SICK IDS230, ISD260 and ISD280 IR Data Transmission Systems Operating instructions

Type
Operating instructions
O PERATING INSTRUCTIONS
ISD 230, ISD 260 and ISD 280
IR Data Transmission Systems
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
© SICK AG · Germany · All rights reserved
2
Quick Finder
Installation procedure (overview)
Installing the ISD 230 system
Two identical units from the ISD 230 series are required (e.g. 2 x ISD 230-2111).
1. Set the transmission frequency on each unit
See Chapter 5.1.2 Setting the transmission frequencies ...................................Page 22
2. Configure the data interface on each unit
(interface type and transfer rate)
See Chapter 5.1.3 Configuring the data interface.................................................Page 24
3. Connect the units
(data interface and function interfaces)
See Chapter 5.1.4 Connector pin assignment........................................................Page 26
See Chapter 5.1.6 Connecting the data interface ................................................. Page 27
See Chapter 5.1.7 Connecting the functions interfaces......................................Page 30
4. Mount and align the units
See Chapter 4 Installation.............................................................................................. Page 16
5. Apply the 24 V DC supply voltage to both units
6. Check alignment
See Chapter 6.1. Switching on the units/fine adjustment ..................................Page 43
7. Send data on electrical interface
See Chapter 6.2. Functional test of the data transmission................................Page 43
The ISD 230 is ready for operation!
Installing the ISD 260/280 system
Two different units are required from the same series (e.g. 1 x ISD 260-1111 and
1 x ISD 260-1112)
1. Configure the data interface on each unit
(interface type and transfer rate)
See Chapter 5.2.3 Configuring the data interface ................................................Page 33
2. Connect the units
(data interface and function interfaces)
See Chapter 5.2.4 Pin assignment .............................................................................Page 35
See Chapter 5.2.6 Connecting the data interface ................................................ Page 37
See Chapter 5.2.7 Connecting the functions interfaces .....................................Page 40
3. Mount and align the units
See Chapter 4 Installation.............................................................................................. Page 16
4. Apply the 24 V DC supply voltage to both units
5. Check alignment
See Chapter 6.1. Switching on the units/fine adjustment ..................................Page 43
6. Send data on electrical interface
See Chapter 6.2. Functional test of the data transmission................................Page 43
The ISD 260/280 is ready for operation!
ISD 230
ISD 260/ISD 280
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
3
Contents
Contents
1 Notes on this document ............................................................................................ 7
1.1 Purpose ....................................................................................................................................... 7
1.2 Target audience ........................................................................................................................ 7
1.2.1 Mounting, electrical installation, maintenance and replacement ............. 7
1.2.2 Configuration and startup ....................................................................................... 7
1.3 Information content ................................................................................................................. 7
1.4 Symbols ....................................................................................................................................... 8
2 Safety Information ....................................................................................................... 9
2.1 Autorized users ......................................................................................................................... 9
2.1.1 Mounting and maintenance ................................................................................... 9
2.1.2 Electrical installation and replacement .............................................................. 9
2.1.3 Startup, operation and configuration .................................................................. 9
2.2 Intended use.............................................................................................................................. 9
2.3 General safety instructions and protection measures ................................................ 9
2.4 Quick stop and quick restart ............................................................................................. 10
2.4.1 Stopping the ISD .................................................................................................... 10
2.4.2 Restarting the ISD .................................................................................................. 10
2.5 Environmental information ................................................................................................. 10
2.5.1 Power requirements .............................................................................................. 10
2.5.2 Disposal after removal from service ............................................................... 10
3
Product description ..................................................................................................11
3.1 Design ....................................................................................................................................... 11
3.1.1 Scope of delivery .................................................................................................... 11
3.1.2 Variants ...................................................................................................................... 11
3.1.3 System requirements ........................................................................................... 12
3.1.4 Design ........................................................................................................................ 13
3.2 Method of operation ............................................................................................................ 14
3.3 Indicators and control elements ...................................................................................... 15
3.3.1 Control elements .................................................................................................... 15
3.3.2 Function of the LEDs ............................................................................................. 15
4 Installation ................................................................................................................... 16
4.1 Installation sequence........................................................................................................... 16
4.2 Preparations ............................................................................................................................ 16
4.2.1 Configuring the units ............................................................................................. 16
4.2.2 Required components .......................................................................................... 16
4.2.3 Required accessories ........................................................................................... 16
4.2.4 Required auxiliary parts ........................................................................................ 16
4.2.5 Selecting the mounting location......................................................................... 17
4.2.6 Mounting accessories .......................................................................................... 18
4.3 Mounting and adjusting the system ............................................................................... 19
4.3.1 Mounting the ISD on the three-point bracket .............................................. 19
4.3.2 Mounting the AMS 50 Connection Module .................................................. 20
4.3.3 Alignment of the ISD ............................................................................................. 20
4.4 Dismantling the system ...................................................................................................... 21
5 Electrical installation ............................................................................................... 22
5.1 ISD 230 system .................................................................................................................... 22
5.1.1 Installation sequence ............................................................................................ 22
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
© SICK AG · Germany · All rights reserved
4
Contents
5.1.2 Setting the transmission frequencies ............................................................. 22
5.1.3 Configuring the data interface ........................................................................... 24
5.1.4 Connector pin assignment .................................................................................. 26
5.1.5 Preparations for electrical installation ............................................................. 26
5.1.6 Connecting the data interface ........................................................................... 27
5.1.7 Connecting the functions interfaces ................................................................ 30
5.1.8 Connecting via the AMS 50 connection module ........................................ 32
5.2 ISD 260 and ISD 280 systems ....................................................................................... 33
5.2.1 Installation sequence ............................................................................................ 33
5.2.2 Transmission frequencies ................................................................................... 33
5.2.3 Configuring the data interface ........................................................................... 33
5.2.4 Pin assignment ........................................................................................................ 35
5.2.5 Preparations for electrical installation ............................................................. 36
5.2.6 Connecting the data interface ........................................................................... 37
5.2.7 Connecting the functions interfaces ................................................................ 40
5.2.8 Connecting via the AMS 50 connection module ........................................ 42
6 Operation ..................................................................................................................... 43
6.1 Switching on the units/fine adjustment ......................................................................... 43
6.2 Functional test of the data transmission ...................................................................... 43
6.3 Note on operation of the sy
stem .................................................................................... 43
6.3.1 Operation in cooling plants ................................................................................. 43
6.4 Management of the system .............................................................................................. 43
7 Maintenance ............................................................................................................... 44
7.1 Cleaning the ISD during operation .................................................................................. 44
7.2 Maintenance ........................................................................................................................... 45
7.3 Disposal .................................................................................................................................... 45
8 Troubleshooting ......................................................................................................... 46
8.1 Overview of the possible errors and malfunctions .................................................... 46
8.1.1 Configuration errors ............................................................................................... 46
8.1.2 Mounting errors ...................................................................................................... 46
8.1.3 Electrical installation errors ................................................................................. 46
8.1.4 Malfunctions ............................................................................................................. 46
8.2 Monitoring errors and malfunctions ................................................................................ 46
8.3 Troubleshooting ..................................................................................................................... 46
8.4 SICK Support .......................................................................................................................... 48
8.5 Replacing a ISD unit ............................................................................................................. 48
9 Technical data ............................................................................................................ 49
9.1 Data sheet ISD....................................................................................................................... 49
9.2 Dimensioned drawing of the ISD ..................................................................................... 50
10 Appendix ......................................................................................................................51
10.1 Accessories ............................................................................................................................. 51
10.1.1 Mounting accessories .......................................................................................... 51
10.1.2 Connection modules ............................................................................................. 51
10.1.3 Cables and plug-in connections ........................................................................ 51
10.2 Dimensioned drawing of the accessories .................................................................... 52
10.3 Supplementary documentation ........................................................................................ 53
10.4 EG Declaration of Conformity ............................................................................................ 54
10.5 Device specification card ................................................................................................... 55
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
5
Figures and Tables
Abbreviations used
AMS Connection module with distributor (signal)/with additional power supply
ISD Infra-red sensor for data transmission
LED Light Emitting Diode
Tables
Table 3-1: ISD 230 variants ...................................................................................................................................... 11
Table 3-2: ISD 260 variants ...................................................................................................................................... 11
Table 3-3: ISD 280 variants ...................................................................................................................................... 11
Table 3-4: Meaning of LEDs ..................................................................................................................................... 15
Table 4-1: Aperture angles ......................................................................................................................................... 17
Table 4-2: Light spot diameter of transmitter .................................................................................................... 18
Table 5-1: ISD 230: Setting of the jumpers ST 12 to ST 15 for transmission frequencies .......... 23
Table 5-2: ISD 230: Setting of the DIL switching blocks S 1 to S 3 ........................................................ 25
Table 5-3: ISD 230: Pin assignment of the 9-pin D-Sub connector ........................................................ 26
Table 5-4: ISD 230: Maximum cables lenghts between the ISD and the host ................................... 26
Table 5-5: ISD 230: Connecting the data interface ........................................................................................ 28
Table 5-6: ISD 230: Characteristic data of the Light path free“ and “Contamination“
switching outputs ..................................................................................................................................... 31
Table 5-7: ISD 230: Characteristic data of the “Transmitter off“ switching input ............................... 32
Table 5-8: ISD 260/280: Setting of the DIL switching blocks S 1 and S 2 .......................................... 34
Table 5-9: ISD 260/280: Pin assignment of the 5-pin round connector ............................................... 35
Table 5-10: ISD 260/280: Pin assignment of the 9-pin D-Sub socket (data interface).................... 35
Table 5-11: ISD 260/280: Maximum cables lenghts between the ISD and the host ........................ 36
Table 5-12: ISD 260/280: Connecting the data interface ............................................................................. 38
Table 5-13: ISD 260/280: Characteristic data of the “Light path free“ switching output ................. 41
Table 5-14: ISD 260/280: Characteristic data of the “Transmitter off“ switching input .................... 42
Table 8-1: Troubleshooting ........................................................................................................................................ 47
Table 9-1: Technical Specifications of ISD 230/260/280 .......................................................................... 49
Table 10-1: Accessories: mounting accessories ................................................................................................ 51
Table 10-2: Accessories: connection modules ................................................................................................... 51
Table 10-3: Accessories: cables and plug-in connections ............................................................................. 51
T
able 10-4: Supplementary documentation in English language ................................................................. 53
Figures
Fig. 3-1: Design of an ISD unit ............................................................................................................................. 13
Fig. 3-2: Block diagram: operating principle of the ISD system ............................................................. 14
Fig. 3-3: LED indicators on the top of the housing ...................................................................................... 15
Fig. 4-1: Mount the two units at a distance of 0.2 ... 150/180/200 m ............................................... 17
Fig. 4-2: ISD unit with three-point bracket no. 5 306 369 (accessory) ............................................. 18
Fig. 4-3: Design of the three-point bracket ....................................................................................................... 19
Fig. 4-4: Using the optical adjustment aid (crosshairs) on an unit ........................................................ 20
Fig. 5-1: ISD 230: Position of the jumpers ST 12 to ST 15 and ST 17 on the main board ........ 22
Fig. 5-2: ISD 230: Arrangement with operation of two systems in parallel ........................................ 23
Fig. 5-3: ISD 230: Switching from CL 20 mA passive to CL 20 mA active ........................................ 24
Fig. 5-4: ISD 230-4111: position of the DIL switches for configuring the data interface............ 25
Fig. 5-5: ISD 230: Line termination for the RS 485 interface ................................................................. 30
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
© SICK AG · Germany · All rights reserved
6
Figures and Tables
Fig. 5-6: ISD 230: Functionality of the “Light path free“ and “Contamination“ LEDs .................... 31
Fig. 5-7: ISD 230: Wiring of the “Light path free“ and “Contamination“ PNP outputs................... 31
Fig. 5-8: ISD 230: Connection diagram of “Transmitter off“ PNP input .............................................. 31
Fig. 5-9: ISD 230: Terminal assignment of an ISD 230 unit in the AMS 50 Connection
Module ......................................................................................................................................................... 32
Fig. 5-10: ISD 260/280: Arrangement with operation of two systems in parallel ............................ 33
Fig. 5-11: ISD 260/280: Position of the DIL switches for configuring the data interface .............. 34
Fig. 5-12: ISD 260/280: Connection cable for supply voltage and function interfaces ................. 35
Fig. 5-13: ISD 260/280: Electrical isolation principle for the data interface ....................................... 36
Fig. 5-14: ISD 260/280: Line termination for the RS 485 interface ....................................................... 40
Fig. 5-15: ISD 260/280: Functionality of the “Light path free“ LED ......................................................... 41
Fig. 5-16: ISD 260/280: Wiring of the “Light path free“ PNP output ........................................................ 41
F
ig. 5-17: ISD 260/280: Connection diagram of “Transmitter off“ PNP input .................................... 41
Fig. 5-18: ISD 260/280: Terminals used for one unit in the AMS 50 Connection Module ........... 42
Fig. 5-19: ISD 260/280: Terminal assignment for supply voltage/function interfaces .................. 42
Fig. 7-1: Cleaning the lenses ................................................................................................................................. 44
Fig. 9-1: Dimensions of an ISD unit .................................................................................................................... 50
Fig. 10-1: Dimensions of the three-point bracket no. 5 306 369 ............................................................ 52
Fig. 10-2: Dimensions of the angle bracket no. 2 013 824........................................................................ 53
Fig. 10-3: Dimensions of the connector cover no. 2 016 130 .................................................................. 53
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Notes on this document
Chapter 1
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
7
1.1 Purpose
This document is a guide to the operation of the IR Data Transmission Systems
ISD 230 (0.2 ... 200 m; max. 38.4 kBd)
ISD 260 (0.2 ... 180 m; max. 0.5 MBd)
ISD 280 (0.2 ... 150 m; max. 1.5 MBd)
in their variants
System without heater
System with heater
This document provides information about
Configuration
Mounting and electrical installation
Startup
Maintenance
Exchanging the device
The systems will in this manual be referred to as the “ISD“, except where a dinstinction is
necessary.
1.2 Target audience
This document is intended for persons who are responsible for the following activities:
1.2.1 Mounting, electrical installation, maintenance and replacement
Electricians and service technicians.
1.2.2 Configuration and startup
Technicians and engineers.
1.3 Information content
This document contains all the information required for configuring, mounting, (electrical)
installing and starting up the ISD.
A
series of step-by-setp instructions is provided for each of these activities.
The ISD is configured by jumpers and DIL switches.
For further information on the design of the system or on the data transfer technology in
general, please contact the Auto Ident devision at SICK AG.
1 Notes on this document
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Notes on this document
Chapter 1
© SICK AG · Germany · All rights reserved
8
Note Indicates special features or characteristics.
Explanation Explanations provide background information on technical features.
Recommendation Recommendations help you carry out certain procedures more effectively.
Default setting Marks a section containing the factory defaults.
This symbol refers to additional technical documentation.
Here you have to do something. This symbol characterizes single-step operating
instructions. Multi-step operating instructions are characterized by sequential numbers.
1.4 Symbols
Some of the information in this document is marked specially so that you can access it
quickly:
Warning!
Warnings are provided to prevent injury to operating personal ar serious damage to the
ISD.
Always read warnings carefully and observe them at all times.
ATTENTION
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 2
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
9
Safety Information
2 Safety Information
2.1 Autorized users
For the ISD to function correctly and safety, it must be mounted and operated by
sufficiently qualified personnel.
The following qualifications are required for the various tasks involved:
2.1.1 Mounting and maintenance
General technical training
Knowledge of the standard guidelines relating to safety at the workplace
2.1.2 Electrical installation and replacement
Practical training in electrical engineering
Knowledge of the standard safety guidelines relating to electrical engineering
Experience operating the devices in the relevant application
2.1.3 Startup, operation and configuration
Knowledge of the hardware and software environment of the relevant application
Basic understanding of data transfer methods
2.2 Intended use
The ISD 230, 260 and 280 systems are used to establish a cordless link for transferring
serial data in full-duplex mode using infrared light.
The link, in this sense, always comprises a pair of devices (2 units) with different carrier
frequencies. Depending on the type of link, the units are either installed at a fixed and
mobile station (variable link) or at two fixed stations (permanent link).
Any warranty claims vis-à-vis SICK AG will be rendered invalid if the device is used for any
other purpose or if changes are made to the device, also as part of the mounting and
electrical installation procedures.
2.3 General safety instructions and protection measures
Always read the general safety instructions carefully and observe them at all times. This
also applies to the warnings provided for the individual activities described in this
document.
Shock hazard!
Depending on the type of device, the AMS 50 Connection Module (accessory) for the ISD
is connected to a mains voltage of 230 V AC 50 Hz or 115 V AC 50/60 Hz.
When working with electrical equipment, always follow the relevant safety specifications.
WARNING
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 2
© SICK AG · Germany · All rights reserved
10
Safety Information
Infra-red light can cause blindness!
The ISD 230/260/280 emit infra-red radiation (
λλ
λλ
λ
= =
= =
= 860 nm).
LIGHT EMITTING LASER DIODE CLASS 1 according EN 60825-1/prA1:1999.
Looking directly at the beam can seriously damage your eyesight.
The light is not perceptible to the human eye (no eyelid reflex). The emitted radiation is not
dangerous to human skin.
When mounting and aligning the both units switch off the system.
Never look directly into the large lenses on the front of the device at close range
against the direction of transmission!
Observe the most recent laser specifications (DIN EN 60825-1, latest version).
2.4 Quick stop and quick restart
2.4.1 Stopping the ISD
Switch off the power supply.
The ISD stops the data transmission.
2.4.2 Restarting the ISD
Switch on the power supply.
The ISD starts the data transmission.
When operating the system in cooling plants (below 0 °C) and if the system is switched
on when cold, data transmission can only be guaranteed after the warm-up time (max.
approx. 60 min., depending on the startup temperature) has expired.
2.5 Environmental information
The ISD is designed to cause minimum impact on the environment.
2.5.1 Power requirements
The power requirements are low:
the ISD has a power consumption of max. 0.4 A at 24 V DC
the ISD with heater has a power consumption of max. 2.5 A at 24 V DC
The values are given for devices with disconnected switching outputs.
2.5.2 Disposal after removal from service
Always dispose irreparable devices in a manner that is not harmful to the environment and
in accordance with the applicable national waste disposal regulations. The ISD can be
separated into recyclable secondary raw materials and special-category waste (electronic
s
crap).
See also Chapter 7.3 Disposal, Page 45.
SICK AG currently does not accept any unusable or irreparable devices.
WARNING
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 3
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
11
Product description
3 Product description
3.1 Design
3.1.1 Scope of delivery
The ISD is provided with the following in the packing of each unit:
an ISD unit in the ordered version without connection cables
an information sheet (notes on device)
Depending on the number of device pairs ordered, one or more of the following:
These ISD 230/260/280 Operatings Instructions in German or English
Chapter 10.1 Accessories, Page 51 contains an overview of the available mounting
accessories, connection modules, cables and plug-in connectors.
3.1.2 Variants
The ISD is available in the following variants:
ISD 230
retaeHecafretni ataD.oN redrOepyT
onp/a Am 02 LC883 710 11112-032 DSI
ISD 230-4111 1 017 389 RS 232/422/485/CL 20 mA a/p no
on1L CENIS093 710 11115-032 DSI
ISD 230-4121 1 017 543 RS 232/422/485/CL 20 mA a/p yes
sey1L CENIS445 710 11215-032 DSI
Table 3-1: ISD 230 variants
retaeHecafretni ataD.oN redrOepyT
ISD 260-1111 1 017 379 RS 422/485 (2/4), Carrier frequency 1 no
ISD 260-1112 1 017 380 RS 422/485 (2/4), Carrier frequency 2 no
ISD 260-1121 1 017 390 RS 422/485 (2/4), Carrier frequency 1 yes
ISD 260-1122 1 017 544 RS 422/485 (2/4), Carrier frequency 2 yes
Table 3-2: ISD 260 variants
ISD 260
retaeHecafretni ataD.oN redrOepyT
ISD 280-1111 1 017 046 RS 422/485 (2/4), Carrier frequency 1 no
ISD 280-1112 1 017 047 RS 422/485 (2/4), Carrier frequency 2 no
ISD 280-1121 1 017 375 RS 422/485 (2/4), Carrier frequency 1 yes
ISD 280-1122 1 017 376 RS 422/485 (2/4), Carrier frequency 2 yes
Table 3-3: ISD 280 variants
ISD 280
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 3
© SICK AG · Germany · All rights reserved
12
Product description
3.1.3 System requirements
The following are required to startup and configurate the ISD:
1. ISD without heater:
For each unit a SICK connection module AMS 50 to provide the power supply and
connect the data and function interfaces. Output voltage 24 V DC ±20 % according to
IEC 742, max. 0.75 A. Enclosure rating max. IP 54.
- or -
An operating voltage of 24 V DC ±20 % according to IEC 742 (functional extra-low
voltage). The max. power consumption of the ISD is 0.4 A per unit.
2. ISD with heater:
An operating voltage of 24 V DC +20 %/-5 % according to IEC 742 (functional extra-
low voltage). The max. power consumption of the ISD is 2.5 A per unit.
The AMS 50 is not suitable for supplying units with integrated heater.
3. The following operating voltages for the connection module:
- AMV 50-013 (no. 1 017 137): 230 V AC ±10 % 50 Hz
- AMV 50-012 (no. 1 017 138): 115 V AC ±10 % 50/60 Hz
4. The following connection cables if the connection module is used:
- ISD 230: cable no. 2 013 568 (3 m)
- ISD 260/280: cable no. 6 010 474 (5 m) for function interfaces/power supply.
The data interface will not be connected via the connection module.
5. For each unit a connector cover no. 2 016 130 to match the enclosure rating IP 65.
6. A precise vehicle guidance system if the ISD is to be used in conjunction with rail-
based transportation systems (see T/R angle, Chapter 9 Technical data, Page 49)
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 3
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
13
Product description
3.1.4 Design
Fig. 3-1: Design of an ISD unit
Key:
Optical adjustment aid
(crosshairs)
“Light path interrupted“ LED
Light admission for optical
adjustment aid
Reception lens
Transmission lens
Additional p.c.b. with DIL
switches (type-dependent)
“Power on“, “RxD“ and “TxD“
LEDs
Running nut M 5 (in slot), max.
depth of engagement 10 mm
from surface of housing
ISD 230: 9-pin D Sub
connector (all signals)
ISD 260/280: 9-pin D Sub
socket (data interface)
ISD 260/280 only: 5-pin round
connector (power supply and
function interfaces)
with rear panel removed:
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 3
© SICK AG · Germany · All rights reserved
14
Product description
3.2 Method of operation
The ISD systems each comprise two units with different carrier frequencies. Each of the
components contains an optical data transmitter and receiver as well as a bidirectional,
electrical data interface (Fig. 3-2).
Fig. 3-2: Block diagram: operating principle of the ISD system
With one pair of devices, data can be transmitter and received simultaneously, i.e. data
transfer is possible in both directions. Different carrier frequencies prevent mutual optical
interference.
The data levels pending at the electrical interface of a transmitter (input) are transferred
optically to the opposite station using the FSK modulation method. The receivers on the
other side then reconvert the optical signals to electrical data levels and output them via
the electrical data interface (output).
If you are using the RS 485 interface, both units are ready to receive (RR) in the idle
state
. The station which first receives data on the electrical interface determines the
direction of transmission until the data string has been transmitted. Both stations are
ready to receive again once transmission has been completed (automatic direction
switching). The data transfer rate must only be set on the ISD if you are using the
RS 485 interface.
The light path between the two units is monitored constantly. An LED on the front of each
unit signals interruptions in the light path and inadequate reception conditions. A
switching output, which is active when the light path is unobstructed (free), is provided in
addition to the LED.
Each of the device units in the ISD 230 system is also equipped with a switching output
which is deactivated under poor transmission conditions (e.g. lenses contaminated). The
transmitter on every unit can be deactivated via a switching input.
Electrical
Interface
Electrical
Interface
Distance:
0.2 ... 150/180/200 m
Light path
Station 1
Station 2
Transmitter
Receiver
Transmitter
Receiver
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 3
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
15
Product description
3.3 Indicators and control elements
3.3.1 Control elements
The ISD is configured via jumpers and DIL switches.
The following can be selected (depending on type):
Carrier frequency (ISD 230)
Type of electrical data interface
Data transfer rate
Chapter 5.1 ISD 230 System, Page 22 and Chapter 5.2 ISD 260 and ISD 280 Systems,
Page 33 describe the configuration.
3.3.2 Function of the LEDs
Four LEDs indicate the operating status, the intensity of received signal on the light path
and data transmitting respectively receiving on the electrical interface. The LEDs (Fig. 3-3)
are located on the top of the housing and on the front. Table 3-4 shows the meaning of
the LEDs.
Fig. 3-3: LED indicators on the top of the housing
LED Display Function
Light Yellow-orange Indicates reception states (indicator for intensity of
path received signal), visible from a distance.
interrupted LED lit: no light received from opposite station
(light path interrupted)
LED blinks: reception intensity too weak
LED off: reception ok
PWO Green LED lights up when the unit is switched on
(Power on)
RxD Red LED off: idle level
LED flickers: unit receiving data on the electrical
interface (input)
TxD Yellow LED off: idle level
LED flickers: unit sending data, which it received across
the optical link, on the electrical interface
(output)
Table 3-4: Meaning of LEDs
PWO RxDTxD
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 4
© SICK AG · Germany · All rights reserved
16
Installation
4.1 Installation sequence
Configure the units
Select the mounting locations for the units
Mount the units
Mount the AMS 50 connection modules
Align the units to each other
4.2 Preparations
4.2.1 Configuring the units
Befor mounting the system, configure the units of ISD 230 as decribed in Chapter
5.1 ISD 230 system, Page 22 or the units of ISD 260/280 system as described in
Chapter 5.2 ISD 260 and ISD 280 systems, Page 33. Also prepare the electrical
connection.
4.2.2 Required components
2 units for each ISD system
4.2.3 Required accessories
For each unit one angle bracket no. 2 013 824 or one three-point bracket
no. 5 306 369 (recommended)
- or -
Alternatively, if the bracket is supplied by the user:
- Stable mounting device that allows the alignment of the units to each other to be varied
in the x and y axes as well as the fine adjustment of the units. The weight of an unit is
approx. 1 kg without connection cable(s)
- Max. 4 screws M 5 for one unit. The screw length depends on the wall thickness of the
bracket used. Depth of engagement in CLV max. 10 mm from housing surface
2
srews M 5 x 10 mm to mount an unit on the angle bracket. 3 srews M 5 x 10 mm
(included) to mount an unit on the three-point bracket
2 srews M 6 (included) to mount the angle bracket on the base. 4 srews M 6 (included)
to mount the three-point bracket on the base
AMS 50 connection module (not included in the scope of supply of the ISD)
Connection cables (not included in the scope of supply of the ISD)
4.2.4 Required auxiliary parts
Tool
For large distances a torch for alignment aid
4 Installation
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 4
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
17
Installation
4.2.5 Selecting the mounting location
The system must be mounted in such a way that the straight line of vision between
the two units is unimpaired.
Aligne both units either vertically or horizonally.
Ensure that the adjustment aid (on the top) is easily accessible on both units.
If two ISD systems are operated in parallel, ensure that the units with the same carrier
frequency are mounted diagonally opposite one another.
See also Chapter 5.1.2 Setting the transmission frequencies, Page 22 or Chapter 5.2.2
Transmission frequencies, Page 33.
If the connector cover is used, observe the longer dimensions in summary due to the
cover (see Fig. 10-3, Page 53).
Path length: 0.2 ... 150/180/200 m
Mount the units at an angle of 180° with respect to each other (Fig. 4-1).
The two large lenses must be directly opposite one another.
Fig. 4-1: Mount the two units at a distance of 0.2 ... 150/180/200 m
Path length: 3 ... 150/180/200 m
If the distance between any position on the mobile station and the fixed station is not
less than 3 m, both units can also be mounted in the same plane (device unit not
rotated through 180°).
Table 4-1 shows the transmitter and receiver aperture angle for a device unit. The light
spot diameter of the transmitter depending on the distcance is shown in Table 4-2.
Rotated
through
180° !
Electrical
interface
Electrical
interface
Distance:
0.2 ... 150/180/200 m
Light path
Station 1
Station 2
Transmitter
Receiver
Transmitter
Receiver
Component Aperture angle
Transmitter approx. ± 0.4°
Receiver approx. ± 0.8°
Table 4-1: Aperture angles
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 4
© SICK AG · Germany · All rights reserved
18
Installation
Fig. 4-2: ISD unit with three-point bracket no. 5 306 369 (accessory)
The bracket can be mounted either directly with the rear plate (panel) or via the angled
flange on the mounting base using the 4 holes provided. The position of the holes and
dimensions of the three-point bracket are shown in Fig. 10-1, Page 52. Two reference
markings allow both brackets to be adjusted vertically and horizontally (x and y direction),
irrespective of the position of the angled flange (can be mounted on the other side of the
unit).
4.2.6 Mounting accessories
The units will be mounted at the transmitter/receiver stations using 3 movable running
nuts. On each longitudinal side there are two of them in a slot (see Fig. 3-1, Page 13). The
maximum depth of engagement in the nuts is 10 mm from the surface of the housing. The
location and dimensions of the nuts are shown in Fig. 9-1, Page 50.
An unit can be mounted using the SICK brackets:
angle bracket no. 2 013 824
three-point bracket no. 5 306 369
Three-point bracket
The three-point bracket facilitates mounting and alignment of the units. A separate bracket
is required for each unit (Fig. 4-2).
Distance IR light spot diameter
50 m approx. 0.7 m
100 m approx. 1.4 m
150 m approx. 2.1 m
Table 4-2: Light spot diameter of transmitter
8 008 207/X064/2013-02-15
Operating Instructions
ISD 230/260/280
Chapter 4
© SICK AG · Germany · All rights reserved8 008 207/X064/2013-02-15
19
Installation
4.3 Mounting and adjusting the system
4.3.1 Mounting the ISD on the three-point bracket
Risk of damage to the housing!
The maximum depth of engagement of the two nuts M 5 is 10 mm from housing surface.
Longer screws will damage the housing.
Use screws with the correct length.
1. Prepare the two three-point brackets for either vertical (angled flange left or right) or
horizontal (angled flange top or bottom) mounting.
2. Ensure that the movable plate is parallel to the fixed plate on each bracket before they
are mounted (if necessary correct the position with the lock nuts using for the fine
adjustment).
3. Align both three-point bracket to each other straight to the eye. The system must be
mounted in such a way that the straight line of vision between the two units is
unimpaired.
4. Attach the two brackets at the required height with the four screws (M 6 x 12 mm) and
washers supplied using the angled flange or the fixed plate. Use the reference
markings as reference points with respect to the common reference (floor). Ensure
that the two brackets are aligned horizontally (devices must be in the same axis).
5. Carefully insert a unit into each bracket. The two top screws on the rear of the housing
facing the cover (optical adjustment aid) must fit into the locking holes of the movable
plate so that the bottom of the device (connector) is flush with the bracket (Fig. 4-3).
Check: the reference marking (horizontal) must be at the same height as the two glass
lenses.
Fig. 4-3: Design of the three-point bracket
Locking hole
Lock nut
w/f 10
Reference marking (vertical)
Angled
flange
Reference marking (horizontal)
Movable
plate
Fixed
plate
Unit mounted on
three-point bracket
ATTENTION
Operating Instructions
ISD 230/260/280 IR Data Transmission Systems
Chapter 4
© SICK AG · Germany · All rights reserved
20
Installation
6. Secure the units to the brackets with the three screws M 5 x 10 mm and washers. To
do so, move the running nuts.
You can then perform a fine adjustment in the horizontal and vertical planes using the
three lock nuts (self-locking).
7. Align the units as described in Chapter 4.3.3 Alignment of the ISD.
Device units in fixed and mobile stations (variable link)
For large distances the units have to be mounted in such a way, that in case of vibrations
the cone of IR light will reach the receiver area in the opposite station (fixed) in the middle
(and the same in the other direction). The vibrations can be caused by accelerating and
stopping the mobile station.
Prefer to mount both units vertically using the angled flange or the fixed plate of the
three-point brackets. With a stabil base this position provides an operation poor of
vibrations.
If the units can only be mounted horizontal (due to small place in the locations), use the
4 drilling holes on the fixed plate of the three-point bracket.
4.3.2 Mounting the AMS 50 Connection Module
Mount the connection modules near the units. The maximum distance between the
AMS 50 and an unit should not exceed 10 m, in particular when using the ISD 230 with
the RS 232 data interface.
For detailed informationen on installing and wiring, please refer to the operating
instructions AMV/S 50 Connection Module“ (order no. 8 008 294, English edition).
4.3.3 Alignment of the ISD
Optical adjustment aid
The optical alignment aid facilitates exact alignment of the devices. Crosshairs, which can
be used to focus on the opposite unit, are visible in the opening at the top of the device
(Fig 4-4). At large distances, it also may be useful to attach a torch (with a tape) to the
opposite unit.
The units should be only be aligned (in particular when using the optical adjustment aid)
when the ISD system is switched off.
This is the only way to prevent direct eye contact with the IR beam (eye protection).
Note
Fig. 4-4: Using the optical adjustment aid (crosshairs) on an unit
a) Alignment with the
opposite station (short
distance)
b) Alignment with the
opposite station (large
distance)
PWO TXD RXD
(View from above)
8 008 207/X064/2013-02-15
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

SICK IDS230, ISD260 and ISD280 IR Data Transmission Systems Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI