MEES19K040
EAHV-P-YBL(-H)(-N), EACV-P-YBL(-N)
18
1. Product Specifications
When using a local controller, refer to the table below for the types of input/output signals that are available and the
operations that correspond to the signals.
External Input/Output
Input
type
Dry contact ON (Close) OFF (Open) Terminal block
(a)UNIT OPERATION Run/Stop The unit will go into operation when the water
temperature drops below the preset temperature.
The unit will stop except when the unit is in
the Anti-Freeze mode.
K95-K96
(b)MODE CHANGE
*EAHV-P****YBL
EAHV-P****YBL-H
Heating
ECO/Heating
Heating ECO mode (EAHV-P****YBL: When
"COOLING/HEATING SWITCHING" contact
(item (i) below) is ON, this mode is enabled.)
Heating mode (EAHV-P****YBL: When
"COOLING/ HEATING SWITCHING" contact
(item (i) below) is ON, this mode is enabled.)
K40-K42
(c)FAN MODE Forced/
Normal
When the outdoor temperature is 5ºC or less, the
fan will remain in operation after the compressor
has stopped.
The fan will stop when the compressor
stops.
K91-K92
(d)ANTI FREEZE
*EAHV-P****YBL
EAHV-P****YBL-H
On/Off The unit will operate in the Anti-Freeze mode
(with the target temperature 30ºC) when the
contact status of (a) "UNIT OPERATION" is
"Stop" or the ON/OFF button on the remote
controller is turned off. (EAHV-P****YBL: When
"COOLING/HEATING SWITCHING" contact
(item (i) below) is ON, this mode is enabled.)
The unit will operate according to the status
of the "UNIT OPERATION" contact (item (a)
above) or the ON/OFF command from the
remote controller.
K40-K41
(e)FLOW SWITCH Normal/Error The unit is allowed to operate. The unit will not operate. K23-K24
(f)PUMP INTERLOCK Normal/Error The unit is allowed to operate. The unit will not operate. K01-K02
(g)PEAK-DEMAND
CONTROL
On/Off The unit will operate at or below the maximum
capacity level that was set for the Peak-demand
control setting.
The unit will operate at or below the
maximum capacity.
K23-K25
(h)OUTLET WATER
TEMP SWITCHING
2nd/1st Setting temp 2
(Refer to page 80 Settings table)
Setting temp 1
(Refer to page 80 Settings table)
KC1-KC2
(i)COOLING/HEATING
SWITCHING
*EAHV-P****YBL
Heating/
Cooling
Heating mode Cooling mode K93-K94
Analog Terminal block
Input type Action
(j)WATER TEMP SETTING/
CAPACITY CONTROL SIGNAL
Water temperature or capacity control signal can be set by using the external analog input to
the CN421 on the MAIN circuit board. One analog input type can be selected from the following
types: 4-20 mA, 1-5 V, 0-10 V, or 2-10 V.
*Use a 4-20 mA signal output devise with insulation.
SG1(+)-KG1(-)
(k)EXTERNAL WATER SENSOR 1
(optional) For simultaneous operating group K1-K2
(l)EXTERNAL WATER SENSOR 2
(optional)
For identical water system group K3-K4
Output
type
Contact type Conditions in which the contact closes
(turns on)
Conditions in which the contact opens
(turns off)
Terminal block
(m)ERROR INDICATOR Close/Open The unit has made an abnormal stop. During normal operation K33-K34
(n)OPERATION
INDICATOR
Close/Open The "UNIT OPERATION" contact (item (a) above)
or the ON/OFF button on the remote controller is
ON.
The "UNIT OPERATION" contact (item (a)
above) or the ON/OFF button on the remote
controller is OFF.
K31-K32
(o)PUMP OPERATION
COMMAND
Close/Open The pump will operate according to the status of
the "UNIT OPERATION" contact or the ON/OFF
button on the remote controller button.
Under all conditions other than the ones
listed on the left
K75-K76
(p)SUPPLEMENTARY
HEATER SIGNAL
Close/Open Water and outdoor temperature has dropped
below a setting water temperature and a set
outdoor temperature.
Water temperature is at or above a set
water temperature +2ºC or the outdoor
temperature is at or above a set outdoor
temperature +2ºC.
RP1-RP2
(q)DEFROST SIGNAL Close/Open The unit is in defrost mode. The unit is not in defrost mode. KD1-KD2
(r)DRAIN PAN HEATER
SIGNAL
Close/Open Outdoor temperature has dropped below a set
outdoor temperature.
Outdoor temperature is at or above a set
outdoor temperature +2ºC.
KB1-KB2
(s)HEATING
OPERATION
DISPLAY
Close/Open The unit is in heating mode. The unit is in cooling mode. K38-K39
RC/M-NET REMOTE
CONTROLLER
PAR-W31MAA RA-RB
Centralized controller AE-200 A-B
M-NET - M1-M2