olympia electronics ZLD-28-EM User manual

Type
User manual
ATTENTION!!!
ZLD-XX/24V/ADR/EM
ADDRESSABLE
EMERGENCY ILLUMINATION SIGNS
FOR CBS
IP40
922504464_09_003 922502862_09_009
45
C: Including inhibiting mode
NOTE: LED= Light Emitting Diode
Z: Central Supply
1: Maintained operation (*)
LABELING EXPLANATION:
Non Maintained operation: The luminaire lights its illumination source, only in mains power
supplys failure.
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by
the mains power supply or not.
G: Internally illuminated safety sign
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies
each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in
official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any
repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing.
Products that have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
European
manufacturers
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr
Non
maintained
NM
Thank you for your trust in our products
Olympia Electronics - European manufacturer
16m 30m 38m
Maintained
Μ
Warranty
The light source of this luminaire is not replaceable when the light source reaches its end of
life the whole luminaire shall be replaced.
Dimensional Drawings (mm) LED Characteristics
MANUFACTURER Olympia Electronics S.A
1111153
8.5-10.5V DC
1200mW 1400mW 1600mW
Non reversible connection between main pcb and led module
o
45 C max. across the board
8.5-10.5V DC 8.7-10.8V DC
1211153 3110123
MODEL NUMBER
VOLTAGE RANGE
CONNECTIONS
NOMINAL POWER
TEMPERATURE (tc)
15-30V DC 20-28V DC15-30V DC
1.6W
70mA
120mA
1.1W 1.3W 1.5W
1.8W
25V
75mA
140mA
1.9W
80mA
160mA
Technical Characteristics
OPERATION VOLTAGE
LUMINAIRE TYPE
LUMINAIRE TYPE
MAX. POWER CONSUMPTION
MAX. OUTPUT VOLTAGE (U-OUT)
SUPPLY CURRENT
WIRE CROSS SECTION
Irated
Prated
2 2
0.3mm - 3.3mm (22-12AWG)
18 white LEDs 21 white LEDs 24 white LEDs
LIGHT SOURCE
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
IP40
16m 30m 38mVIEWING DISTANCE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
o
-30 to 50 C
Aluminum, Acrylic Plate, ABS/PC
990gr. 1480gr.650gr.
290 x 172 x 38 mm 350 x 242 x 38 mm 450 x 295 x 38 mm
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
Up to 95%
3 years
LIGHT SOURCE LUMINOUS FLUX
150lm 175lm 200lm
ELECTRONIC CONTROL GEAR
150/175/200lm
Light output
C G
1
Z
ZLD-28/24V/ADR/EM
ZLD-28/24V/ADR/EM
ZLD-28/24V/ADR/EM: 290x172x38
ZLD-34/24V/ADR/EM
ZLD-34/24V/ADR/EM
ZLD-34/24V/ADR/EM: 350x242x38
ZLD-44/24V/ADR/EM
ZLD-44/24V/ADR/EM
ZLD-44/24V/ADR/EM: 450x295x38
172
290
350
450
242 295
38
36
50
182 100
46
44
70
The controlgear is suitable for LED modules only
Οptional Mounting Methods (Upon Request)
Α-1130
Α-1131
Α-1132
Tube
Α=1m
Α=0.5m
Α=0.25m
Flag mounting A-1133 SET
(only for ZLD-28/24V/ADR/EM,
ZLD-34/24V/ADR/EM)
Hanging mounting
A-1130, A-1131, A-1132 SET
Central
Battery
CBS
Addres-
sable
ADR
1
1
1
Luminaire
Mounting accessories
Manual
1 2 3
Surface mounting on a Wall with A-1134 base
(Included in the package) Single sided luminaire
2. The device must be connected to the mains power supply through a fuse dependent by
the total amount of the line’s power load.
3. Set the luminaire’s address before the installation. The luminaire must be connected
only to the GR-8600 panel via its ADR line.
1. Operations for installation, maintainance or testing must be done by authorized
personel only.
o
These luminaires are for indoors use, only (ta 50 C) where emergency luminaires (CBS) are
needed. Each luminaire must be permanently connected to mains power supply.
ΑΤΤΕΝΤΙΟΝ!!!
4. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type
2x1mm² or any other type, at least equal to its mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is
important to ensure the ΙΡ rating).
General
Package Contents
922504464_09_003 922504464_09_003 922504464_09_003
1
1 1
1
1
1 1
1 1
1
5 6
21
3
7
8
10
9
1
4
12
3 4
Installation Instructions
SET THE ADDRESS
AA
A
A
B
-L
-L
L
L
Connection Diagram
BB
LOCK
Make the connections
Follow step 4 of installation on page 1.
+L
-L
Set the luminaire’s address by using the dip-switches.
Address Address Address
Dipswitch
setting Dipswitch
setting Dipswitch
setting
51
ON
2 3 4 5 6
61
ON
2 3 4 5 6
71
ON
2 3 4 5 6
81
ON
2 3 4 5 6
91
ON
2 3 4 5 6
Address Dipswitch
setting
10 1
ON
2 3 4 5 6
11 1
ON
2 3 4 5 6
12 1
ON
23456
13 1
ON
23456
14 1
ON
23456
15 1
ON
2 3 4 5 6
16 1
ON
23456
17 1
ON
2 3 4 5 6
18 1
ON
23456
Address Dipswitch
setting
19 1
ON
23456
20 1
ON
23456
21 1
ON
2 3 4 5 6
22 1
ON
2 3 4 5 6
23 1
ON
2 3 4 5 6
24 1
ON
2 3 4 5 6
25 1
ON
2 3 4 5 6
26 1
ON
2 3 4 5 6
27 1
ON
2 3 4 5 6
28 1
ON
2 3 4 5 6
29 1
ON
2 3 4 5 6
30 1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
1
ON
2 3 4 5 6
2
1
ON
2 3 4 5 6
3
1
ON
2 3 4 5 6
432 1
ON
23456
31 1
ON
23456
B
B
LOCK
A
A
A
A
  • Page 1 1