Automatic Voltage Regulation (AVR) circuits maintain 120V nominal output over an input voltage range of 87-140V
Includes 6 fully protected NEMA 5-15R outlets with 2 single outlet load banks that can be individually powered off and back on again via
software interface
PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,
event logging and running user defined script commands
Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces,
or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software
In addition to the contact closure monitoring of on battery, low battery and power restored messaging, built-in RS-232 interface supports
messaging of UPS and line power status, including AC line voltage, DC battery voltage and remaining battery capacity
Supports activate self-test and UPS output power control for delayed or immediate reboot of connected equipment
Diagnostic LEDs (indicate 17 performance conditions)
UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Business) Listed
$250,000 Ultimate Lifetime Insurance (USA & Canada Only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V AC
Frequency
compatibility
60 Hz
OUTPUT
Output VA 2200
Output watts 1700
Output nominal
voltage
120V AC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-13% / +5%)
BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10%
BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 6 NEMA 5-15R
Customized load
management
receptacles
2 individually controlled single-outlet banks supports reboot of selected items and load shedding to increase battery
runtime for the most critical of loads.
Overload protection Via 20A input breaker
INPUT
Maximum input amps 15A, 1770 watts
Input connection type NEMA 5-15P
Input cord length 8 ft., 12 gauge
Recommended
Electrical Service
20A 120V
BATTERY
Full load runtime 11 minutes (2200VA)
Half load runtime 27 minutes (1100VA)
Expandable battery
runtime
Supports extended runtime with optional BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible) external
battery pack. Capacity de-rates to 1600VA / 1280 watts with 1 external BP and 1250VA / 800 watts with 2 external BPs
DC system voltage 24 V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to
maintain usable, computer grade output without consuming battery power.