Napoleon Fireplaces Vittoria GD19N User manual

Category
Fireplaces
Type
User manual

This manual is also suitable for

1
W415-0612 / C / 01.25.08
INSTALLATION AND
OPERATION INSTRUCTIONS
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada (705)721-1212 fax(705)722-6031
www.napoleonreplaces.com [email protected]
GD19N
NATURAL GAS
GD19P
PROPANE
- Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from
a neighbours phone. Follow the gas
suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
- Installation and service must be
performed by a qualified installer, service
agency or the supplier.
SAFETY INFORMATION
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.50 CSA 2.22 FOR VENTED GAS FIREPLACE.
Shown wi
t
hFK
19
If the information in these instructions are
not followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
!
WARNING
INSTALLER: LEAVE THIS MANUAL WTIH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
$10.00
2
W415-0612 / C / 01.25.08
• Do not burn wood or other materials in this replace.
Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or
clothing ignition. Supervise young children when they are in the same room as the replace.
• Clothing or other ammable material should not be placed on or near the replace.
• Due to high temperatures, the replace should be located out of traf c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the replace is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens
and guards must be fastened to the oor.
Any safety screen or guard removed for servicing must be replaced prior to operating the replace.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the replace and venting system
are kept clean. The replace and its venting system should be inspected before use and at least annually by a quali ed service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The replace area must be kept clear
and free from combustible materials, gasoline and other ammable vapours and liquids.
• Under no circumstances should this replace be modi ed.
• This replace must not be connected to a chimney ue pipe serving a separate solid fuel burning appliance.
• Do not use this replace if any part has been under water. Immediately call a quali ed service technician to inspect the replace and to
replace any part of the control system and any gas control which has been under water.
• Do not operate the replace with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed
or quali ed service person.
• Do not strike or slam shut the replace glass door.
• This replace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
• Pressure relief doors must be kept closed while the replace is operating to prevent exhaust fumes containing carbon
monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause
the surrounding combustible materials to overheat and catch re.
• Only doors/optional fronts certi ed with the appliance shall be used.
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
TABLE of CONTENTS
RETAIN THIS MANUAL FOR FUTURE REFERENCE
PG 2-5 INTRODUCTION
Warranty
General Instructions
General Information
Care of Glass and Plated Parts
Dimensions
5-15 VENTING
Venting Lengths and Air Terminal Locations
Typical Vent Installations
Special Vent Installations
Minimum Air Terminal Location Clearances
Venting Application Flow Chart
Venting Speci cations
Top Exit Conversion
16-23 INSTALLATION
Wall and Ceiling Protection
Horizontal Installation
Vertical Installation
Using Flexible Vent Components
Fireplace Vent Connection
Using Rigid Vent Components
Restricting Vertical Vents
Mobile Home Installation
Gas Installation
Optional Wall Switch Installation
Framing
Minimum Mantel and Enclosure Clearances
24 FRONT FACING AND INSERT KIT
25 BLOWER INSTALLATION
25 NIGHT LIGHT
TM
REPLACEMENT
26-27 FINISHING
Glass Door Installation and Removal
Log Placement
Logo Placement
Control Functions
28 WIRING DIAGRAM
29 OPERATION / MAINTENANCE
Operating Instructions
Maintenance
30 ADJUSTMENTS
Pilot Injector and Ori ce Replacement
Venturi Adjustment
Flame Adjustment
Flame Characteristics
31-32 REPLACEMENTS
Ordering Replacement Parts
Replacement Parts
Terminal Kits
Accessories
33-34 TROUBLE SHOOTING GUIDE
35 SERVICE HISTORY
36 NOTES
!
WARNING
3
W415-0612 / C / 01.25.08
NAPOLEON® products are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certifi cate.
NAPOLEON® products are designed with superior components and materials, assembled by trained
craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fi red at
a quality test station. The complete fi replace is test-fi red and thoroughly inspected by a qualifi ed techni-
cian before packaging to ensure that you, the customer, receives the quality product that you expect from
NAPOLEON®
.
NAPOLEON® GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new NAPOLEON® gas fi replace are warranted against
defects for as long as you own the fi replace. This covers: combustion chamber, heat exchanger, stainless steel
burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing,
porcelainized enamelled components and aluminium extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON® will
provide replacement parts free of charge during the fi rst year of the limited warranty. Light bulbs are not covered
by this warranty.
Labour related to warranty repair is covered free of charge during the fi rst year. Repair work however, requires
the prior approval of an authorized company of cial. Labour costs to the account of Napoleon® are based on a
predetermined rate schedule and any repair work must be done through an authorized Napoleon® dealer.
CONDITIONS AND LIMITATIONS
NAPOLEON® warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity
(registered customer) whose name appears on the warranty registration card led with NAPOLEON® -- provided that the purchase was
made through an authorized NAPOLEON® dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas replace must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance
with the installation instructions included with the product and all local and national building and re codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and
parts installed from other manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and
chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting com-
ponents used in the installation of the replace.
NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following condi-
tions: During the rst 10 years NAPOLEON® will replace or repair the defective parts at our option free of charge. From 10 years to life,
NAPOLEON® will provide replacement burners at 50% of the current retail price.
In the rst year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workman-
ship provided that the product has been operated in accordance with the operation instructions and under normal conditions.
After the rst year, with respect to this President's Limited Lifetime Warranty, NAPOLEON® may, at its discretion, fully discharge
all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but
defective part(s).
After the rst year, NAPOLEON® will not be responsible for installation, labour or any other costs or expenses related to the reinstal-
lation of a warranted part, and such expenses are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON®’S responsibility under this war-
ranty is de ned as above and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty de nes the obligations and liability of NAPOLEON® with respect to the NAPOLEON® gas replace and any other war-
ranties expressed or implied with respect to this product, its components or accessories are excluded.
NAPOLEON® neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this
product. NAPOLEON® will not be responsible for: over- ring, downdrafts, spillage caused by environmental conditions such as rooftops,
buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting con gurations, insuf cient makeup air, or
negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to replace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long
periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON®.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your
authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON® reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty
claim.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGIS-
TERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD. THIS PRODUCT HAS AN INDUSTRIAL DESIGN
REGISTRATION
4
W415-0612 / C / 01.25.08
FOR YOUR SATISFACTION, THIS FIREPLACE HAS
BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column
for natural gas and 11 inches water column for propane.
Maximum inlet gas pressure is 7 inches water column for
natural gas and 13 inches water column for propane. When
the valve is set to "HI", the manifold pressure under ow
conditions is 3.5 inches water column for natural gas and
10 inches water column for propane. When the replace is
installed at elevations above 4,500ft, and in the absence of
speci c recommendations from the local authority having
jurisdiction, the certi ed high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000ft.
Expansion / contraction noises during heating up and cooling
down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for use
with other gases, unless a certi ed kit is used.
Maximum input is 11,500 BTU/hr for natural gas. Maximum
output for natural gas is 8,600 BTU/hr at an ef ciency of 75%.
Maximum input is 11,000 BTU/hr for propane. Maximum output
for propane gas is
8,250 BTU/hr at an ef ciency of 75%.
Provide adequate accessibility clearance for servicing and
operating the replace.
Never obstruct the front opening of the replace.
Provided that the clearance to combustibles are achieved,
the most desirable and bene cial location for a Napoleon®
replace is in the centre of a building, thereby allowing
the most ef cient use of the heat created. The location of
windows, doors and the traf c ow in the room where the
replace is to be located should be considered. If possible,
you should choose a location where the vent will pass
through the house without cutting a oor or roof joist.
RATING LABEL LOCATION: The rating label is located
under the control panel and is chained to the replace.
DO NOT REMOVE.
THIS GAS FIREPLACE SHOULD BE INSTALLED AND
SERVICED BY A QUALIFIED INSTALLER to conform with
local codes. Installation practices vary from region to region
and it is important to know the speci cs that apply to your
area,
for example: in Massachusetts State:
The replace damper must be removed or welded in the open
position prior to installation of a replace insert or gas log.
A carbon monoxide detector is required in all rooms containing
gas red appliances.
The appliance off valve must be a “T” handle gas cock.
The exible connector must not be longer than 36 inches.
The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
WARNING: This product must be installed by a licensed
plumber or gas tter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install to the current CAN1-B149
Installation Code in Canada or to the National Fuel Gas
Code, ANSI Z223.1, and NFPA 54 in the United States.
Mobile home installation must conform with local codes. In
the absence of local codes, install to the current standard for
gas equipped mobile housing CAN/CSA Z240 MH Series in
Canada or the manufactured home construction and safety
standard, Title 24 CFR, part 3280, or the Fire Safety Criteria
for manufactured home installations, Sites and Community
Standard ANSI/NFPA 501A in the United States.
Objects placed in front of the replace must be kept a
minimum of 48" away from the front face of the unit.
The fireplace and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of ½ psig (3.5 kPa). The replace must be isolated from the
gas supply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than ½ psig
(3.5 kPa).
When the replace is installed directly on carpeting, vinyl tile
or other combustible material other than wood ooring, the
replace shall be installed on a metal or wood panel extending
the full width and depth.
The fireplace, when installed with a blower, must be
electrically connected and grounded in accordance with
local codes. In the absence of local codes, use the current
CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or
the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the
United States.
GENERAL INSTRUCTIONS GENERAL INFORMATION
CARE OF GLASS AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly
with a clean dry cloth.
The glass is
3
/
16
" ceramic glass available from your Napoleon®
/ Wolf Steel Ltd. dealer. DO NOT SUBSTITUTE MATERIALS.
Clean the glass after the rst 10 hours of operation with a
recommended gas replace glass cleaner. Thereafter clean
as required. DO NOT CLEAN GLASS WHEN HOT! If the
glass is not kept clean permanent discolouration and / or
blemishes may result.
5
W415-0612 / C / 01.25.08
33
1
/
8
4” DIA.
7” DIA.
13”
15
3
/
8
12”
26
3
/
8
34
1
/
8
34
1
/8
33
7
/
8
9
1
/
2
5”
2
1
/
2
1
3
/
4
GAS
LINE
ACCESS
ELECTRICAL
ACCESS
4” DIA.
7” DIA.
10
1
/
4
20
1
/
2
19
3
/
4
21
3
/
4
9”
DIMENSIONS
FIGURE 1a
VENTING
VENTING LENGTHS AND AIR TERMINAL LOCATIONS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct
Temp or American Metal Amerivent venting components.
Minimum and maximum vent lengths, for both horizontal
and vertical installations, and air terminal locations for either
system are set out in this manual and must be adhered to.
For Simpson Dura-Vent, Selkirk Direct Temp and American
Metal Amerivent, follow the installation procedure provided
with the venting components.
For vent systems that provide seals on the inner exhaust ue,
only the outer air intake joints must be sealed using red high
temperature silicone (RTV). this same sleant may be used
on both the inner exhaust and outer intake vent pipe joints of
all other approved vent systems except for the exhaust vent
pipe connection to the replace ue collar which must be
sealed using the black high temperature sealant Mill Pac.
The connection between the adaptor for these systems and
the replace ue collar must be sealed using the black high
temperature sealant Mill Pac (not supplied).
A starter adaptor must be used with the following vent
systems and may be purchased from the corresponding
supplier:
PART 4"/7" SUPPLIER
Duravent W175-0053 Wolf Steel
Amerivent 4DSC-N2 American Metal
Direct Temp 4DT-AAN Selkirk
For Simpson Dura-Vent, Selkirk Direct Temp and American
Metal Amerivent, follow the installation procedure found
on the website for your venting supplier:
VENTING SUPPLIER WEBSITE ADDRESS
Simpson Dura-Vent www.duravent.com
Selkirk Direct Temp www.selkirkcorp.com
American Metal Amerivent www.americanmetalproducts.com
FIGURE 1b
FIGURE 1c
FIGURE 1d
FIGURE 1e
FIGURE 1f
6
W415-0612 / C / 01.25.08
For safe and proper operation of the replace follow the venting instruction exactly.
Deviation from the minimum or the maximum vertical vent length can create dif culty in burner start-up and/or
carboning.
Under extreme vent con gurations, allow several minutes (5-15) for the ame to stabilize after ignition.
Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation
wrapped in a protective sleeve to minimize condensation.
Provide a means for visually checking the vent connection to the replace after the replace is installed.
Use a restop, vent pipe shield or attic insulation shield when penetrating interior walls, oor or ceiling.
FOR SPECIFIC VENTING PARAMETERS, REFER TO
PAGES 10-15.
When using Wolf Steel venting components, use only
approved Wolf Steel rigid / exible components with the
following termination kits:Wall Terminal Kit GD222, or
1/12 to 7/12 Pitch Roof Terminal Kit GD110, 8/12 to 12/12
Roof Terminal Kit GD111, Flat Roof Terminal Kit GD112 or
Periscope Kit GD201 (for wall penetration below grade).
With exible venting, in conjunction with the various
terminations, use either the 5 foot Vent Kit GD220 or the 10
foot Vent Kit GD330.
The maximum allowable vertical vent length is 35 feet,
the minimum is 3 feet.
For optimum ame appearance and replace performance,
keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify that it
is unobstructed and undamaged.
Horizontal runs may have a 0" rise per foot in all cases using
Wolf Steel or Simpson Dura-Vent rigid, Selkirk Direct Temp,
American Metal Amerivent or Wolf Steel exible venting
components when venting.
For optimum performance, it is recommended that horizontal
runs have a minimum 1" rise per foot when using any of
these vent systems.
Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and
American Metal Amerivent venting systems must not be
combined.
VENTING LENGTHS AND AIR TERMINAL LOCATIONS CONTINUED
VENT INSTALLATIONS
HORIZONTAL VENT SECTIONS
A minimum clearance of 1" at the bottom and sides and 2" at the top of the vent pipe in all horizontal runs to
combustibles is required. Use restop spacer W010-1774 (supplied).
VERTICAL VENT SECTIONS
A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clearances
in replace enclosures. See "Minimum Enclosure Clearances" section. Use restop spacer W500-0096 (not
supplied).
7
W415-0612 / C / 01.25.08
Use the GD201 periscope kit to locate the air termination
above grade. The periscope must be installed so that when
nal grading is completed, the bottom air slot is located a
minimum of 12" above grade. The maximum allowable vent
length is 10 ft.
16”
MINIMUM
35 FT MAXIMUM
3 FT MINIMUM
16”
MINIMUM
35 FT MAXIMUM
3 FT MINIMUM
FIGURE 4a
The maximum vent length for a corner installation is 20" of
horizontal run, in addition to the 45° offset. In this case zero
rise is acceptable when using rigid. See FIGURE 5a. Flexible
venting must maintain a 6" rise. See FIGURE 5b.
TYPICAL VENT INSTALLATIONS
PERISCOPE TERMINATION CORNER TERMINATION
FIGURE 5b
FIGURE 5a
FIGURE 4b
FIGURE 2a
FIGURE 3a
FIGURE 2b
FIGURE 3b
24" MAXIMUM
20" MAXIMUM
26
3
/8" MINIMUM
PLUS RISE*
10"
MINIMUM
43
1
/8" MINIMUM
PLUS RISE*
24”
MINIMUM
12”
MINIMUM
24”
MINIMUM
12”
MINIMUM
TOP EXIT INSTALLATION
REAR EXIT INSTALLATION
MAXIMUM 10FT VENT LENGTH
20” MAXIMUM
6” RISE
MINIMUM
* Refer to "Venting"
section.
TOP EXITREAR EXIT
SPECIAL VENT INSTALLATIONS
33
1
/8"
8
W415-0612 / C / 01.25.08
FIGURE 6
MINIMUM AIR TERMINAL LOCATION CLEARANCES
9
W415-0612 / C / 01.25.08
VENTING APPLICATION FLOW CHART
FIREPLACE VENT EXIT
REAR EXIT
TOP EXIT
Horizontal Termination
Vertical Termination
Vertical Termination
Vertical rise
is equal to
or greater
than the
horizontal
run
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
Horizontal
run + verti-
cal rise to
maximum of
24.75 feet
3.5 times the
vertical rise
equal to or
greater than
the horizon-
tal run
Horizontal Termination
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
3 times the
vertical rise
equal to or
greater than
the horizon-
tal run
vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum of
24.75 feet
4.2 times the
vertical rise
equal to or
greater than
the horizon-
tal run
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 35 feet
3 times the
vertical rise
equal to or
greater than
the horizon-
tal run
10
W415-0612 / C / 01.25.08
90°
90°
90°
H
1
V
2
H
2
V
1
n guration (only one 90° elbow)
Simple venting con guration
(only one 90° elbow)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
For vent con gurations requiring more than one 90° elbow,
the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 35 feet
Example 1:
V
1
= 3 ft
V
2
= 8 ft
V
T
=
V
1
+
V
2
=
3 + 8 = 11 ft
H
1
= 2.5 ft
H
2
= 2 ft
H
R
= H
1
+ H
2
= 2.5 + 2 = 4.5 ft
H
O
= .
03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4
ft
H
T
= H
R
+ H
O
= 4.5 + 5.4 = 9.9 ft
H
T
+ V
T
= 9.9 + 11 = 20.9 ft
Formula 1: H
T
< V
T
9.9 < 11
Formula 2: H
T
+ V
T
< 35 feet
20.9 < 35
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 8
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
For the following symbols used in the venting calculations
and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H
T
- total of both horizontal vent lengths (H
R
) and offsets
(H
O
) in feet
H
R
- combined horizontal vent lengths in feet
H
O
- offset factor: .03(total degrees of offset - 90°*) in
feet
V
T
- combined vertical vent lengths in feet
feet inches
0.03 0.5
15° 0.45 6.0
30° 0.9 11.0
45° 1.35 16.0
90°* 2.7 32.0
* the rst 90° offset has a zero value and is shown in the
formula as -90°
DEFINITIONS
ELBOW VENT LENGTH VALUES
TOP EXIT / HORIZONTAL TERMINATION
FIGURE 7
0
2.5 5 7.5 10 12.5 15
35
10
20
30
17.5 20
33.3
17.5
.5
(H
T
) < (V
T
)
REQUIRED
VERTICAL
RISE IN
FEET V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
11
W415-0612 / C / 01.25.08
H
2
H
4
V
2
90°
H
3
H
1
V
1
90°
90°
H
2
H
1
V
1
Simple venting con guration
(only one 90° elbow)
Example 2:
V
1
= V
T
= 6 ft
H
1
= 3 ft
H
2
= 5 ft
H
R
= H
1
+ H
2
= 3 + 5 = 8 ft
H
O
= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft
H
T
= H
R
+ H
O
= 8 + 2.7 = 10.7 ft
H
T
+ V
T
=
10.7 + 6 =16.7
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2 x 6 = 25.2 ft
10.7 < 25.2
Formula 2: H
T
+ V
T
< 24.75 feet
16.7 < 24.75
Since both formulas are met, this vent configuration is
acceptable.
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
Example 3:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
= V
1
+ V
2
= 4 + 1.5 = 5.5 ft
H
1
= 2 ft
H
2
= 1 ft
H
3
= 1 ft
H
4
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2 + 1 + 1 + 1. 5 = 5.5 ft
H
O
= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft
H
T
= H
R
+ H
O
= 5.5 + 8.1 = 13.6 ft
H
T
+ V
T
= 13.6 + 5.5 = 19.1 ft
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2 x 5.5 = 23.1 ft
13.6 < 23.1
Formula 2: H
T
+ V
T
< 24.75 feet
19.1 < 24.75
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 9
FIGURE10
FIGURE 11
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
TOP EXIT / HORIZONTAL TERMINATION
20
10
051015
90
100
120
110
30
40
50
60
70
80
130
140
150
20
(H
T
) > (V
T
)
For vent con gurations requiring more than one 90° elbow
the following formulas apply:
Formula 1: H
T
< 4.2 V
T
Formula 2: H
T
+ V
T
< 24.75 feet
REQUIRED
VERTICAL
RISE IN
INCHES V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
12
W415-0612 / C / 01.25.08
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
For vent con gurations requiring more than two 90° elbows
the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 35 feet
Example 4:
FIGURE 12
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
REAR EXIT / HORIZONTAL TERMINATION
Simple venting con guration
(only two 90° elbows)
FIGURE 13
H
3
90°
90°
90°
V
2
H
1
V
1
H
2
V
1
= 9 ft
V
2
= 6 ft
V
T
=
V
1
+
V
2
=
9 + 6 = 15 ft
H
1
= 3 ft
H
2
= 2 ft
H
3
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
= 3 + 2 + 1.5 = 6.5 ft
H
O
= .03(four 90° elbows - 90°)
= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
= H
R
+ H
O
= 6.5 + 8.1 = 14.6 ft
H
T
+ V
T
= 14.6 + 15 = 29.6 ft
Formula 1: H
T
< V
T
14.6 < 15
Formula 2: H
T
+ V
T
< 35 feet
29.6 < 35
Since both formulas are met, this vent con guration is
acceptable.
0
2.5 5 7.5 10 12.5 15
35
10
20
30
17.5
20
33.3
17.5
.5
(H
T
) < (V
T
)
REQUIRED
VERTICAL
RISE IN
FEET V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
13
W415-0612 / C / 01.25.08
H
1
H
2
V
1
V
2
90°
45°
90°
90°
Simple venting con guration
(only two 90° elbows)
Example 5:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
=
V
1
+
V
2
=
4 + 1.5 = 5.5 ft
H
1
= 2 ft
H
2
= 1 ft
H
3
= 1 ft
H
4
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2 + 1 + 1 + 1.5 = 5.5 ft
H
O
= .03(four 90° elbows + one 45° elbow - 90°)
= .03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft
H
T
= H
R
+ H
O
= 5.5 + 9.45 = 14.95 ft
H
T
+ V
T
= 14.95 + 5.5 = 20.45 ft
Formula 1: H
T
< 3.5V
T
3.5V
T
=
3.5 x
5.5 = 19.25 ft
14.95 < 19.25
Formula 2: H
T
+ V
T
< 24.75 feet
20.45 < 24.75
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 15
For vent con gurations requiring more than two 90° elbows
the following formulas apply:
Formula 1: H
T
< 3.5V
T
Formula 2: H
T
+ V
T
< 24.75 feet
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
FIGURE 14
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
REAR EXIT / HORIZONTAL TERMINATION
H
3
H
4
90°
0
10
515
100
50
150
3.4
19.12.5
12
66
147
(H
T
) > (V
T
)
REQUIRED
VERTICAL
RISE IN
INCHES V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
14
W415-0612 / C / 01.25.08
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
Example 6:
V
1
= 3 ft
V
2
= 6 ft
V
3
= 8 ft
V
T
=
V
1
+
V
2
+
V
3
=
3 + 6 + 8 = 17 ft
H
1
= 2 ft
H
2
= 2.5 ft
H
R
= H
1
+ H
2
= 2 + 2.5 = 4.5 ft
H
O
= .03(four 90° elbows - 90°)
= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
= H
R
+ H
O
= 4.5 + 8.1 = 12.6 ft
H
T
+ V
T
= 12.6 + 17 = 29.6 ft
Formula 1: H
T
< V
T
12.6 < 17
Formula 2: H
T
+ V
T
< 35 feet
29.6 < 35
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 16
For vent con gurations requiring more than zero 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 35 feet
ple venting con gurations
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
TOP OR REAR EXIT VERTICAL TERMINATION
90°
90°
90°
H
2
V
3
90°
FIGURE 17
V
1
0
5101520
35
10
20
30
3
17.5
17.5
(H
T
) < (V
T
)
H
1
V
2
REQUIRED
VERTICAL
RISE IN
FEET V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
15
W415-0612 / C / 01.25.08
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
For vent con gurations requiring more than two 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:
Formula 1: H
T
< 3V
T
Formula 2: H
T
+ V
T
< 35 feet
Simple venting con gurations
FIGURE 18
Example 7:
V
1
= 2 ft
V
2
= 1 ft
V
3
= 1.5 ft
V
T
=
V
1
+
V
2
+
V
3
=
2 + 1 + 1.5 = 4.5 ft
H
1
= 6 ft
H
2
= 2 ft
H
R
= H
1
+ H
2
= 6 + 2 = 8 ft
H
O
= .03(four 90° elbows - 90°)
= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
= H
R
+ H
O
= 8 + 8.1 = 16.1 ft
H
T
+ V
T
= 16.1 + 4.5 = 20.6 ft
Formula 1: H
T
< 3V
T
3V
T
=
3 x
4.5 = 13.5 ft
16.1 > 13.5
Since this formula is not met, this vent con guration is
unacceptable.
Formula 2: H
T
+ V
T
< 35 feet
20.6 < 35
Since only formula 2 is met, this vent con guration
is unacceptable and a new replace location or vent
con guration will need to be established to satisfy both
formulas.
Example 8:
V
1
= 1.5 ft
V
2
= 5 ft
V
T
=
V
1
+
V
2
=
1.5 + 5 = 6.5 ft
H
1
= 1 ft
H
2
= 1 ft
H
3
= 10.75 ft
H
R
= H
1
+ H
2
+ H
3
= 1 + 1 + 10.75 = 12.75 ft
H
O
= .03(three 90° elbows + one 45° elbow - 90°)
= .03(90 + 90 + 90 + 45 - 90) = 6.75 ft
H
T
= H
R
+ H
O
= 12.75 + 6.75 = 19.5 ft
H
T
+ V
T
= 19.5 + 6.5 = 26 ft
Formula 1: H
T
< 3V
T
3V
T
=
3 x
6.5 = 19.5 ft
19.5 = 19.5
Formula 2: H
T
+ V
T
< 35 feet
26 < 35
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 19
FIGURE 17
H
1
H
2
V
3
V
1
90°
90°
90°
90°
H
2
H
3
V
1
V
2
90°
45°
90°
H
1
90°
V
2
(H
T
) > (V
T
)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED
VERTICAL
RISE IN
FEET V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
16
W415-0612 / C / 01.25.08
In order to convert the venting con guration from a rear exit to a top exit, remove the components as illustrated:
When reinstalling in the alternate position: Check gaskets for tears, replace if necessary to ensure a proper seal.
TOP EXIT CONVERSION
FIGURE 18
4” Collar
4” Gasket
7” Collar
7” Gasket
4” Gasket
4” Cover Plate
7” Gasket
7” Cover Plate
7” Top Access Plate
Outer Top
17
W415-0612 / C / 01.25.08
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
INSTALLATION
WALL AND CEILING PROTECTION
FIGURE 19
This application occurs when venting through an exterior
wall. Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall 9 7/8" wide
by 11 3/8" high to accommodate the restop assembly. Dry
t the restop assembly before proceeding to ensure the
brackets on the rear surface t to the inside surface of the
horizontal framing. Firestop spacer and shield do not limit
the thickness of a wall. For wall construction when using less
than 2" x 6" framing, the shield must be cut to suit.
As an alternative to framing, the vent pipe can be enclosed
in the wall using Napoleon
®
vent sleeve VS47KT.
NOTE: THE FIRESTOP ASSEMBLY MUST BE
INSTALLED WITH THE VENT SHIELD TO THE TOP.
The length of the vent shield may be cut shorter for combustible
walls that are less than 8 1/2" thick but the vent shield must
extend the full depth of the combustible wall.
1. Apply a bead of caulking (not supplied) around the corner
edge of the inside surface of the restop assembly, t the
restop assembly to the hole and secure using the 4 screws
(W570-0026) supplied in your manual baggie.
2. Once the vent pipe is installed in its nal position, apply
high temperature sealant W573-0002 (not supplied) between
the pipe and the restop.
NOTE: DO NOT FILL THE CAVITY BETWEEN THE PIPE
/ LINER AND THE FIRESTOP SLEEVE WITH ANY TYPE
OF MATERIAL.
FIGURES 21a&b
FIRESTOP
UNDERSIDE OF JOIST
9
3
/4
9
3
/4
FIGURE 20
For optimum performance, it is recommended that
horizontal runs have a minimum 1" rise per foot when
using Simpson Dura-Vent, Selkirk Direct Temp,
American Metal Amerivent, or Wolf Steel rigid or
exible vent components.
For safe and proper operation of the replace,
follow the venting instructions exactly.
CAULKING
VENT PIPE
SHIELD
VENT
PIPE
COLLAR
VENT PIPE
SHIELD
This application occurs when venting through a roof.
Installation kits for various roof pitches are available from
your Napoleon® dealer. See Accessories to order the speci c
kit required.
1. Determine the air terminal location, cut and frame a 9
3/4" square opening in the ceiling and the roof to provide
the minimum clearance between the vent pipe and any
combustible material. Try to center the vent pipe location
midway between two joists to prevent
having to cut them. Use a plumb bob to
line up the center of the openings.
Do not ll this space with any
type of material.
A vent pipe shield will prevent any materials such as insulation,
from lling up the 1" air space around the pipe. Nail headers
between the joist for extra support.
2. Apply a bead of caulking (not supplied) to the framework
or to the Wolf Steel vent pipe shield plate or equivalent (in the
case of a nished ceiling), and secure over the opening in
the ceiling. A restop must be placed on the bottom of each
framed opening in a roof or ceiling that the venting system
passes through. Apply a bead of caulking all around and
place a restop spacer over the vent shield to restrict cold
air from being drawn into the room or around the replace.
Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe is installed
in its nal position, apply sealant between the pipe and the
restop assembly.
3. In the attic, slide the vent
pipe collar down to cover up
the open end of the shield and
tighten. This will prevent any
materials, such as insulation,
from lling up the 1" air space
around the pipe.
18
W415-0612 / C / 01.25.08
Use only approved exible vent pipe kits marked:
“Wolf Steel Approved Venting” as
identi ed by the stamp only on the
7” exible vent pipe.
FIGURE 24
USING FLEXIBLE VENT COMPONENTS
FIGURES 22a&b
Six inches (6") is the minimum bend radius allowed for
the seven inch (7") diameter exible vent pipe.
For optimum performance it is recommended that all
horizontal runs have a minimum 1" rise per foot using
exible vent components.
ELBOW
SPACERS
1. Fasten the roof support to the roof using the screws provided. The roof support is optional. In this case the venting is to
be adequately supported using either an alternate method suitable to the authority having
jurisdiction or the optional roof support. Figure 25.
2. Stretch the 4" exible vent pipe to the required length. Slip the 4" exible vent pipe
a minimum of 2” over the inner sleeve of the air terminal connector and secure with 3 #8
screws. Seal using a heavy bead of high temperature sealant W573-0007 (not supplied).
Figure 26.
NOTE: If using pipe clamps to connect vent components, 3 screws must also
be used to ensure the connection cannot slip off.
3. Repeat using the 7" exible vent pipe, using a heavy bead of high temperature
sealant W573-0002 (not supplied). Figure 26.
ROOF SUPPORT
FIGURE 25
VERTICAL AIR TERMINAL INSTALLATION
7” FLEXIBLE
VENT PIPE
7” COUPLER
4”
FLEXIBLE
VENT PIPE
#8 X 1/2”
SELF DRILLING
SCREWS AND
WASHERS
4” COUPLER
HIGH
TEMPERATURE
SEALANT
7” FLEXIBLE
VENT PIPE
SCREWS
#10x2"
VENT PIPE
2" OVERLAP
7" FLEXIBLE
4" FLEXIBLE
VENT PIPE
CAULKING
ATTENTI
ON-
CHAUD
CAUT
ION - HOT
HIGH TEMPERATURE
SEALANT
FIGURE 23
1. Stretch the 4" exible vent pipe to the required length taking into
account the additional length needed for the nished wall surface. Slip
the vent pipe a minimum of 2" over the inner sleeve of the air terminal
and secure with 3 #8 screws. Apply a heavy bead of the high temperature
sealant W573-0007 (not supplied).
NOTE: If using pipe clamps to connect vent components, 3 screws
must also be used to ensure the connection cannot slip off.
2. Using the 7" exible vent pipe, slide over the outer combustion air
sleeve of the air terminal and secure with 3 #8 screws. Seal using high
temperature sealant W573-0002 (not supplied).
3. Insert the vent pipes through the restop maintaining the required
clearance to combustibles. Holding the air terminal (lettering in an upright,
readable position), secure to the exterior wall and make weather tight by
sealing with caulking (not supplied).
4. If more vent pipe needs to be used to reach the replace, couple them
together as illustrated. The vent system must be supported approximately
every 3 feet for both vertical and horizontal runs. Use noncombustible
strapping to maintain the minimum 1" clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall
or siding by 1½", the depth of the return ange.
HORIZONTAL AIR TERMINAL INSTALLATION
For safe and proper operation of the replace, follow the venting instructions exactly.
Do not allow the 4" flexible vent pipe
to bunch up on horizontal or vertical
runs and elbows. Keep it pulled
tight. A 1 1/4” air gap between the 4"
and 7" flexible vent pipes all around
is required for safe operation. A
spacer is required at the start, middle
and end of each elbow to ensure this
gap is maintained. Spacers are
attached to the 4" flexible vent pipe
at predetermined intervals to
maintain a 1-1/4” air gap to the 7"
flexible vent pipe. These spacers
must not be removed.
!
WARNING
For safe and proper operation of the replace, follow the venting instructions exactly.
All 4" exible vent pipe and 7" exible vent pipe joints may be sealed using high temperature sealant W573-0002
(not supplied) or the high temperature sealant W573-0002 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint connecting the 4" exible vent and the exhaust
ue collar.
19
W415-0612 / C / 01.25.08
CAULKING
#10x2"
SCREWS
HIGH
TEMPERATURE
SEALANT
#8 x 1/2"
SCREWS
7" RIGID
VENT PIPE
2" OVERLAP
4" RIGID
VENT PIPE
ATTE
NTION-CH
AUD
CAUTI
ON - H
OT
FIGURE 29
1. Move the replace into position. Measure the vent length required
between terminal and replace taking into account the additional length
needed for the nished wall surface and any 1¼" overlaps between vent-
ing components.
2. Apply high temperature sealant W573-0007 (not supplied) to the outer
edge of the 4" inner collar of the replace. Attach the rst 4" rigid vent pipe
component and secure using 3 self tapping screws. Repeat using the 7"
rigid vent pipe component.
NOTE: Before attaching elbows to the collars on the back of the
replace, 1 1/2" will need to be trimmed off the 4" collar.
3. Holding the air terminal (lettering in an upright, readable position), insert into
both vent pipes with a twisting motion to ensure that both the terminal sleeves engage
into the vent pipes and the sealant. Secure the terminal to the exterior wall and make weather tight by sealing with
caulking (not supplied).
The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return
ange.
STORM
COLLAR
FLASHING
CAULKING
WEATHER
SEALAN
T
2”
AIR INLET
BASE
FIGURE 27
1. Install the 4" exible vent pipe to the replace. Secure with 3 screws and
at washers. Seal the joint and screw holes using the high temperature sealant
W573-0007 (not supplied).
2. Install the 7" exible vent pipe to the replace. Attach and seal the joints
using the high temperature sealant W573-0002 (not supplied).
FIREPLACE VENT CONNECTION
FIGURE 28
2” OVERLAP
HIGH TEMPERATURE
SEALANT
#8 X 1/2”
SELF
DRILLING
SCREWS
4. Thread the air terminal connector / vent pipe assembly down through the roof. The air
terminal must be located vertically and plumb. Attach the air terminal connector to the roof
support, ensuring that the top of the air terminal is 16” above the highest point that it penetrates
the roof. Figure 27. DO NOT CLAMP THE FLEXIBLE VENT PIPE.
5. Remove nails from the shingles, above and to the sides of the chimney. Place the ashing
over the air terminal connector leaving a min. 3/4” of the air terminal connector showing
above the top of the ashing. Slide the ashing underneath the sides and upper edge of
the shingles. Ensure that the air terminal connector is properly centred within the ashing,
giving a 3/4” margin all around. Fasten to the roof. Do
not nail through the lower portion of the ashing. Make
weather-tight by sealing with caulking. Where possible,
cover the sides and top edges of the ashing with roo ng
material. Figure 27.
6. Aligning the seams of the terminal and air terminal
connector, place the terminal over the air terminal
connector making sure the vent pipe goes into the hole in the terminal. Secure with
the three screws provided. Figure 27.
7. Apply a heavy bead of weatherproof caulking 2" above the ashing. Note: Maintain
a minimum 2” space between the air inlet base and the storm collar. Install the storm
collar around the air terminal and slide down to the caulking. Tighten to ensure that a
weather-tight seal between the air terminal and the collar is achieved. Figure 27.
8. If more vent pipe needs to be used to reach the replace, couple them together
as illustrated. The vent system must be supported approximately every 3 feet for both
vertical and horizontal runs. Use noncombustible strapping to maintain the minimum
1" clearance to combustibles. Figure 24.
4” FLEXIBLE
VENT PIPE
7” FLEXIBLE
VENT PIPE
INNER
PIPE
HIGH
TEMPERATURE
SEALANT
AIR
TERMINAL
CONNECTOR
FIGURE 26
USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Wolf Steel vent
spacers W615-0033 every 3 feet on either side of each elbow to maintain the minimum 1¼" clearance between the 7" rigid
vent pipe and 4" rigid vent pipes. Use Napoleon® support ring assembly W010-0370 or equivalent noncombustible strapping
to maintain the minimum clearance to combustibles for both vertical and horizontal runs.
HORIZONTAL AIR TERMINAL INSTALLATION
20
W415-0612 / C / 01.25.08
REAR VENT APPLICATION: Attach 4" and 7" elbows to
the replace. Secure with 3 screws and seal the joints and
screw heads using high temperature sealant. Proceed to
step 1 below.
TOP VENT APPLICATION:
1. Move the replace into position.
2. Fasten the roof support to the roof using the screws
provided.The roof support is optional. The venting is to
be adequately supported using either an alternate method
suitable to the authority having jurisdiction or the optional
roof support.
3. Apply high temperature sealant W573-0007 (not
supplied) to the outer edge of the inner pipe of the air terminal
connector. Slip the 4" rigid vent pipe pipe a minimum of 2"
over the inner pipe of the air terminal connector and secure
using 3 screws.
4. Apply high temperature sealant W573-0002 (not
supplied) to the outer edge of the
of the outter pipe of the air terminal
connector. Slip the 7" rigid vent
pipe over the outer pipe of the air
terminal connector and secure as
before. Trim the 7" rigid vent pipe
even with the end of the 4" rigid
vent pipe.
5. Thread the air terminal
connector / vent pipe assembly
down through the roof support and
attach, ensuring that a minimum
16" of air terminal connector will
penetrate the roof when fastened.
If the attic space is tight, we recommend threading
the Wolf Steel vent pipe collar or equivalent loosely
onto the air terminal connecter /
vent pipe assembly as it is passed
through the attic. The air terminal
connector must be located vertically
and plumb.
FIGURE 32
4” RIGID VENT
PIPE
7” RIGID VENT
PIPE
INNER
PIPE
HIGH
TEMPERATURE
SEALANT
AIR
TERMINAL
CONNECTOR
FIGURE 31
6. Remove nails from the shingles, above and to the
sides of the chimney. Place the ashing over the air terminal
connector and slide it underneath the sides and upper edge
of the shingles. Ensure that the air terminal connector is
properly centered within the ashing, giving a
3
/
4
" margin all
around. Fasten to the roof. Do NOT nail through the lower
portion of the ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of
the ashing with roo ng material.
7. Aligning the seams of the terminal and air terminal
connector, place the terminal over the air terminal connector
making sure the vent pipe goes into the hole in the terminal.
Secure with the three screws provided.
8. Apply a heavy bead of weatherproof caulking 2" above
the ashing. Note: Maintain a minimum 2” space between
the air inlet base and the storm collar. Install the storm collar
around the air terminal and slide down to the caulking. Tighten
to ensure that a weather-tight seal between the air terminal
and the collar is achieved.
9. Continue adding rigid vent pipe sections, sealing and
securing as above. Attach a 4" collapsed telescopic sleeve to
the last section of rigid piping. Secure with screws and seal.
Repeat using a 7" telescopic sleeve.
10. REAR VENT APPLICATION: Run a bead of high
temperature sealant around the outside of the 4" elbow. Pull
the adjustable pipe a minimum 2" onto the elbow. Secure with
3 screws. Repeat with the 7" telescopic pipe.
TOP VENT APPLICATION: Run a bead of high temperature
sealant W573-0007 (not supplied) around the outside of the
4" collar on the replace. Pull the adjustable pipe a minimum
of 2" onto the collar. Secure with 3 screws. Repeat with the
7" telescopic pipe.
11. In the attic, slide the vent pipe collar down to cover up
the open end of the shield and tighten. This will prevent any
materials, such as insulation, from lling up the 1" air space
around the pipe.
VERTICAL VENTING INSTALLATION
RESTRICTING VERTICAL VENTS
Vertical termination installations exiting either from the
rear or the top ue collar of the replace may display a
very active flame. If this appearance is not desirable,
the vent exit must be restricted to reduce the velocity of
the exhaust gases, thus slowing down the ame pattern
and creating a more traditional gentle appearance.
Remove the baf e plate from the rear wall of the rebox,
exposing the ue gas outlet opening. Superimpose this outlet
hole with the smaller hole on the kit restrictor plate. Secure
with the two screws provided and replace the baf e plate.
1. Remove the front
and the door from the
replace.
2. Remove the screws
securing the baf e plate.
Figure 33.
Note: The baffle rests
on two screws that are
attached to the back of
the rebox.
3. Using the screws
supplied, attach the
restrictor plate as
shown in Figure 34.
4. Replace the baf e.
RESTRICTOR PLATE
BAFFLE PLATE
SCREWS
FIGURE 33
FIGURE 34
1. Follow the instructions
for "Horizontal Air Terminal
Installations", items 1 to 3.
2. Continue adding
components alternating 4"
and 7" vent pipes. Ensure
that all 4" vent pipes and elbows have
suf cient vent spacers attached and each
component is securely fastened to the
one prior. Attach the 4" telescopic sleeve
to the vent run.
Repeat using a 7" telescopic sleeve.
Secure and seal as before. To facilitate completion, attach 4"
and 7" couplers to the air terminal.
3. Install the air terminal. See item 3 of the Horizontal Air
Terminal Installation. Extend the 4" telescopic sleeve; connect
to the air terminal connector. Fasten with self tapping screws
and seal. Repeat using the 7" telescopic sleeve.
FIGURE 30
EXTENDED HORIZONTAL AND CORNER
AIR TERMINAL INSTALLATION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Napoleon Fireplaces Vittoria GD19N User manual

Category
Fireplaces
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI