Yazaki AROACE CH-MG150 Operating Instructions Manual

Category
Water heaters & boilers
Type
Operating Instructions Manual

This manual is also suitable for

GAS-FIRED DOUBLE-EFFECT
ABSORPTION CHILLER-HEATER
FOR YOUR SAFETY
If you smell gas:
1. Open windows (only if installed
indoors)
2. Don’t touch electrical switches
3. Extinguish any open flame
4. DO NOT SMOKE!
5. Immediately call your gas supplier
FOR YOUR SAFETY
Do not store or use gasoline or
other flammable vapors and
liquids in the vicinity of this or any
other equipment.
CONTENTS
GENERAL Page
ABSORPTION PRINCIPLE 2
COOLING OPERATION 3
HEATING OPERATION 4
CONTROLS
GENERAL INFORMATION 5
CONTROL ADJUSTMENTS 8
CONTROL SEQUENCE 12
OPERATION
COOLING 13
PRECAUTIONS 13
HEATING 13
REMOTE CONTROL 13
Page
SAFETY CONTROLS 13
WINTER SHUTDOWN 14
MAINTENANCE
GENERAL INFORMATION 14
MAINTENCE SCHEDULE 14
ROUTINE MAINTENANCE 15
EVACUATION OVERVIEW 15
CHEMICAL MAINTENANCE 17
WINTERIZING 17
TROUBLESHOOTING 17
WATER QUALITY 18
ERROR CODES 19
OPERATING INSTRUCTIONS
CH-MG150
CH-MG200
2
This product is a gas-fired absorption unit which provides
chilled water for cooling or hot water for heating in central
plant-type air conditioning systems. Units with nominal
refrigeration capacities of 150 and 200 tons are complete
with operating and safety controls. The chiller-heater is fitted
with a low NOx burner, automatic spark ignition systems,
power combustion blower and proportional firing control.
When this equipment has been applied correctly,
installed in accordance with Yazaki INSTALLATION
INSTRUCTIONS (supplied with the chiller-heater), and with
proper maintenance on the chiller-heater itself and
accompanying support items such as pumps, cooling tower,
etc., it can provide many years of trouble free operation.
GENERAL
These instructions are intended to
acquaint the Owner/End User with the
operation and general maintenance
requirements of Yazaki Gas-Fired
Double-Effect Absorption Chiller-Heater
units.
Please read ALL instructions carefully
and observe precautions. Failure to
operate and properly maintain this
equipment in accordance with the
OPERATING INSTRUCTIONS may
affect the equipment performance and
product Warranty.
If the equipment does not operate as
expected, check the Troubleshooting
Guide in these instructions BEFORE
calling your Yazaki Authorized Service
Provider (ASP). This approach will not
only save cost but also helps to avoid
any unnecessary down time.
THE ABSORPTION PRINCIPLE
Yazaki absorption chiller-heaters use
a solution of lithium bromide and water,
under vacuum, as the working fluid.
Water is the refrigerant and lithium
bromide is the absorbent. During cooling
operation, refrigerant liquid boils under
the influence of a deep vacuum in the
evaporator and creates a refrigerating
effect which removes heat from the
chilled water circuit.
The double-effect absorption cycle
has two generators one heated by a
gas burner and another heated by
superheated refrigerant vapor. The
resulting refrigerant is passed through to
the condenser, and is then metered into
the evaporator. Lithium bromide solution
leaving the generators flows into the
absorber.
Heat from the cycle is removed by
cooling water flowing inside the
condenser and absorber tubing bundles.
Heat from the cooling water is rejected
most typically to a cooling tower, but may
also be rejected by alternative methods,
including ground loops.
3
COOLING OPERATION
High-Temperature Generator (HGE)
The gas burner heats a dilute lithium
bromide solution in the High-
Temperature Generator resulting in a
release of superheated refrigerant vapor.
The dilute solution becomes more
concentrated due to this release.
Gravity, temperature, and pressure
differences push the more concentrated
solution through Heat Exchangers to
recycle heat before the concentrated
solution is sent to the Absorber (ABS).
After release, the superheated
refrigerant vapor flows through the Low-
Temperature Generator (LGE) tubing
bundle and is used as the heat source for
the dilute solution that the LGE contains.
Most, if not all, of the refrigerant vapor
will condense into liquid refrigerant
during this process. Ultimately, this
tubing dumps the liquid refrigerant into
the Condenser (COND).
Low-Temperature Generator (LGE)
After release, the superheated
refrigerant vapor heats dilute lithium
bromide solution in the Low-Temperature
Generator. The refrigerant vapor
liberated from this solution flows into the
Condenser while the lithium bromide
solution becomes more concentrated.
Gravity, temperature, and pressure
differences push this more concentrated
solution through Heat Exchangers to
recycle heat before the concentrated
solution is sent to the Absorber.
Condenser (COND)
In the Condenser, refrigerant vapor is
condensed on the outer surface of the
condenser tubing bundle. Latent heat is
removed by the cooling water that flows
inside this tubing bundle. The heat
absorbed by the cooling water is rejected
to a cooling tower or alternative system.
The liquid refrigerant that drips off the
tubing bundle joins the liquid refrigerant
that resulted from the operation of the
LGE and accumulates in the condenser
sump. Liquid refrigerant is routed from
the condenser sump through an
electronic expansion valve which meters
the liquid refrigerant as required into the
Evaporator (EVA).
Evaporator (EVA)
In the Evaporator, liquid refrigerant is
exposed to a substantially deeper
vacuum than in the Condenser due to the
influence of the Absorber. As the liquid
refrigerant flows over the surface of the
Evaporator tubing bundle, it boils and
removes heat from the chilled water
flowing inside the Evaporator tubing
bundle. The heat removed from the
chilled water circuit is equal to the latent
heat of the refrigerant, roughly 1000 BTU
per pound of liquid refrigerant boiling into
refrigerant vapor.
Absorber (ABS)
The Evaporator and the Absorber
share the same space. A deep vacuum
in the ABS is maintained by the affinity of
the concentrated solution for refrigerant
vapor. The concentrated solution flows
over the outside of the Absorber tubing
bundle where it is cooled by the cooling
water flowing inside the Absorber tubing
bundle. When the concentrated solution
is cooled, it develops an even greater
affinity for the refrigerant vapor. The
heat absorbed by the cooling water is
rejected to a cooling tower or alternative
system.
The deep level of vacuum in the ABS
section is maintained by the action of the
concentrated solution absorbing the
refrigerant vapor that is being generated
by the EVA during its normal operation.
4
This action dilutes the concentrated
solution back to the same concentration
level as it was when the cycle began.
The dilute solution gathers in the
Absorber sump before being pumped
back into the Generators to start the
cycle anew.
Fig. 1 DOUBLE-EFFECT ABSORPTION CYCLE (COOLING)
HEATING OPERATION
High-Temperature Generator (HGE)
Dilute lithium bromide solution is heated
in the HGE by the gas burner in the
same manner as in the cooling cycle.
The solution boils vigorously, releasing
superheated refrigerant vapor and
leaving a more concentrated solution.
The refrigerant vapor flows through a
changeover valve into the Evaporator
section. The concentrated solution flows
through another changeover valve into
the Absorber sump.
Low-Temperature Generator (LGE)
Although solution does flow through the
LGE, since the superheated refrigerant
vapor is not flowing in any meaningful
amount through the LGE, the solution
does not release any refrigerant vapor
and the solution simply flows back into
the Absorber sump in essentially a still-
diluted state. The lack of this generator
operation in heating mode is why the
heating capacity is lower than the cooling
capacity in these chiller-heaters.
5
HEATING OPERATION
Evaporator (EVA)
Superheated refrigerant vapor
condenses on the outer surface of the
Evaporator tubing bundle. Heat equal to
the latent heat of the refrigerant is
transferred into the hot water circuit. The
liquid refrigerant that condensed on the
outer surface simply drips off into the
Absorber sump, diluting the solution back
to the same concentration level as when
it started the cycle.
Absorber (ABS)
Liquid refrigerant that condensed on the
outer surface of the Evaporator tubing
bundle drips into the Absorber sump.
Concentrated solution from the HGE and
dilute solution cycled through the LGE
also ends up in the Absorber sump. The
joining of all the liquids results in diluting
the solution back to the state at which it
began the cycle. This diluted solution is
then pumped to the Generators to begin
the cycle anew.
Fig. 2 DOUBLE-EFFECT ABSORPTION CYCLE (HEATING)
6
CONTROLS
GENERAL INFORMATION
A control panel, shown in Fig. 3, is
built into each absorption chiller-heater
and is located on the front of the control
box. The control box is located behind
the right-hand service door, as shown in
Fig. 4. After inspecting the control panel
or changing the mode of operation, make
sure that the front panel is latched and
locked in order to prevent rain from
entering the cabinet and damaging the
controls. This will also help to prevent
unauthorized tampering with controls and
settings.
The chiller-heater may also be
supervised and controlled in a limited
manner by Building Automation Systems
(BAS, BMS) when Remote Operation is
engaged. Additional controls and
interlocks may be required in some
instances. These controls and their
functions can be explained by your
Yazaki Authorized Service Provider.
Once COOLING or HEATING
operation is selected and the unit has
started, the chiller-heater will function
automatically and remain in operation for
as long as there is a demand for chilled
or hot water. The burner modulates the
Generator heat input in response to the
leaving chilled/hot water temperature.
When the chilled water temperature
demand is satisfied, the solution pump
automatically changes to Dilution Mode
and the cooling water pump demand
stops after a minimum of 4 minutes
additional time.
Fig. 3 Chiller-Heater Control Panel
7
GENERAL INFORMATION
Fig. 4
SOLUTION PUMP CONTROL
The VFD Solution Pump is controlled
by a Hitachi VFD Controller. This
controller has been set up at the factory
and SHOULD NOT BE ADJUSTED!
Universal replacements are NOT
recommended. Only use OEM parts for
the solution pump and controller.
Fig. 5 Hitachi VFD Controller
Control Panel
located behind
this panel in this
location.
Evacuation Service
Valves A and B are
located behind this
panel in this location.
8
CONTROL ADJUSTMENTS
The chiller-heater is normally operated
from the control panel behind the right
access door. If it is necessary to open
the control box for troubleshooting,
observe all safety warnings on the chiller-
heater and in these instructions. Only
qualified and trained personnel should
have access to the live electrical parts
inside the chiller-heater. Failure to
observe the safety warnings can
result in personal injury, death, and/or
damage to property.
Fig. 6 Control Box (Opened)
9
CONTROL ADJUSTMENTS
The ACT5 Maintenance Checker
plugs into the Main CPU Board, shown in
Fig. 8, and is used in many functions,
including choosing the leaving chilled/hot
water temperature set points.
This board also has the Mode Setting
Switch. This switch must be positioned
to the left whenever the unit is to be in
normal operating condition. Position this
switch to the right when adjusting the
burner. Position this switch to the middle
when the unit is to sit dormant and
unresponsive, but with power applied to
it. The Unit Number Setting Dip Switch is
only used in conjunction with the optional
AroTrend Remote Monitoring or an
optional LON Adapter. If not being
monitored, this dial switch must be set to
“0” or “F”.
Fig. 8 Main CPU Board
10
CONTROL ADJUSTMENTS
The leaving chilled water and hot
water temperature controls are set at the
factory to the Standard Specifications Set
Points, which are a cooling set point of
44.6°F (7°C) and a heating set point of
140.0°F (60°C). A Yazaki Authorized
Service Provider can adjust these set
points using the ACT5 Maintenance
Checker. The cooling set point is
adjustable from 41°F (5°C) to 53.6°F
(12°C). The heating set point is
adjustable from 104.0°F (40°C) to 145.4°F
(63°C).
The CH-MG Series has an Economy
Mode feature as well that can be
controlled by the Building Management
System. Economy Mode functions in
much the same way as night set-back.
When engaged, the cooling set point will
rise by 5.4°F (3°C) and the heating set
point will fall by 9°F (5°C). Dis-engaging
the Economy Mode will immediately
restore the cooling and heating set points
back to their original values.
Fig. 7 ACT5 Maintenance Checker
Adjusting the chilled and hot water set
points can only be done using the ACT5.
Using a standard CAT5 cable (one was
provided from the factory), connect the
ACT5 to the Main CPU Board located in
the upper right of the control box. There
is a jack in the upper middle of the CPU
Board (See Figure 8) that is for use with the
ACT5.
There is also an identical jack on the
Sub-Control Board located in the top left
corner of the control box. This board’s
jack is not functional and should not be
used.
To adjust the chilled and hot water set
points:
1. On the ACT5, use the “Λ” and “V”
buttons to move the cursor to the line
“2. Unit data set” and press “ENTER”.
2. Then use the “Λ” and “V” buttons to
move the cursor to the line “B2 CB
Set” and press “ENTER”.
3. Use the “◄” and “►” buttons to reach
the menu displaying data points 13-16.
4. Use the “Λ”, “V”, “<”, and “>” buttons to
move the cursor to temperature
numbers of data point 14 to change
the cooling set point, or data point 15
to change the heating set point.
5. Once highlighting the block to be
changed, use the “+” and -“ buttons to
scroll through the available values until
the desired value is displayed.
6. Press “ENTER” to save the new
setting.
7. Press and hold the “◄” for longer than
one full second to back out of the
menu, or simply unplug the ACT5 if it
is no longer needed for other
functions.
11
CONTROL ADJUSTMENTS
To enable the Economy Mode, locate
terminals TB1-75 and TB1-76 (See Fig. 9)
on the I/O Board, located at the middle
left in the control box. The board sends
voltage out on TB1-75, so no external or
field-supplied power should be applied to
the circuit or else damage to the board
could result.
To engage Economy Mode, close a
circuit between TB1-75 and TB1-76.
When that circuit is closed, the Main
CPU Board logic will automatically apply
a modifier to the temperature set point
data in memory. When the circuit is
open, no modifier will be applied.
Most often, a relay with dry contacts
that is controlled by the BMS is used to
control Economy Mode. However, a
timer, light sensor, or a simple toggle
switch could also be used to make or
break this circuit.
Fig. 9 I/O Board
12
CONTROL SEQUENCE
A built-in microprocessor in the chiller-
heater controls the external pump
demand signals in response to the
cooling and heating load. The operating
sequence of each pump and the cooling
tower fan after start-up, during normal
operation, and after a normal stop or
abnormal shut down is shown in Fig. 10.
It is important that the chiller-heater have
control over the pumps to allow for
controlled shut down under normal and
abnormal conditions.
Running the chilled water pump at all
times is discouraged as the chiller-heater
logic will expect to see the flow switch
open when the “P” dry contacts are
opened. If it does not open, the chiller
assumes the flow switch has failed and
will generate error code E016.
Fig. 10 General Control Sequence
CP = Cooling Water Pump Demand Relay
CTF = Cooling Tower Fan Demand Relay
P = Chilled/Hot Water Pump Demand Relay
13
OPERATION
COOLING
1. Select “ON” on the DIRECT
OPERATION section of the control
panel.
2. Select “COOLING” on the MODE
SELECT section of the control panel.
Cooling operation will commence after
all self-check functions have completed.
This can take as long as 5 minutes so do
not be alarmed if the unit does not seem
to respond immediately. If the unit is
being switched over from HEATING
mode, there is an enforced 30-minute
delay period before COOLING mode will
engage.
PRECAUTIONS
1. Ensure that all AUTO-OFF-MANUAL
switches for external pumps and the
cooling tower fan are set in the AUTO
position during normal operation. The
chiller-heater is designed to
automatically control the chilled/hot
water pump, cooling water pump, and
cooling tower fan signals as it
requires.
2. At the beginning of the cooling
season, clean and refill the cooling
tower with fresh water. Check
strainers for debris and spray nozzles
for proper operation.
3. During the heating season, the cooling
tower and cooling water circuit should
be drained in order to help prevent
freezing and scaling in the Absorber
and Condenser tubing bundles.
4. When two or more absorption chiller-
heaters are installed in parallel, set all
units to the same operating mode.
HEATING
1. Select “ON” on the DIRECT
OPERATION section of the control
panel.
2. Select “HEATING” on the MODE
SELECT section of the control panel.
Heating operation will commence after
all self-check functions have completed.
This can take as long as 5 minutes so do
not be alarmed if the unit does not seem
to respond immediately. If the unit is
being switched over from COOLING
mode, there is an enforced 30-minute
delay period before HEATING mode will
engage.
REMOTE CONTROL
In order to respond to BMS signals,
the chiller-heater must be set to remote
operation. Simply press the “REMOTE”
button on the REMOTE OPERATION
section of the control panel. The LED
will illuminate on the “REMOTE” button
to indicate remote operation has been
engaged.
SAFETY CONTROLS
Safety and limit controls monitor
critical operating conditions in the chiller-
heater and may shut down the unit when
abnormal conditions occur. Not all
abnormal conditions are harmful to the
chiller-heater, therefore, the chiller-
heater may not always shut down when
an error code is displayed.
An Error Code will be displayed when
an abnormal condition arises. This error
14
code will be displayed by LEDS located
at the top left of the control panel. A list
of error codes and their meanings is
shown in Table 2 at the back of this
manual.
Some Error Codes will automatically
reset themselves once the abnormal
condition clears. Others may require a
manual reset by pressing the “RESET”
button on the control panel. Some
manual reset codes will not clear until
certain conditions are met, so if the Error
Code does not clear or the chiller-heater
does not restart, contact your Yazaki
Authorized Service Provider (ASP).
WINTER SHUT DOWN
If a chiller-heater is only used in the
cooling mode and is to be shut down for
the winter, it is necessary to run the
chiller-heater in Heat mode for a
minimum of 30 minutes in order to
properly return all fluids to the bottom of
the unit and to prepare the unit for long
term shutdown. Without running in Heat
mode, some water will be trapped in
upper portions of the chiller-heater and
could potentially damage the unit should
it freeze in the winter conditions.
See the Service Manual for detailed
information on proper Winter Shut Down.
MAINTENANCE
GENERAL INFORMATION
ALL MAINTENANCE SHOULD BE
PERFORMED BY SKILLED,
EXPERIENCED PERSONNEL. Your
Yazaki Authorized Service Provider
(ASP) can help you establish a standard
maintenance procedure.
For your safety, keep the area around
the equipment clear and free of
combustible materials, gasoline, and
other flammable substances. DO NOT
obstruct service access to the
equipment.
MAINTENANCE SCHEDULE
Every 6 months:
Evacuation
Inhibitor Check (if required)
Combustion Analysis
Gas Pressure Check
Flow Rate Check
Palladium Cell Heater Check
Verify Flow Switch Operation
Every 12 months:
Flame Rod Replacement
Igniter Rod Replacement
Every 3 years:
Generator Internal Inspection
Average Cycle for Inhibitor
Replenishment
ROUTINE MAINTENANCE
Routine maintenance should be
provided throughout the life of the
equipment in order to ensure satisfactory
operation and performance.
During the warranty period, an ASP
must be engaged to provide routine
maintenance at the beginning of each
cooling season (spring changeover) and
heating season (fall changeover). When
the chiller-heater is used for process
cooling or heavy load operation, it may
be necessary to schedule additional
service visits to evacuate non-
condensable gasses from the vacuum
section.
Be aware that during the first few
months of operation, non-condensable
gases may accumulate at a greater rate
than expected as the inhibitor coating in
the unit finishes forming. However, after
approximately 3 months, the formation of
non-condensable gases should decrease
to the normal expected rates.
Each routine maintenance item is
covered in detail, many in step-by-step
detail, in Section 5 of the Service
Manual. What is provided here is a brief
summary of what the Service Manual
covers.
EVACUATION OVERVIEW
Arguably the most important aspect of
maintenance for the chiller-heater is
maintaining a proper level of vacuum.
Evacuation is performed at the front of
the machine. The evacuation service
valves are referred to as Service Valve A
(upper) and Service Valve B (lower).
Refer to Fig. 4 for detail on where these
valves are located at the front of the unit.
The evacuation service valves are
back-seating access valves similar to
those used throughout the refrigeration
industry. The stem has a 10mm square
head. The stem secures a copper seal
to a steel seat inside the valve. Do not
over-torque this valve or else the seal
can become damaged and compromise
vacuum integrity.
Yazaki offers a torque wrench (P/N
N7510) specifically for use with this service
valve.
A number of precautions should be
observed at all times during evacuation.
Key points are:
*** Great care must be taken to
ensure that no oil enters the Yazaki
chiller-heater! Permanent damage
could result from even a small amount
of oil being introduced into the
vacuum section! ***
Never leave a vacuum pump running
unattended. Power loss could allow
the chiller-heater vacuum section to
suck oil out of the pump in a matter of
minutes.
Never have the Service Valve open
unless the vacuum pump is running
and the integrity of the vacuum lines
between the valve and the pump has
been verified as tight.
Never have the vacuum pump
discharge tube in the water bucket
unless the vacuum pump is running.
The vacuum pump could suck water
from the bucket and contaminate the
oil charge.
Never pull a vacuum when the unit is
running in Heat mode. Only pull a
vacuum in Off or Cool modes.
16
Always start with a fresh oil charge in
the vacuum pump.
Always use a liquid trap or collection
flask.
Always use a vacuum gauge to verify
the level of vacuum achieved. Run
time has almost nothing to do with the
level of vacuum achieved.
Never pull a vacuum if the ACT5
Maintenance Checker indicates an LT
temperature exceeding 90°F (32°C).
Never pull an extended vacuum
(exceeding a few hours). If such seems
to be necessary, there is likely to be
something wrong with the vacuum
pump or the oil has been
contaminated with moisture inherently
found inside the chiller-heater vacuum
section.
Use only dual-stage, deep vacuum
pumps. Typical refrigeration vacuum
pumps may not perform well on a vessel
as large as the chiller-heater vacuum
section. Just because the vacuum pump
has stopped producing bubbles in the
water bucket does NOT mean the
vacuum level is adequate. A digital
vacuum gauge MUST be used in order to
determine the true level of vacuum
achieved.
The desired level of vacuum on a
machine that is not running would be
less than 2000 microns (<2mmHg), with
less than 1000 microns (<1mmHg)
preferred. On a machine actively
running in Cool mode (burner engaged),
the desired level of vacuum is 5000
microns (5mmHg), no less. Any lower
than 5000 microns (5mmHg) on a running
machine will cause the vacuum pump to
remove an extraordinary amount of
refrigerant vapor (water).
A step-by-step, detailed evacuation
method is provided in Section 5 of the
Service Manual. The general evacuation
assembly setup is displayed in Fig. 11.
Fig. 11 General Evacuation Assembly Setup
17
CHEMICAL MAINTENANCE
It is not necessary to perform regular
chemical maintenance on the Yazaki
chiller-heater itself. The chemical
balance has been established in the
factory during run testing. Normally, the
only chemical that must be maintained is
the inhibitor charge. By capturing non-
condensable gases, as shown in Fig. 12,
comparison can be made to determine if
the normal hydrogen byproduct is being
produced at anticipated rates. If more
hydrogen is being produced than
anticipated, a maintenance inhibitor
charge may need to be introduced into
the machine by the ASP. An inhibitor
charge is typically needed every three
years in Yazaki gas-fired chiller-heaters.
Fig. 12 Capturing Gases
WINTERIZING
When equipment is located outdoors
in climates subject to freezing, cooling
water must be drained from the chiller-
heater, piping, and cooling tower at the
end of the cooling season. Use of glycol
may also be permissible. Consult the
Service Manual for details concerning
Anti-Freeze Strategies.
When draining a fluid loop, make sure
to blow through the emptied loop with
compressed air (or similar). Blow in both
directions through the loop so as to blow
out as much of the residual fluid as
possible. This is to help prevent
potential tube damage during freezing
conditions.
TROUBLESHOOTING
SYMPTOM: Chiller-Heater does not operate.
Possible Cause
REMEDY
No High Voltage
Check the LED for the Power indication on the Control Panel. If it is not illuminated, check the
main power disconnect, fuses, and breakers.
Solution Pump Not Running
Check for illumination of the "FAILURE" LED in the row of indicator LEDs for the Solution
Pump. If lit, check the VFD Controller.
Manual Reset Device Tripped
Check the error codes using the display on the front panel or the ACT5 Maintenance Checker
to identify which device is tripped.
Unit Overheated
Check combustion, gas pressure, and vent assembly for conditions that cause over-firing or
prevent proper venting. Check the VFD controller for the Solution Pump. Improper mass flow
through the machine can cause overheating symptoms.
SYMPTOM: Poor cooling capacity.
Possible Cause
REMEDY
Poor Vacuum
Evacuate the machine per normal maintenance procedure.
High Inlet Cooling Water
Temperature
Check the cooling tower fan. Check the cooling tower fluid level.
Low Cooling Water Flow Rate
Check the cooling tower sump and cooling water circuit strainers.
Condenser/Absorber Fouling,
Scale Buildup
Check the cooling water circuit strainers. It may be necessary to drain the cooling water circuit
and open the inspection doors on the chiller-heater condenser and absorber for a visual
confirmation.
18
WATER QUALITY
It is the responsibility of the Owner or
End User to have the cooling water
analyzed and chemically treated as often
as is necessary so that it conforms to the
limits shown in Table 1. The water
quality in the chilled/hot water and the
cooling water circuits should not exceed
the following limits:
Note:
1. Items shown in the Trend column: An “Omark indicates the potential issue should this line item go
out of acceptable range.
2. When water temperature rises above 104°F (40°C), the tendency for corrosion rises remarkably. As
such, there may arise a need for additional corrosion protection measures such as buffers and
inhibitors.
3. For closed-loop cooling towers, use the Hot Water column data in the Circulating Water chart instead
of the Cooling Water column data. For make-up water, use the Chilled Water column data instead of
the Cooling Water column data.
Table 1 Water Quality Charts
19
ERROR CODES
Error
Code
Error Description
1
DCP power error
2
DCP communication line short
3
DCP communication line noise
4
Accessory error
5
Chilled/hot water pump interlock
error
6
Cooling water pump interlock
error
7
Cooling tower fan interlock error
8
Solution pump error
9
Generator (HGE) over heat error
10
Generator (HGE) temp error
12
Generator (HGE) solution level
error
13
WTO sensor error
16
Flow switch error (FS1)
18
Seismic switch error
19
Generator (HGE) over heat alarm
20
Cooling water scale alarm
21
Cooling water scale error
24
Freeze protection error
25
High cooling water temperature
26
Generator (HGE) over heat in
heating mode
27
Chilled water flow switch error
28
Cooling water flow switch error
29
CTO sensor error
30
Exhaust gas temperature error
31
Generator (HGE) pressure error
32
GP sensor error
33
CTI sensor error
35
Aspirator and exhaust fan error
36
CND sensor error
40
Loss of cooling capacity
43
Low cooling water temperature
44
Changeover valve error
52
Combustion system error
72
LT sensor error
77
Generator (HGE) pressure sensor
error
88
Corpus pressure error
93
Model setting error
94
Check mode neglect
95
Data initial clear
96
Extended Error Code Alert
101
WTI sensor error
105
Low chilled/hot water temp alert
Table 2 Error Codes
YAZAKI AUTHORIZED SERVICE PROVIDER
For information concerning service, operation
or technical assistance, please contact your
Yazaki Authorized Service Provider or the following:
YAZAKI ENERGY SYSTEMS, INC.
701 E PLANO PKWY, SUITE 305
PLANO, TEXAS
75074-6700
Phone: 469-229-5443
Fax: 469-229-5448
Email: yazaki@yazakienergy.com
Web: www.yazakienergy.com
This symbol on the product’s nameplate means it is listed by
UNDERWRITERS LABORATORIES, INC.
Yazaki reserves the right to discontinue, or change at any time,
specifications or designs without notice and without incurring obligations.
MGUL-OI-1C2-0813
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Yazaki AROACE CH-MG150 Operating Instructions Manual

Category
Water heaters & boilers
Type
Operating Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI