Danfoss OFC is a check valve designed for use with Danfoss Turbocor compressors. It features a maximum working pressure of 23 bar / 334 psig and can withstand temperatures ranging from 0°C / 32°F to 90°C / 194°F (short-term up to 100°C / 212°F). The valve is oil-free and has an outlet flange for 3 1/8" copper tube. It also comes with additional check valve springs for different orientations. The OFC valve is easy to install and maintain, making it a reliable choice for various refrigeration and air conditioning applications.

Danfoss OFC is a check valve designed for use with Danfoss Turbocor compressors. It features a maximum working pressure of 23 bar / 334 psig and can withstand temperatures ranging from 0°C / 32°F to 90°C / 194°F (short-term up to 100°C / 212°F). The valve is oil-free and has an outlet flange for 3 1/8" copper tube. It also comes with additional check valve springs for different orientations. The OFC valve is easy to install and maintain, making it a reliable choice for various refrigeration and air conditioning applications.

Installation guide
Check valve
Type OFC
© Danfoss | Climate Solutions | 2021.12 AN391972458172en-000101 | 1
Refrigerant:
For a complete list of approved refrigerants, visit http://store.danfoss.com/ and search for individual code
numbers, where refrigerants are listed as part of product details.
Oil: OFC valve is designed for an oil-free environment
Interface Connections:
Install valve directly on Danfoss Turbocor compressor, picture shown with vertical down installation.
All fasteners and bolts require stainless steel. Bolts with minimum class A2-70.
Media Temperature:
Min. 0 C / 32 F
Max. 90 C / 194 F, short term up to 100 C / 212 F
Contents of accessory box
Outlet flange for 3 1/8 in. copper tube
Outlet flange fasteners
O-ring for outlet flange
O-ring lubrication (2 gram)
Additional check valve springs (2 pcs):
- Yellow spring, for 45 down orientation
- Red spring, for horizontal orientation
Max. Working Pressure:
PS/MWP = 23 bar / 334 psig
020R5432
020R5432
NOTE: refer to check valve orientation options
below
Torque: 38 Nm ± 4 Nm
Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
NOTE: Protection of entire valve including steel
nge is recommended after installation for out-
door use.
089
Імпортер:ТОВ з іі "Данфосс ТОВ" 04080, Київ 80, п/с 168, Україна
© Danfoss | Climate Solutions | 2021.12 2 |
Outlet Flange Brazing:
Place outer ange on evenly cut copper pipe
NOTE: ensure ange is not mounted on main
housing during brazing
When changing check valve spring:
1. Remove check valve insert from main housing
2. Remove check valve head
3. Remove spring and replace with correct color based on in-
tended orientation
4. Replace check valve head and insert
5. Install outlet ange, O-ring and fasteners
Min 5% Ag
Main housing
Check valve insert
Check valve head
NOTE: Use silicone lubricant spray
at O-ring if needed
Check valve spring
Outlet flange,
O-ring and fasteners
NOTE: Apply provided lubrication to
O-ring
Orientation:
NOTE: Check valve spring must be changed when using any
orientation other than vertical downing
AN391972458172en-000101
  • Page 1 1
  • Page 2 2

Danfoss OFC Installation guide

Type
Installation guide

Danfoss OFC is a check valve designed for use with Danfoss Turbocor compressors. It features a maximum working pressure of 23 bar / 334 psig and can withstand temperatures ranging from 0°C / 32°F to 90°C / 194°F (short-term up to 100°C / 212°F). The valve is oil-free and has an outlet flange for 3 1/8" copper tube. It also comes with additional check valve springs for different orientations. The OFC valve is easy to install and maintain, making it a reliable choice for various refrigeration and air conditioning applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI