Laars MT2H0750NACK1CJX Installation guide

Type
Installation guide

This manual is also suitable for

Installation and Operation Instructions Document 1211K
H2329100K
Hydronic Boiler
Model MT2H
Volume Water Heater
Model MT2V
Sizes 500–2000 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty. For indoor installations, as an additional
measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide detectors in the
vicinity of this appliance and in any adjacent occupied spaces.
Installation and Operation Instructions for
MIGHTY THERM2
®
WARNING
If the information in this manual is not followed
exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
re department.
Installation and service must be performed by
a qualied installer, service agency, or gas supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute blessure
ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres
vapeurs ou liquides inammables dans le voisinage
de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter d’allumer d’appareils.
Ne touchez à aucun interrupteur. Ne pas vous servir des
téléphones dansle bâtiment vous êtes.
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du
fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualié ou par le
fournisseur de gaz.
LAARS Heating Systems
Table of Contents
i
SECTION 1 General Information
1.A Introduction ....................................................... 1
1.B Warranty ........................................................... 1
1.C Model Identication ........................................... 2
1.D Safety Notes ..................................................... 3
1.E Locating the unit ............................................... 5
1.F Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s) ....................... 5
1.G Locating Pump-Mounted Boiler
with Respect to Return/Supply Header ............ 5
1.H Locating the Unit for Correct Horizontal
Vent/Ducted Air Distance from Outside Wall .... 5
1.I Dimensions ....................................................... 6
SECTION 2 Venting and Combustion Air
2.A Combustion Air ................................................. 8
2.A.1 Combustion Air From Room ............................. 8
2.A.2 Intake Combustion Air ...................................... 8
2.B Venting .............................................................. 8
2.B.1 Vent Categories ................................................ 8
2.B.2 Category I Vent ................................................. 9
2.B.3 Common Venting Systems ............................... 9
2.B.4 Category III Vent ............................................... 9
2.C Locating Vent & Combustion Air Terminals ..... 10
2.C.1 Side Wall Vent Terminal .................................. 10
2.C.2 Side Wall Combustion Air Terminal ................. 10
2.C.3 Vertical Vent Terminal ..................................... 10
2.C.4 Vertical Combustion Air Terminal .................... 12
2.D Common Vent Test — Boilers ......................... 12
2.E Vent Terminals for Outdoor Units .................... 13
SECTION 3 Gas Supply and Piping
3.A Gas Supply and Piping ................................... 14
SECTION 4 Water Connections
4.A Boilers. .......................................................... 15
4.A.1 Heating System Piping:
Hot Supply Connections — Boiler .................. 15
4.A.2 Cold Water Make-Up — Boiler ....................... 15
4.A.3 Water Flow Requirements — Boiler ............... 15
4.A.4 Freeze Protection — Boiler ............................ 16
4.B Water Heater .................................................. 16
4.B.1 Water System Piping — Water Heater ........... 16
4.B.2 Hot Water Supply Piping — Water Heater ...... 16
4.B.3 Water Flow Requirements — Water Heater ... 16
4.B.4 Combined Water Heating (potable)
and Space Heating — Water Heater ............. 17
4.B.5 Freeze Protection – Water Heater .................. 17
SECTION 5 Electrical Connections
5.A Main Power ..................................................... 23
5.A.1 Changing Single Circuit to Two Circuits ......... 23
6.H.1 Field Wiring ..................................................... 28
6.I External Staging Control Wiring ..................... 28
SECTION 6 Operating Instructions
6.A Sequence of Operation ................................... 28
6.B Filling the System ........................................... 29
6.C Operating Temperature Control ...................... 30
6.D External Boiler Operations .............................. 30
6.E Limit Controls .................................................. 30
6.F Operating the Burner and Set Up ................... 30
6.F.1 Set Up for 0 to 2500 Feet Altitude .................. 30
6.F.2 High Altitude Adjustment and Set Up .............. 31
6.G Shutting Down the Unit ................................... 31
6.H To Restart the Unit .......................................... 31
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
ii
SECTION 7 Maintenance
7.A System Maintenance ...................................... 32
7.B Maintenance and Component Description ..... 32
7.B.1 Burners ........................................................... 32
7.B.2 Filter ................................................................ 32
7.B.3 Gas Valves ..................................................... 32
7.B.4 Manual Reset High Limit Control .................... 32
7.B.5 Temperature Control ....................................... 33
7.B.6 Ignition Controls .............................................. 33
7.B.7 Ignitors/Sensor ............................................... 33
7.B.8 Transformer .................................................... 33
7.B.9 Blowers ........................................................... 33
7.B.10 Flow Switch ................................................... 33
7.B.11 Heat Exchanger Coil ..................................... 33
SECTION 8 Trouble Shooting
8.A Resolving Lockouts ........................................ 34
8.B Delayed Ignition — Possible Causes ............. 34
8.C Short Cycling — Boiler ................................... 35
8.D Short Cycling — Water Heater ....................... 35
8.E High Gas Consumption .................................. 35
SECTION 9 Replacement Parts
9.A General Information ........................................ 35
9.B Parts List ........................................................ 35
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 1
USING THIS MANUAL – Because these Boilers
and Water Heaters are identical appliances, with the
exception of materials of manufacture, labels and
ultimate use and application, this manual provides
information for the proper installation, operation and
maintenance of both products. Where dierences
exist between their application and their operation,
the sections pertinent to only one or the other will be
so identied.
In the Commonwealth of Massachusetts, this unit
must be installed by a licensed plumber or gas tter.
This manual provides information necessary for
the installation, operation, and maintenance of the
Laars Heating Systems Mighty Therm2 commerical
hydronic boilers and volume water heaters (including
the Low Temp units). Read this manual carefully before
installation.
All application and installation procedures should
be reviewed completely before proceeding with
the installation. Consult the factory, or local factory
representative, with any issues or questions regarding
this equipment. Experience has shown that most
operating issues are caused by improper installation.
The Mighty Therm2 is protected against over
pressurization. A pressure relief valve is tted to all units.
It is installed on the outlet header, at the water outlet of
the unit
Laars Heating Systems Mighty Therm2s are
covered by a limited warranty. Owners should submit
online warranty registration at www.Laars.com.
All warranty claims must be made to an authorized
Laars Heating Systems representative, directly to
Customer Service, or online at www.Laars.com.
Claims must include the serial number and model
number (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.A Introduction
1.B Warranty
NOTE: Throughout the content of this
manual, the Mighty Therm2 will be referred to
as a ‘unit’. unit = MightyTherm2
SECTION 1 General Information
GAS
VENTINLET
HYDRONIC SUPPLY
AND RETURN
The Pump and the Hydronic Supply/Return are reversible.
GAS
PUMP
LAARS Heating Systems
Page 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M T 2 A C K 1
SERIES
M T 2
SIZE
0 5 0 0
0 7 5 0
1 0 0 0
1 2 5 0
1 5 0 0
1 7 5 0
2 0 0 0
REVISION
1 - FIRST
REV
OPTIONS
CODE
X - STD
J - CSD-1,
GAP,
FM
USAGE
H - HYDRONIC
V - VOLUME WATER
FUEL
N - NATURAL
P - PROPANE
PUMP
OPTIONS
X - NO PUMP
H - PUMP MOUNTED
TACO, HARD
WATER (MT2V)
N - PUMP MOUNTED,
TACO, NORMAL
WATER (MT2V, MT2H)
S - PUMP MTD, TACO
SOFT WATER PUMP
(MT2V)
C - PUMP MOUNTED
B&G, HARD
WATER (MT2V)
B - PUMP MOUNTED,
B&G, NORMAL
WATER (MT2V, MT2H)
D - PUMP MTD, B&G
SOFT WATER PUMP
(MT2V)
ALTITUDE
A - 0' – 10,000'
LOCATION
C - INDOOR/
OUTDOOR
FIRING
MODE
K - 2-Stage
HEAT EXCHANGER
B - GLASS-LINED CAST IRON/
COPP/BRZ TRIM (std.MT2V)
C - GLASS-LINED CASTIRON/
COPP. (std.MT2H, n/a MT2V)
N - GLASS-LINED CAST IRON/
CU-NICKEL (n/a MT2V)
P - GLASS-LINED CAST IRON /
CU-NICKEL, BRZ TRIM
HLW STAMP (MT2V only)
2 - GLASS-LINED CAST IRON/
COPPER / BRZ TRIM
5 - GLASS-LINED CAST IRON/
CU-NICKEL / BRZ TRIM
Consult the rating plate on the unit.
The following information describes the
model number structure.
1-3 Model Series Designation
M T 2 = Mighty Therm2
4 Usage
H = Hydronic
V = Volume Water
5-8 Size
0 5 0 0 = 500,000 BTU/h input
0 7 5 0 = 750,000 BTU/h input
1 0 0 0 = 999,000 BTU/h input
1 2 5 0 = 1,250,000 BTU/h input
1 5 0 0 = 1,500,000 BTU/h input
1 7 5 0 = 1,750,000 BTU/h input
2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas
P = Propane
10 Altitude
A = 0–10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
K = Two-stage
13 Revision
1 = First version of design
14 Heat Exchanger
B = Glass-lined cast iron / copper / bronze trim
(std. on water heaters)
C = Glass-lined cast iron / copper
(std. on boilers, n/a on water heaters)
N = Glass-lined cast iron / cupro-nickel
(n/a on water heaters)
P = Glass-lined cast iron / cu-nickel / bronze trim
15 Option Code
X = Standard unit
J = CSD-1, FM, IRI, IL
16 Pump Options
X = No Pump
H = Pump mounted MT2V, TACO, hard water pump
N = Pump mounted (any), TACO, normal water pump
S = Pump mounted MT2V, TACO, soft water pump
C = Pump mounted MT2V, B&G, hard water pump
B = Pump mounted (any), B&G, normal water pump
D = Pump mounted MT2V, B&G, soft water pump
1.C Model Identication
(Model Nomenclature)
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 3
1.D Safety Notes
WARNING
Carbon Monoxide Hazard
Improper adjustment of the burners may lead to poor
combustion quality, increasing the amount of carbon
monoxide produced. Excessive carbon monoxide
levels may lead to personal injury or death.
WARNING
This unit must be installed in accordance with the
procedures detailed in this manual, or the manufacturers
warranty will be voided. The installation must conform
to the requirements of the local jurisdiction having
authority, and, in the United States, to the latest edition
of the National Fuel Gas Code, ANSI Z223.1/NFPA54.
In Canada, the installation must conform to the latest
edition of CSA B149.1 Natural Gas and Propane Gas
Installation Code, and/or local codes. Where required
by the authority having jurisdiction, the installation of
these units must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1. Any modifi cations to the boiler, its
gas controls, or wiring may void the warranty. If eld
conditions require modifi cations, consult the factory
representative before initiating such modifi cations.
WARNING
Water temperature over 125°F (52°C) can cause
severe burns instantly or death from scalds.
Children, disabled and
elderly are at highest
risk of being scalded.
See instruction manual
before setting temperature
at the unit.
Feel water before bathing
or showering.
If this unit is used
to produce water that could scald if too hot, such
as domestic hot water use, adjust the outlet control
(limit) or use temperature limiting valves to obtain a
maximum water temperature of 125°F (52°C).
WARNING
The inlet gas pressure to the unit must not
exceed 13” W.C. (3.2kPa).
WARNING
Fire or Explosion Hazard
Improper confi guration can cause fuel buildup and
explosion. Improper user operation may result in
property loss, severe physical injury, or death.
Any changes to safety-related confi guration
parameters must only be done by experienced and/or
licensed burner/boiler operators and mechanics.
If any odor of gas is detected, or if the gas burner does
not appear to be functioning in a normal manner, close
the main gas shutoff valve. Do not shut off the power
switch. Contact your heating contractor, gas company,
or factory representative.
NOTE: This unit is protected against hydronic
over-pressurization. A pressure relief valve is included
with each unit.
WARNING
Indicates an imminently hazardous situation which, if not
avoided, can or will result in death or serious injury and can
or will result in catastrophic property damage.
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in moderate injury and/or property damage.
NOTE:
Indicates instructions that are important to that topic but not
related to personal injury or property damage.
Safety Notes are used thoughout this manual to bring attention to the presence of hazards with various
risk levels and to off er important information concering the life of this product. There are 3 basic types.
WARNING
CANCER AND REPRODUCTIVE HARM.
WWW.P65WARNINGS.CA.GOV.
AS REQUIRED BY THE STATE OF
CALIFORNIA PROPOSITION 65.
1
2
3
LAARS Heating Systems
Page 4
WARNING
Electrical Shock Hazard
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply before
beginning installation or changing the wiring to prevent
electrical shock or damage to the equipment. It may be
necessary to turn off more than one power supply
to disconnect.
All electrical wiring is to be done in accordance with
local codes, or in the absence of local codes, with: 1)
The National Electrical Code ANSI/NFPA No. 70 - latest
Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code
- Part 1.” This appliance must be electrically grounded in
accordance with these codes.
WARNING
The Repair Parts list designates parts that contain
refractory ceramic bers (RCF). RCF has been classifi ed
as a possible human carcinogen. When exposed to
temperatures above 180ºF, such as during direct ame
contact, RCF changes into crystalline silica, a known
carcinogen. When disturbed as a result of servicing or
repair, these substances become airborne and, if inhaled,
may be hazardous to your health.
Do not remove or replace RCF parts or attempt any
service or repair work involving RCF without wearing
the following protective gear:
1. A National Institute for Occupational Safety and
Health (NIOSH) approved respirator.
2. Long sleeved, loose tting clothing.
3. Gloves.
4. Eye Protection.
NOTE: All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
Edition “National Fuel Gas Code” or
2) CSA B149.1 “Natural Gas and Propane Installation
Code” or in Canada reference the B149.1 latest
edition and with the requirement of the local utility or
other authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein. All electrical wiring is to
be done in accordance with the local codes, or in the
absence of local codes, with: 1) The National Electrical
Code ANSI/NFPA No. 70-latest Edition, or
2) CSA STD. C22.1 “Canadian Electrical Code - Part
1”. This appliance must be electrically grounded in
accordance with these codes.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 5
REQUIRED RECOMMENDED
CLEARANCE FROM SERVICE ACCESS
SURFACE COMBUSTIBLE MATERIAL CLEARANCE
inches cm inches cm
Left Side 1 2.5 24 61
Right Side 1 2.5 24 61
Top 1 2.5 12 30
Back 1 2.5 **12** 30**
Front 1 2.5 36 91
Vertical
(Category 1) 6* 15.2*
Vent
Horizontal per UL1738 venting
(Category 3) system supplier’s
Vent instructions
*1" (2.5cm) when b-vent is used.
**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).
1.E Locating the unit
This unit should be located to provide clearances
on all sides for maintenance and inspection. It should not
be located in an area where leakage of any connections
will result in damage to the area adjacent to the unit or to
lower oors of the structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the unit.
This unit is design certied by CSA-International
for installation on combustible ooring; in basements;
in closets, utility rooms or alcoves. These units must
never be installed on carpeting. The location for
the unit should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
control replacement, etc.). When vented vertically, this
unit must be located as close as practical to a chimney
or outside wall. If the vent terminal and/or combustion air
terminal terminate through a wall, and there is potential
for snow accumulation in the local area, both terminals
should be installed at an appropriate level above grade.
The dimensions and requirements that are shown
in Table 1 should be met when choosing the locations for
the unit.
1.F Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results, a pump-mounted water heating
unit should be located within 15 feet (4.6m) of the
storage tank(s). The pump is sized for 30 feet (9.1m) of
piping.
If the unit must be installed with longer piping
runs, then larger diameter pipe or tubing shall be used.
Consult the factory for assistance.
1.G Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
For the best results, a pump-mounted boiler should
be located within 15 feet (4.6m) of the supply and return
headers. The pump is sized for 30 feet (9.1m) of piping.
If the unit must be installed with longer piping runs,
then larger diameter tubing shall be used. Consult the
factory for assistance.
1.H Locating the Unit for Correct
Horizontal Vent/Ducted Air Distance
from Outside Wall
The forced draft combustion air blower/blowers in
the unit has/have sucient power to pull air and vent
properly when the following guidelines for horizontal air
and vent are followed (see Table 2).
NOTE: The vent collar size is larger than the size of
the vent pipe that can be used. Vent collar size and
horizontal pipe diameters can be found in Table 2. The
larger vent collar size is to accommodate Category I
(vertical) vent systems.
NOTE: When located on the same wall, the
combustion air intake terminal must be installed
a minimum of 12" (30cm) below the exhaust vent
terminal and separated by a minimum of 36 inches
(91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other
debris.
Table 1. Clearances
LAARS Heating Systems
Page 6
1.I Dimensions
See Figures 1 and 2.
Figure 1. Dimensional Data (standard units).
Air Vent Shipping Weight
1
Unit Conn. Conn.
Size A B C D E W V lbs kg
500 33¾ 85 16¾ 43 17 10 25 8 20 6 15 8 20 425 193
750 45¾ 116 22¾ 53 17 10 25 24 8 20 10 25 505 229
1000 57¾ 147 28¾ 73 17 10 25 24 8 20 10 25 615 279
1250 68¼ 173 34 87 10¼
26 10 25 9 23 12 30 12 30 675 306
1500 78¾ 200 39½ 100 10¼
26 10 25 9 23 12 30 12 30 760 345
1750 89¼ 227 44¾ 113 10¼
26 10 25 9 23 12 30 14 36 825 375
2000 99¾ 253 49¾ 127 10¼
26 10 25 9 23 12 30 14 36 955 434
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in inches cm.
GAS
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 7
GAS
Air Vent
Conn. Conn.
Size A B C D E F W V
500 33¾ 86 16¾ 43 17 10 25 8 20 46¼ 117 6 15 8 20
750 45¾ 116 22¾ 58 17 10 25 24 58¼ 148 8 20 10 25
1000 57¾ 147 28¾ 73 17 10 25 24 70¼ 178 8 20 10 25
1250 68¼ 173 34¼ 87 10¼
26 10 25 9 23 80¾ 205 12 30 12 30
1500 78¾ 200 39½ 100 10¼
26 10 25 9 23 91¼ 232 12 30 12 30
1750 89¼ 227 44¾ 113 10¼
26 10 25 9 23 101¾ 258 12 30 14 36
2000 99¾ 253 49¾ 127 10¼ 26 10 25 9 23 112¼ 285 12 30 14 36
Figure 2. Dimensional Data (pump-mounted models).
HORIZONTAL INTAKE AIR
VENT COLLAR VENT PIPE PIPE MAX. PIPE MAX. NO. SIDE WALL SIDE WALL
SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION
TERMINAL AIR TERMINAL
in. cm in. cm in. cm ft. m PART NUMBER PART NUMBER
500 8 20 6 15 6 15 50 15 3 CA001401 CA20260701
750 10 25 8 20 8 20 50 15 3 CA001402 CA20260703
1000 10 25 8 20 8 20 50 15 3 CA001402 CA20260703
1250 12 30 10 25 12 30 50 15 3 CA001405 CA20260706
1500 12 30 10 25 12 30 50 15 3 CA001405 CA20260706
1750 14 36 12 30 12 30 50 15 3 CA001404 CA20260706
2000 14 36 12 30 12 30 50 15 3 CA001404 CA20260706
Table 2. Horizontal Vent / Combustion Air Parameters.
LAARS Heating Systems
Page 8
UNIT
EACH OPENING*
SIZE
SQUARE INCHES SQUARE CM
500 125 807
750 188 1213
1000 250 1613
1250 313 2020
1500 375 2420
1750 438 2826
2000 500 3226
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at oor level and one
at the ceiling, so the total net free area could be double the gures
indicated.
This chart is for use when communicating directly with the
outdoors. For special conditions and alternate methods, refer to the
latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of
louvers. Correct for screen resistance to the net free area if a
screen is installed. Check all local codes applicable to combustion air.
Table 3. Combustion Air Openings.
SECTION 2 Venting and
Combustion Air
2.A Combustion Air
These boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with section 5.3, Air for Combustion and
Ventilation, of the National Fuel Gas Code, ANSI Z223.1,
or Sections 7.2, 7.3 or 7.4 of CSA B149.1, Installation
Codes, or applicable provisions of the local building
codes.
This unit may receive combustion air from the
space in which it is installed, or it can be ducted directly
to the unit from the outside. Ventilation air must be
provided in either case.
2.A.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top and
one commencing within 12 inches (30 cm) of the bottom,
of the enclosure shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the outdoors.
When directly communicating with the outdoors, or
when communicating to the outdoors through vertical
ducts, each opening shall have a minimum free area of
1 square inch per 4000 BTU/hr (5.5 square cm/kW) of
total input rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal ducts,
each opening shall have a minimum free area of not less
than 1 square inch per 2000 BTU/hr (11 square cm/kW)
of total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, and for each
model.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces that
directly communicate with the outdoors and shall have a
minimum free area of 1 square inch per 3000 BTU/hr (7
square cm/kW) of the total input rating of all equipment
located in the enclosure. This opening must not be less
than the sum of the areas of all vent connectors in the
conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to
the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes
or, in absence of such requirements, follow CSA B149.1.
2.A.2 Intake Combustion Air
The combustion air can be taken through the wall,
or through the roof. When taken from the wall, it must be
taken from out-of-doors by means of the Manufacturers
horizontal wall terminal (see Table 2). When taken
from the roof, a eld-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain water
(see Figure 3).
Use single-wall galvanized pipe, per Table 4, for the
combustion air intake (see Table 2 for appropriate size).
Route the intake to the heater as directly as possible.
Seal all joints with tape. Provide adequate hangers. The
unit must not support the weight of the combustion air
intake pipe. Maximum linear pipe length allowed is 50
feet (15.2m). Three elbows have been calculated into the
50-foot (15.2m) linear run. Subtract 10 allowable linear
feet (3.0m) for every additional elbow used (see Table
2). When fewer than 3 elbows are used, the maximum
linear pipe length allowed is still 50 feet (15.2m).
The connection for the intake air pipe is on the lter
box. This unit has venting and combustion air ducting
attached to the top.
In addition to air needed for combustion, air shall
also be supplied for ventilation, including all air required
for comfort and proper working conditions for personnel.
This unit loses less than 1 percent of its input rating to
the room, but other heat sources may be present.
2.B Venting
2.B.1 Vent Categories
Depending upon desired venting for this unit, it may
be considered a Category I or a Category III appliance.
In general, a vertical vent system will be a Category
I system. However, in rare instances, a vertical vent
system may be considered Category III. In the U.S., the
National Fuel Gas Code (ANSI Z223.1-Latest Edition),
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 9
Figure 3. Combustion Air and Vent Through Roof.
TERM DESCRIPTION
Pipe Single-wall galvanized steel pipe, 24 gauge
minimum (either insulated or non-insulated)
Joint Permanent duct tape or aluminum tape
Sealing
Table 4. Required Combustion Air Piping Material.
or in Canada the CSA B149.1 (latest edition), denes a
Category I vent system, and includes rules and tables to
size these vent systems. If this units vertical vent system
does not satisfy the criteria for Category I venting, it
must be vented as a Category III system.
All vent systems which discharge horizontally
(without the use of a power venter) are considered
Category III vent systems.
2.B.2 Category I Vent
When vented as a category I appliance, the vent
system must conform to the National Fuel Gas Code
(ANSI Z223.1-Latest Edition) in the U.S., or in Canada,
to CSA B149.1 (latest edition). The vent system must
be sized and installed for a Category I Fan-Assisted
Appliance.
If chimney height is greater than 25 feet, or if
multiple units are vented into the same vertical vent, a
barometric damper must be installed on each unit, such
that the ue draft does not exceed (negative) 0.1" w.c.
If using a power venter for any type of Category I
venting, the draft should be set between (negative) 0.01
and 0.10" w.c.
2.B.3 Common Venting Systems
These units are Category I fan-assisted when
vented vertically and adhering to all applicable codes.
When common venting a fan-assisted unit with
other other appliances through one shared vertical duct
called a “common vent”, special care must be taken by
the installer to ensure safe operation. In the event that
the common vent is blocked, it is possible, especially
for fan-assisted devices, to vent backwards through
non-operating appliances sharing the vent, allowing
combustion products to inltrate occupied spaces. If the
appliances are allowed to operate in this condition,
serious injury or death may occur.
WARNING
Operation of appliances with a blocked common
vent may lead to serious injury or death. If safe
operation of all appliances connected to a common
vent cannot be assured, including prevention of
spillage of ue gasses into living spaces, common
venting should not be applied, and appliances
should each be vented separately.
Proper vent sizing, construction and safety
requirements from the National Fuel Gas Code, ANSI
Z223.1 or in Canada, from CSA B149.1 as well as all
applicable local codes must be followed.
As an additional precaution, it is recommended
that a Carbon Monoxide (CO) alarm be installed in all
enclosed spaces containing combustion appliances.
MightyTherm2 units are not allowed to be vented
into a common horizontal Cat III vent system (horizontal
discharge or other conguration for Cat III), unless
a properly sized vent fan is used, and the common
vent system is properly designed by the vent fan
manufacturer or a qualied engineer.
Refer to the installation and operating instructions
on all appliances to be common vented for instructions,
warnings, restrictions and safety requirements. If safe
operation of all appliances connected to a common vent
cannot be assured, including prevention of spillage of
ue gasses into living spaces, common venting should
not be applied, and appliances should each be vented
separately.
2.B.4 Category III Vent
When this unit is vented with horizontal discharge,
it must be installed per this installation manual and the
venting system manufacturer’s installation instructions.
The vent system must be sealed stainless steel (see
Table 5).
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers
as required in the venting system manufacturer’s Instal-
lation Instructions. Horizontal portions of the venting
system must be supported to prevent sagging and may
not have any low sections that could trap condensate.
The unit must not support the weight of the vent pipe.
LAARS Heating Systems
Page 10
TERM DESCRIPTION
Pipe Must comply with UL Standard 1738
such as Type 29-4C Stainless Steel
(either insulated or non-insulated).
Joint Follow vent manufacturer’s instructions
Sealing
Table 5. Required Horizontal Venting Material.
Horizontal runs must slope downwards not less than ¼
inch per foot (2 cm/m) from the unit to the vent terminal.
Reference Table 2 for the size of the Category III vent
system. Up to three elbows can be used with 50 linear
feet (15.2m) of pipe. Subtract 10 allowable linear feet
(3.0m) for every additional elbow used.
WARNING
The outdoor vent terminal gets hot. This unit must
be installed in such a way as to reduce the risk of
burns from contact with the vent terminal.
2.C Locating Vent & Combustion Air
Terminals
2.C.1 Side Wall Vent Terminal
The appropriate manufacturers side wall vent
hood must be used, and is listed in the installation
and operation manual. The terminal provides a means
of installing the vent piping through the building wall,
and must be located in accordance with ANSI Z223.1/
NFPA 54 and applicable local codes. In Canada, the
installation must be in accordance with CSA B149.1 or .2
and local applicable codes. Consider the following when
installing the terminal:
1. Figure 4 shows the requirements for mechanical vent
terminal clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or
appliances with condensing vents are not permitted
to terminate above a public walkway, or over an area
where condensate or vapor could create a nuisance
or hazard.
3. Locate the vent terminal so that vent gases cannot be
drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows, gravity
inlets or other openings. When possible, locations
under windows or near doors should be avoided.
5. Locate the vent terminal so that it cannot be blocked
by snow. The National Fuel gas code requires that
it be at a minimum of 12" above grade. In a location
that has the possibility of snow accumulation, it
is critical the installer places the vent at least 12"
higher than the maximum potential snow line. Seek
local municipalities and their codes for appropriate
installation techniques.
6. Locate the terminal so the vent exhaust does not
settle on building surfaces or other nearby objects.
Vent products may damage such surfaces or objects.
7. If the boiler or water heater uses ducted
combustion air from an intake terminal located on
the same wall, locate the vent terminal at least 3
feet (0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1 foot
(0.3m) above the combustion air terminal.
2.C.2 Side Wall Combustion Air Terminal
The manufacturers side wall combustion air
terminal (see Table 2) must be used when the unit
takes its combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning uid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject to
damage by accident or vandalism.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
gas code requires that it be at a minimum of 12"
above grade. Depending on local conditions, the
installer should ensure that it remains at least 12"
above the maximum potential snow line. Seek
local municipalities and their codes for appropriate
installation techniques.
WARNING
It is critical that the combustion air intake and the vent
terminals remain at least 12" above the maximum
potential snow line. If either the vent terminal or the
air terminal is blocked by snow, there may be potential
for the unit to produce excess carbon monoxide and
or recirculate ue gasses into the building/dwelling.
Personal injury or DEATH may occur. Natural snowfall,
drifting, and banking should all be taken into account
when locating the terminals in a potential snow
environment.
4. If this unit is side-wall vented to the same wall,
locate the vent terminal at least 3 feet (0.9m)
horizontally from the combustion air terminal, and
locate the vent terminal at least 1 foot (0.3m) above
the combustion air terminal (see Figure 4).
2.C.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent
must extend at least 3 feet (0.9m) above the point at
which it penetrates the roof. It must extend at least 2
feet (0.6m) higher than any portion of a building within a
horizontal distance of 10 feet (3.0m), and high enough
above the roof line to prevent blockage from snow. When
the combustion air is taken from the roof, the combustion
air must terminate at least 12" (30cm) below the vent
terminal (see Figure 3). Seek local municipalities and
their codes for appropriate installation techniques.
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas fueled equip-
ment installed in every dwelling, building or structure
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 11
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
deck, or balcony
B= Clearance to window or door that may be 4 feet (1.2 m) below or to side of opening; 36 inches (91 cm)
opened 1 foot (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated sot located
above the terminal within a horizontal See note 4 See note 5
distance of 2 feet (61cm) from the center
line of the terminal
E= Clearance to unventilated sot See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet above
extended above meter/regulator assembly See note 4 the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to 4 feet (1.2 m) below or to side of opening; 36 inches (91 cm)
any other appliance 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
Vent termination not allowed in this location
Vent termination not allowed in this location for category IV appliances. A vent shall not
L= Clearance above paved sidewalk or paved for category IV appliances. For Category III terminate directly above a sidewalk or paved
driveway located on public property appliances, vent must terminate at least 7 driveway that is located between two single
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.
For Category III appliances that do not violate
the previous condition, vent must terminate
at least 7 feet (2.13m) above the sidewalk or
driveway.
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA-B149.1 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
4. For clearances not specied in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specied in CSA-B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.
Figure 4. Combustion Air and Vent Through Side Wall.
LAARS Heating Systems
Page 12
used in whole or inpart for residential purposes, includ-
ing those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less than
seven (7) feet above nished grade in the area of the
venting, including but not limited to decks and porches,
the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gastter shall
observe that a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on the oor level
where the gas equipment is to be installed. In addition, the
installing plumber or gastter shall observe that a battery op-
erated or hard-wired carbon monoxide detector with an alarm
is installed on each additional level of the dwelling, building
or structure served by the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the property
owner to secure the services of qualied licensed profes-
sionals for the installation of hard-wired carbon monoxide
detectors.
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the
hard-wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/
UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (½) inch in size,
"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not ap-
prove the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a) 1
through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not
Required To Be Vented" in the most current edition of NFPA
54 as adopted by the Board; and
2. Product Approved side wall horizontal vented gas fueled
equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for
residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED. When the manufacturer of
Product Approved side wall horizontally vented gas equip-
ment provides a venting system design or venting system
components with the equipment, the instructions provided
by the manufacturer for installation of the equipment and the
venting system shall include:
1. Detailed instructions for the installation of the venting system
design or the venting system components; and
2. A complete parts list for the venting system design or venting
system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEMNOT PROVIDED. When the manufac-
turer of a Product Approved side wall horizontally vented gas
fueled equipment does not provide the parts for venting the
fuel gases, but identies "special venting systems", the fol-
lowing requirements shall be satised by the manufacturer:
1. The identication of each "special venting system" shall
include either the listing of the website, phone number or
manufacturer's address where the venting system installation
instructions can be obtained; and
2. The "special venting systems" shall be Product Approved
by the Board, and the instructions provided with that system
shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the Product
Approved side wall horizontally vented gas fueled equip-
ment, and all the venting instructions, parts lists, and/or
design instructions for the venting system shall remain
with the appliance or equipment at the completion of the
installation.
Manufacturers' websites where venting system installation
instructions may be obtained is located on the manufacturers
website (see back cover).
2.C.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water (see Figure 3). The
opening on the end of the terminal must be at least 12"
(30cm) above the point at which it penetrates the roof,
and high enough above the roof line to prevent blockage
from snow. When the vent terminates on the roof, the
combustion air must terminate at least 12" (30cm) below
the vent terminal.
2.D Common Vent Test — Boilers
When an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remain-
ing connected to the common venting system are not in
operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deciencies which could cause an unsafe
condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 13
OUTDOOR VENT OUTDOOR
SIZE TERMINAL COMBUSTION
AIR TERMINAL
500 20254703 CA014701
750 20254705 CA014702
1000 20254705 CA014702
1250 D2007700 CA014704
1500 D2007700 CA014704
1750 D2007800 CA014704
2000 D2007800 CA014704
Table 6. Vent Terminals for Outdoor Units.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so that the heating unit will operate continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
replace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Installation
Codes. When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size as
determined using the appropriate tables in Part II of
the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CSA B149.1, Installation Codes.
2.E Vent Terminals for Outdoor Units
For outdoor applications, the vent and combustion
air openings must be covered with proper terminals to
prevent rain, snow and other objects from falling into the
unit.
If local codes allow, outdoor installations may
use 1' of appropriately sized galvanized single wall or
B-Vent and a rain cap for exhaust vent termination in
the default conguration (venting out of the top). Note
that some local codes may require a higher vertical
vent height, extending above any perimeter fencing,
etc. In installations where the appearance of the vent is
objectionable, the low prole vent terminals in Table 6
may be used.
Combustion air inlets consist of appropriately
sized galvanized pipe and elbows to allow the open
end to face down aside the boiler. This is available as a
Commercial Kit from the manufacturer.
Part numbers for the low prole terminals to cover the
vent and combustion air openings are shown in Table 6.
LAARS Heating Systems
Page 14
SIZE DISTANCE FROM GAS METER
AND OR LAST STAGE REGULATOR
GAS TYPE 0-100' 100-200' 200-300'
500 natural 1½" 2" 2"
500 propane 1" 1½" 1½"
750 natural 2" 2" 2½"
750 propane 1½" 1½" 2"
1000 natural 2" 2½" 3"
1000 propane 1½" 2" 2½"
1250 natural 2½" 2½" 3"
1250 propane 2" 2" 2½"
1500 natural 2½" 3" 3"
1500 propane 2" 2½" 2½"
1750 natural 2½" 3" 3"
1750 propane 2" 2½" 2½"
2000 natural 3" 3" 3½"
2000 propane 2½" 2½" 3"
Metric Equivalent
SIZE DISTANCE FROM GAS METER
AND OR LAST STAGE REGULATOR
GAS TYPE 0-31m 31-61m 61-91m
500 natural 3.8cm 5.1cm 5.1cm
500 propane 2.5cm 3.8cm 3.8cm
750 natural 5.1cm 5.1cm 6.4cm
750 propane 3.8cm 3.8cm 5.1cm
1000 natural 5.1cm 6.4cm 7.6cm
1000 propane 3.8cm 5.1cm 6.4cm
1250 natural 6.4cm 6.4cm 7.6cm
1250 propane 5.1cm 5.1cm 6.4cm
1500 natural 6.4cm 7.6cm 7.6cm
1500 propane 5.1cm 6.4cm 6.4cm
1750 natural 6.4cm 7.6cm 7.6cm
1750 propane 5.1cm 6.4cm 6.4cm
2000 natural 7.6cm 7.6cm 8.9cm
2000 propane 6.4cm 6.4cm 7.6cm
NOTES: 1. These gures are based on 1/2" (0.12kPa) water column
pressure drop.
2. Check supply pressure and local code requirements
before proceeding with work.
3. Pipe ttings must be considered when determining gas
pipe sizing.
Table 7. Gas Piping Sizes.
SECTION 3 Gas Supply and Piping
3.A Gas Supply and Piping
Gas piping should be supported by suitable
hangers or oor stands, not by the boiler or water heater.
This units gas train allows the user to pipe the gas
from either the right side or the left side of the unit. As
shipped, the right side of the gas train is capped o, and
there is a manual valve on the left side. If desired, the
manual valve on the left side of the gas train may be
moved to the right side, and the cap on the right side
may be moved to the left.
Review the following instructions before proceeding
with the installation.
1. Verify that the unit is tted for the proper type of
gas by checking the rating plate. These units are
equipped to operate at elevations up to 10,000 feet
(3050m) and may be adjusted to operate properly
at altitudes above 2500 feet (see Section 6.F.2)
and the input will be reduced if the heating value of
the gas supply is below sea level values.
2. The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas pressure
is 5" W.C. (1.2kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shuto valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of the
gas controls.
7. All threaded joints should be coated with piping
compound resistant to action of liqueed petroleum
gas.
8. The unit and its individual shuto valve must be
disconnected from the gas supply piping during any
pressure testing of that system at test pressures in
excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shuto
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less
than 1/2 PSIG (3.45kpa).
10. The unit and its gas connection must be leak tested
before placing it in operation.
11. Purge all air from gas lines.
NOTE: This unit and all other gas appliances sharing
the gas supply line must be ring at maximum capacity
to properly measure the inlet supply pressure. The
pressure can be measured at the supply pressure
port on the gas valve. Low gas pressure could be an
indication of an undersized gas meter, undersized gas
supply lines and/or an obstructed gas supply line.
WARNING
Do not use open ame to check for leaks. An
open ame could lead to explosion, which could result
in property damage, serious injury or death.
WARNING
If an inline high gas pressure regulator is used, it
must be of the lockup type and located a minimum
of 10 feet from the unit. Failure to do so may result in
insucient gas volume supplied to the unit.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 15
Unit
20°F 25°F 30°F 35°F
Size ow H/L ow H/L ow H/L ow H/L
gpm feet gpm feet gpm feet gpm feet
500 43 1.7 34 1.1 28 0.9 24 0.7
750 64 3.3 51 2.3 43 1.7 36 1.2
1000 85 5.0 68 3.6 57 3.1 49 2.2
1250 106 8.1 85 6.1 71 4.7 61 3.4
1500 128 10.0 102 7.2 85 5.5 73 4.2
1750 N/R N/R 119 10.5 99 8.4 85 5.8
2000 N/R N/R 136 12.5 113 10.4 97 8.3
Metric Equivalent
Unit
11°C 14°C 17°C 19°C
Size ow H/L ow H/L ow H/L ow H/L
lpm m lpm m lpm m lpm m
500 161 0.5 129 0.3 107 0.3 92 0.2
750 241 1.0 193 0.7 161 0.5 138 0.4
1000 321 1.5 257 1.1 214 0.9 184 0.7
1250 401 2.5 322 1.9 269 1.4 231 1.0
1500 483 3.0 386 2.2 322 1.7 276 1.3
1750 N/R N/R 451 3.2 375 2.6 322 1.8
2000 N/R N/R 515 3.8 429 3.2 368 2.5
Notes: gpm = gallons per minute, lpm = liters per minute,
H/L = headloss, ft = headloss in feet, m = headloss in meters.
Maximum temperature rise is 35°F (19°C), as shown. Headloss is
for boiler’s heat exchanger only. N/R = not recommended.
Table 8. Water Flow Requirements — Boilers.
Figure 5. Typical Gas Train Conguration.
SECTION 4 Water Connections
4.A Boilers.
4.A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This unit must be installed in a closed pressure
system with a minimum of 12 psi (82.7kPa) static
pressure at the boiler.
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with this
unit. Due to expansion and contraction of copper pipe,
consideration should be given to the type of hangers
used. Rigid hangers may transmit noise through the
system resulting from the piping sliding in the hangers.
It is recommended that padding be used when rigid
hangers are installed. Maintain 1" clearance to
combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent, a
diaphragm-type expansion tank, and a hydronic ow
check in the system supply loop. Minimum ll pressure
must be 12psig (82.7kPa). Install shuto valves where
required by code.
Suggested piping diagrams are shown (see Fig-
ures 6 through 10). These diagrams are meant only as
a guide. Components required by local codes must be
properly installed.
4.A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic ll valve.
2. Install a suitable back ow preventer between the
automatic ll valve and the cold water supply.
3. Install shut o valves where required.
NOTE: This boiler, when used in connection with a
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air handling
appliances where they may be exposed to refrigerated
air circulation must be equipped with ow control valves
or other automatic means to prevent gravity circulation of
the boiler water during the cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cuto device either as a part of
the boiler or at the time of boiler installation.
4.A.3 Water Flow Requirements — Boiler
A hydronic heating (closed loop) application
re-circulates the same uid in the piping system. As a
result, no new minerals or oxygen is introduced into
the system. To ensure a proper operating temperature
leading to long boiler life, a ow rate has been
established based on the uid temperature rise for this
specic size boiler.
Pump-mounted boilers can be ordered for use in
primary secondary piping systems. The pumps used are
sized for the headloss through the heater, plus 30 feet
(9.1m) of full-sized piping (same size as boiler outlet)
and a normal number of ttings.
LAARS Heating Systems
Page 16
Table 8 species water ow rates for boilers, which
will enable the user to size a pump. The headloss shown
is for the heater only, and the user will need to add the
headloss of the system piping to properly size the pump.
The minimum inlet water temperature for the this
unit is 120°F (49°C) to avoid condensing on the copper
coils.
4.A.4 Freeze Protection — Boiler
Boiler installations are not recommended in areas
where the danger of freezing exists unless proper
precautions are made for freeze protection. A non
toxic, heating system, anti-freeze may be added to
the hydronic system provided that the concentration
does not exceed 50% and the anti freeze contains an
anti foamant. When a 50/50 mixture is used, increase
the water ow requirements by 15%, and increase the
headloss requirements by 20%.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a boiler from ring. Any time a boiler
is subjected to freezing conditions, and the boiler is not
able to re, and/or the water is not able to circulate,
there is a risk of freezing in the boiler or in the pipes in
the system. When water freezes, it expands. This can
result in bursting of pipes in the system, or damage
to the boiler, which could result in leaking or ooding
conditions.
NOTE: Dierent glycol products may provide varying
degrees of protection. Glycol products must be
maintained properly in a heating system, or they may
become ineective. Consult the glycol specications,
or the glycol manufacturer, for information about
specic products, maintenance of solutions, and set up
according to your particular conditions.
4.B Water Connections —
Water Heaters
4.B.1 Water System Piping — Water Heater
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with this
unit. Due to expansion and contraction of copper pipe,
consideration should be given to the type of hangers
used. Rigid hangers may transmit noise through the
system resulting from the piping sliding in the hangers.
It is recommended that padding be used when rigid
hangers are installed.
This unit can be used with several dierent types
of readily available storage tanks. A pump draws water
from the storage tank and pumps the water through the
heater and back into the tank. Pump-mounted units have
a circulating pump built into the water heater. The pumps
used are sized for the headloss through the heater, plus
30 feet (9.1m) of full-sized piping (same size as boiler
outlet) and a normal number of ttings. Pumps used on
pump-mounted unit are sized for soft/normal or hard
water, so make sure a pump-mounted unit matches the
water quality of the installation.
Pipe the outlet from the heater’s relief valve such
that any discharge from the relief valve will be conducted
to a suitable place for disposal when relief occurs. Do
not reduce line size or install any valves in this line. The
line must be installed to allow complete drainage of both
the valve and the line.
Suggested piping diagrams are shown in Figures
11 through 14. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
The minimum inlet water temperature for this unit is
120°F (49°C) to avoid condensing on the copper coils.
4.B.2 Hot Water Supply Piping — Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A temperature and pressure relief valve, listed
as complying with the Standard for Relief Valves
and Automatic Gas Shuto Devices for Hot Water
Supply Systems (ANSI Z21.22 / CSA 4.4) of suitable
discharge capacity, must be installed in the separate
storage tank system.
If this water heater is installed in a closed water
supply system, such as one having a backow preventer
in the cold water supply line, the relief valve may
discharge periodically, due to thermal expansion. A
properly-sized expansion tank (or other means) must be
provided to control thermal expansion. Contact the water
supplier or local plumbing inspector on how to control
this situation.
4.B.3 Water Flow Requirements — Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the units heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water ow
requirements for this units water heater are based upon
the hardness of the water. The water ow is kept high
enough to prevent scaling, but low enough to prevent
tube erosion. For extremely soft or hard water, cupro-
nickel tubes are available. Contact a manufacturers
representative if you have questions or concerns about
water quality.
Pump-mounted water heaters can be ordered
with standard pumps for soft or normal water or with
pumps for hard water. The pumps used are sized for the
headloss through the heater, plus 30 feet (9.1m) of full-
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48