finish
Weight
~ 23 kg / m² Weight including floor finish
Thermal resistance (R)
0,75 m²K / W Thermal resistance value for SpeedUp panel
Thermal transmission coefficient (U)
1,09 W / m²K
Be aware that building regulations can specify better thermal
insulation
Distribution load
≤ 2,0 kN / m²
Point load (≥ 20 cm²)
≤ 2,0 kN
Sum point load ≤ design load; please notice special heavy objects
(aquaria etc.)
Impact subsonic noise reduction
21 dB
Test value according to ISO 140-8; applies to concrete slabs thicker
than 12 cm
Application area
Rooms in residential bulildings and houses; bedrooms and wards in hospitals; bedrooms
in hotels and hostels kitchens and toilets. Correponding to category A of EN 1991. Office
areas. Correponding to category B of EN 1991.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (maximum uneveness allowed is 3 mm per 1 m).
If necessary, protect floorboards and prefabricated parquet against moisture penetration
from below according to the manufacturer’s instructions (vapour barrier).
Structural sealing according to EN 13967 must be placed beneath the floor panel in case
of structures facing the ground, and otherwise on the unfinished floor.
Observe all installation instructions and manufacturers instructions.
Additional insulation
For maximum thickness of additional insulation and recommended minimum thermal
resistence values, please refer to the SpeedUp handbook.
Construction
Referring to EN 1264, EN 1991, EN 13967 and local building regulations.
Construction number 521
1
2
3
4
5
/