Napoleon Fireplaces GDS26N User manual

Category
Fireplaces
Type
User manual

This manual is also suitable for

1
W415-0607 / A / 01.18.08
$10.00
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.88 • CSA 2.33 FOR VENTED GAS FIREPLACE HEATERS.
INSTALLATION AND
OPERATION INSTRUCTIONS
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • [email protected]
GDS26N
NATURAL GAS
GDS26P
PROPANE
WARNING: If the information in these
instructions are not followed exactly, a fire
or explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from
a neighbours phone. Follow the gas
suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
- Installation and service must be
performed by a qualified installer, service
agency or the supplier.
SAFETY INFORMATION
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS.
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
!
WARNING
2
W415-0607 / A / 01.18.08
• Do not burn wood or other materials in this stove.
Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or
clothing ignition. Supervise young children when they are in the same room as the stove.
• Clothing or other ammable material should not be placed on or near the stove.
• Due to high temperatures, the stove should be located out of traf c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the stove is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the oor.
Any safety screen or guard removed for servicing must be replaced prior to operating the stove.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the stove and venting system are
kept clean. The stove and its venting system should be inspected before use and at least annually by a quali ed service person. More
frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The stove area must be kept clear and
free from combustible materials, gasoline and other ammable vapours and liquids.
• Under no circumstances should this stove be modi ed.
• This stove must not be connected to a chimney ue pipe serving a separate solid fuel burning appliance.
• Do not use this stove if any part has been under water. Immediately call a quali ed service technician to inspect the stove and to
replace any part of the control system and any gas control which has been under water.
• Do not operate the stove with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or
quali ed service person.
• Do not strike or slam shut the stove glass door.
• This stove uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
• Pressure relief doors must be kept closed while the stove is operating to prevent exhaust fumes containing carbon monoxide, from
entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible
materials to overheat and catch re.
• Only doors / optional fronts certi ed with the unit are to be installed on the appliance.
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
TABLE of CONTENTS
RETAIN THIS MANUAL FOR FUTURE REFERENCE
PG 3-5 INTRODUCTION
Warranty
General Instructions
General Information
Care of Glass and Plated Parts
Dimensions
5-15 VENTING
Venting Lengths and Air Terminal Locations
Vent Installations
Typical Vent Installations
Special Vent Installations
Minimum Air Terminal Location Clearances
Venting Application Flow Chart
Venting Speci cations
Vertical Through Existing Chimney
Rear Exit Conversion
16-20 INSTALLATION
Wall and Ceiling Protection
Horizontal Installation
Vertical Installation
Stove Vent Connection
Horizontal Venting Installation
Vertical Venting Installation
Mobile Home Installation
Gas Installation
Minimum Clearances to Combustibles
Minimum Mantel, Shelf or Ceiling Clearances
21 BLOWER INSTALLATION
21 NIGHT LIGHT
TM
REPLACEMENT
22-23 FINISHING
Glass Door Installation and Removal
Logo Placement
Glass Door Replacement
Switch Functions
Log Placement
24 WIRING DIAGRAM
25 OPERATION / MAINTENANCE
Operating Instructions
Maintenance
26 ADJUSTMENTS
Pilot Injector and Ori ce Replacement
Flame Adjustment and Characteristics
Venturi Adjustment
27-28 REPLACEMENTS
Ordering Replacement Parts
Replacement Parts
Terminal Kits
Accessories
29-30 TROUBLE SHOOTING GUIDE
31 SERVICE HISTORY
32 NOTES
!
WARNING
3
W415-0607 / A / 01.18.08
NAPOLEON® products are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certifi cate.
NAPOLEON® products are designed with superior components and materials, assembled by trained
craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fi red at
a quality test station. The complete stove is test-fi red and thoroughly inspected by a qualifi ed technician
before packaging to ensure that you, the customer, receives the quality product that you expect from
NAPOLEON®
.
NAPOLEON® GAS STOVE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new NAPOLEON® gas stove are warranted against defects
for as long as you own the stove. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™
logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized
enamelled components and aluminium extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON® will
provide replacement parts free of charge during the fi rst year of the limited warranty. Light bulbs are not covered
by this warranty.
Labour related to warranty repair is covered free of charge during the fi rst year. Repair work however, requires
the prior approval of an authorized company of cial. Labour costs to the account of Napoleon® are based on a
predetermined rate schedule and any repair work must be done through an authorized Napoleon® dealer.
CONDITIONS AND LIMITATIONS
NAPOLEON® warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity
(registered customer) whose name appears on the warranty registration card led with NAPOLEON® -- provided that the purchase was
made through an authorized NAPOLEON® dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas stove must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance
with the installation instructions included with the product and all local and national building and re codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and
parts installed from other manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and
chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting
components used in the installation of the stove.
NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following
conditions: During the rst 10 years NAPOLEON® will replace or repair the defective parts at our option free of charge. From 10 years
to life, NAPOLEON® will provide replacement burners at 50% of the current retail price.
In the rst year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship
provided that the product has been operated in accordance with the operation instructions and under normal conditions.
After the rst year, with respect to this President's Limited Lifetime Warranty, NAPOLEON® may, at its discretion, fully discharge
all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but
defective part(s).
After the rst year, NAPOLEON® will not be responsible for installation, labour or any other costs or expenses related to the reinstallation
of a warranted part, and such expenses are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON®’S responsibility under this warranty
is de ned as above and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty de nes the obligations and liability of NAPOLEON® with respect to the NAPOLEON® gas stove and any other warranties
expressed or implied with respect to this product, its components or accessories are excluded.
NAPOLEON® neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this
product. NAPOLEON® will not be responsible for: over- ring, downdrafts, spillage caused by environmental conditions such as rooftops,
buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting con gurations, insuf cient makeup air, or
negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to stove, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long
periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON®.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your
authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGIS-
TERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD. THIS PRODUCT HAS AN INDUSTRIAL DESIGN
REGISTRATION
4
W415-0607 / A / 01.18.08
FOR YOUR SATISFACTION, THIS STOVE HAS BEEN TEST-
FIRED TO ASSURE ITS OPERATION AND QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column
for natural gas and 11 inches water column for propane.
Maximum inlet gas pressure is 7 inches water column for
natural gas and 13 inches water column for propane. When
the valve is set to "HI", the manifold pressure under ow
conditions is 3.5 inches water column for natural gas and 10
inches water column for propane. When the stove is installed
at elevations above 4,500ft, and in the absence of speci c
recommendations from the local authority having jurisdiction,
the certi ed high altitude input rating shall be reduced at the
rate of 4% for each additional 1,000ft.
Expansion / contraction noises during heating up and cooling
down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for use
with other gases, unless a certi ed kit is used.
Maximum input is 25,000 BTU/hr for natural gas and propane.
Maximum output is 20,500 BTU/hr at an ef ciency of 82%.
Provide adequate accessibility clearance for servicing and
operating the stove.
Never obstruct the front opening of the stove.
Provided that the clearance to combustibles are achieved,
the most desirable and bene cial location for a Napoleon®
stove is in the centre of a building, thereby allowing the most
ef cient use of the heat created. The location of windows,
doors and the traf c ow in the room where the stove is to be
located should be considered. If possible, you should choose
a location where the vent will pass through the house without
cutting a oor or roof joist.
Rating Label Location: The rating label is located behind the
control door and is chained to the stove.
DO NOT REMOVE.
THIS GAS STOVE SHOULD BE INSTALLED AND SERVICED
BY A QUALIFIED INSTALLER to conform with local codes.
Installation practices vary from region to region and it is
important to know the speci cs that apply to your area,
for example: in Massachusetts State:
The stove damper must be removed or welded in the open
position prior to installation of a stove insert or gas log.
A carbon monoxide detector is required in all rooms containing
gas red appliances.
The appliance off valve must be a “T” handle gas cock.
The exible connector must not be longer than 36 inches.
The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
WARNING: This product must be installed by a licensed
plumber or gas tter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install to the current CAN1-B149
Installation Code in Canada or to the National Fuel Gas
Code, ANSI Z223.1, and NFPA 54 in the United States.
Mobile home installation must conform with local codes. In
the absence of local codes, install to the current standard for
gas equipped mobile housing CAN/CSA Z240 MH Series in
Canada or the manufactured home construction and safety
standard, Title 24 CFR, part 3280, or the Fire Safety Criteria
for manufactured home installations, Sites and Community
Standard ANSI/NFPA 501A in the United States.
Objects placed in front of the stove must be kept a
minimum of 48" away from the front face of the unit.
The stove and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of ½ psig (3.5
kPa). The stove must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.5 kPa).
The stove, when installed with a blower, must be electrically
connected and grounded in accordance with local codes.
In the absence of local codes, use the current CSA C22.1
CANADIAN ELECTRICAL CODE in Canada or the ANSI/
NFPA 70 NATIONAL ELECTRICAL CODE in the United
States.
GENERAL INSTRUCTIONS GENERAL INFORMATION
CARE OF GLASS AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly
with a clean dry cloth.
The glass is
3
/
16
" ceramic glass available from your Napoleon®
/ Wolf Steel Ltd. dealer. DO NOT SUBSTITUTE MATERIALS.
Clean the glass after the rst 10 hours of operation with a
recommended gas stove glass cleaner. Thereafter clean as
required. DO NOT CLEAN GLASS WHEN HOT! If the glass
is not kept clean permanent discolouration and / or blemishes
may result.
5
W415-0607 / A / 01.18.08
35
1
/2
37”
18
1
/
8
23
5
/
8
4” DIA.
7” DIA.
GAS
LINE
ACCESS
ELECTRICAL
ACCESS
29
1
/
8
DIMENSIONS
FIGURE 1a
VENTING
VENTING LENGTHS AND AIR TERMINAL LOCATIONS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct
Temp or American Metal Amerivent venting components.
Minimum and maximum vent lengths, for both horizontal
and vertical installations, and air terminal locations for either
system are set out in this manual and must be adhered to.
For Simpson Dura-Vent, Selkirk Direct Temp and American
Metal Amerivent, follow the installation procedure provided
with the venting components.
All outer pipe joints of these venting systems must be sealed
using Red RTV High Temperature Sealant.
The connection between the adaptor for these systems and
the stove ue collar must be sealed using the black high
temperature sealant Mill Pac (not supplied).
A starter adaptor must be used with the following vent
systems and may be purchased from the corresponding
supplier:
PART 4"/7" SUPPLIER
Duravent GDS924N Wolf Steel
Amerivent 4DSCB-N1 American Metal
Direct Temp 4DT-AAN Selkirk
For Simpson Dura-Vent, Selkirk Direct Temp and
American Metal Amerivent, follow the installation
procedure found on the website for your venting
supplier:
VENTING SUPPLIER WEBSITE ADDRESS
Simpson Dura-Vent www.duravent.com
Selkirk Direct Temp www.selkirkcorp.com
American Metal Amerivent www.americanmetalproducts.com
For vent systems that provide seals on the inner exhaust
ue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant
may be used on both the inner exhaust and the outer intake
vent pipe joints of all other approved vent systems except
for the exhaust vent pipe connection to the stove ue collar
which must be sealed using the black high temperature
sealant Mill Pac.
When using Wolf Steel venting components, use only
approved Wolf Steel rigid / exible components with the
following termination kits:Wall Terminal Kit GD222, or
1/12 to 7/12 Pitch Roof Terminal Kit GD110, 8/12 to 12/12
Roof Terminal Kit GD111, Flat Roof Terminal Kit GD112 or
Periscope Kit GD201 (for wall penetration below grade).
Also approved for use with Duravent's co-axial to co-linear
adaptor for installations using an existing chimney.
The maximum allowable vertical vent length is 40 feet,
the minimum allowable vertical vent length is 3 feet.
For optimum ame appearance and stove performance,
keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify that it
is unobstructed and undamaged.
Horizontal runs may have a 0" rise per foot in all cases
using Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp,
American Metal Amerivent rigid venting components or Wolf
Steel exible venting components.
For optimum performance, it is recommended that horizontal
runs have a minimum 1" rise per foot when using Simpson
Dura-Vent, Selkirk Direct Temp, American Metal Amerivent
or Wolf Steel rigid / exible vent components.
Wolf Steel, Simpson Dura-vent, Selkirk Direct Temp, and
American Metal Amerivent venting systems must not be
combined.
FIGURE 1b FIGURE 1c
For safe and proper operation of the stove follow the venting instruction exactly.
Deviation from the minimum or the maximum vertical vent length can create dif culty in burner start-up and/or carboning.
Under extreme vent con gurations, allow several minutes (5-15) for the ame to stabilize after ignition.
Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation
wrapped in a protective sleeve to minimize condensation.
Use a restop, vent pipe shield or attic insulation shield when penetrating interior walls, oor or ceiling.
FOR SPECIFIC VENTING PARAMETERS, REFER TO PAGES 9-13.
VENT INSTALLATIONS
6
W415-0607 / A / 01.18.08
16”
MINIMUM
40 FT MAXIMUM
3 FT MINIMUM
16”
MINIMUM
40 FT MAXIMUM
3 FT MINIMUM
TYPICAL VENT INSTALLATIONS
FIGURE 2a
FIGURE 3a
* Refer to "Venting" Section
The maximum vent length for a corner installation is 20" of
horizontal run, in addition to the 45° offset. In this case zero
rise is acceptable. See FIGURE 5a. It is recommended to
maintain a 6" rise. See FIGURE 5b.
CORNER TERMINATION
FIGURE 5b
FIGURE 5a
20” MAXIMUM
6”
RISE
MINIMUM
SPECIAL VENT INSTALLATIONS
Use the GD201 periscope kit to locate the air termination
above grade. The periscope must be installed so that when
nal grading is completed, the bottom air slot is located a
minimum of 12 inches above grade. The maximum allowable
vent length is 10 ft.
PERISCOPE TERMINATION
FIGURE 4b
FIGURE 4a
24”
MINIMUM
12”
MINIMUM
24”
MINIMUM
12”
MINIMUM
MAXIMUM 10FT VENT LENGTH
FIGURE 2b
20" MAXIMUM
29
1
/8" MINIMUM
PLUS RISE*
35
1
/2"
FIGURE 3b
24" MAXIMUM
10"
MINIMUM
45
1
/2" MINIMUM
PLUS RISE*
35
1
/2"
HORIZONTAL VENT SECTIONS: A minimum clearance
of 1" at the bottom and sides and 2" at the top of the
vent pipe in all horizontal runs to combustibles is
required. Use restop spacer W010-1313 and shield
W585-0240 (supplied).
REAR EXIT TOP EXIT
VERTICAL VENT SECTIONS: A minimum of 1"
all around the vent pipe on all vertical runs to
combustibles is required. Use restop spacer W010-
1313 (supplied).
7
W415-0607 / A / 01.18.08
FIGURE 6
MINIMUM AIR TERMINAL LOCATION CLEARANCES
8
W415-0607 / A / 01.18.08
VENTING APPLICATION FLOW CHART
STOVE VENT EXIT
REAR EXIT
TOP EXIT
Horizontal Termination
Vertical Termination
Vertical Termination
Vertical rise
is equal to
or greater
than the
horizontal
run
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
Horizontal
run + verti-
cal rise to
maximum of
24.75 feet
3.5 times the
vertical rise
equal to or
greater than
the horizon-
tal run
Horizontal Termination
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
Vertical rise
is equal to
or greater
than the
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
3 times the
vertical rise
equal to or
greater than
the horizon-
tal run
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum of
24.75 feet
4.2 times the
vertical rise
equal to or
greater than
the horizon-
tal run
Vertical rise
is less than
horizontal
run
Horizontal
run + verti-
cal rise to
maximum
of 40 feet
3 times the
vertical rise
equal to or
greater than
the horizon-
tal run
9
W415-0607 / A / 01.18.08
90°
90°
90°
H
1
V
2
H
2
V
1
Simple venting con guration
(only one 90° elbow)
For vent con gurations requiring more than one 90° elbow,
the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet
Example 1:
V
1
= 3 ft
V
2
= 8 ft
V
T
=
V
1
+
V
2
=
3 + 8 = 11 ft
H
1
= 2.5 ft
H
2
= 2 ft
H
R
= H
1
+ H
2
= 2.5 + 2 = 4.5 ft
H
O
= .
03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft
H
T
= H
R
+ H
O
= 4.5 + 5.4 = 9.9 ft
H
T
+ V
T
= 9.9 + 11 = 20.9 ft
Formula 1: H
T
< V
T
9.9 < 11
Formula 2: H
T
+ V
T
< 40 feet
20.9 < 40
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 8
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
H
T
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
for the following symbols used in the venting calculations
and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H
T
- total of both horizontal vent lengths (H
R
) and offsets
(H
O
) in feet
H
R
- combined horizontal vent lengths in feet
H
O
- offset factor: .03(total degrees of offset - 90°*) in
feet
V
T
- combined vertical vent lengths in feet
feet inches
0.03 0.5
15° 0.45 6.0
30° 0.9 11.0
45° 1.35 16.0
90°* 2.7 32.0
* the rst 90° offset has a zero value and is shown in the
formula as -90°
DEFINITIONS
ELBOW VENT LENGTH VALUES
TOP EXIT / HORIZONTAL TERMINATION
FIGURE 7
VERTICAL
RISE
IN FEET
V
T
0
2.5 5 7.5 10 12.5 15
40
10
20
30
17.5 20
39
(H
T
) < (V
T
)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
10
W415-0607 / A / 01.18.08
V
2
90°
H
3
H
1
90°
H
2
H
1
V
1
Simple venting con guration
(only one 90° elbow)
Example 2:
V
1
= V
T
= 6 ft
H
1
= 3 ft
H
2
= 5 ft
H
R
= H
1
+ H
2
= 3 + 5 = 8 ft
H
O
= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft
H
T
= H
R
+ H
O
= 8 + 2.7 = 10.7 ft
H
T
+ V
T
=
10.7 + 6 =16.7
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2 x 6 = 25.2 ft
10.7 < 25.2
Formula 2: H
T
+ V
T
< 24.75 feet
16.7 < 24.75
Since both formulas are met, this vent con guration is ac-
ceptable.
For vent con gurations requiring more than one 90° elbow
the following formulas apply:
Formula 1: H
T
< 4.2 V
T
Formula 2: H
T
+ V
T
< 24.75 feet
Example 3:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
= V
1
+ V
2
= 4 + 1.5 = 5.5 ft
H
1
= 2 ft
H
2
= 1 ft
H
3
= 1 ft
H
4
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2 + 1 + 1 + 1. 5 = 5.5 ft
H
O
= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft
H
T
= H
R
+ H
O
= 5.5 + 8.1 = 13.6 ft
H
T
+ V
T
= 13.6 + 5.5 = 19.1 ft
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2 x 5.5 = 23.1 ft
13.6 < 23.1
Formula 2: H
T
+ V
T
< 24.75 feet
19.1 < 24.75
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 9
FIGURE10
REQUIRED
VERTICAL
RISE IN
INCHES
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
FIGURE 11
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
TOP EXIT / HORIZONTAL TERMINATION
20
10
0 5 10 15
90
100
120
110
30
40
50
60
70
80
130
140
150
20
V
1
H
2
H
4
(H
T
) > (V
T
)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
11
W415-0607 / A / 01.18.08
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
For vent con gurations requiring more than two 90° elbows
the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET H
T
Example 4:
FIGURE 12
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
REAR EXIT / HORIZONTAL TERMINATION
Simple venting con guration
(only two 90° elbows)
FIGURE 13
H
3
90°
90°
90°
V
2
H
1
V
1
H
2
V
1
= 9 ft
V
2
= 6 ft
V
T
=
V
1
+
V
2
=
9 + 6 = 15 ft
H
1
= 3 ft
H
2
= 2 ft
H
3
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
= 3 + 2 + 1.5 = 6.5 ft
H
O
= .03(four 90° elbows - 90°)
= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
= H
R
+ H
O
= 6.5 + 8.1 = 14.6 ft
H
T
+ V
T
= 14.6 + 15 = 29.6 ft
Formula 1: H
T
< V
T
14.6 < 15
Formula 2: H
T
+ V
T
< 40 feet
29.6 < 40
Since both formulas are met, this vent con guration is
acceptable.
90°
REQUIRED
VERTICAL
RISE IN
FEET
V
T
0
2.5 5 7.5 10 12.5 15
40
10
20
30
17.5 20
39
(H
T
) < (V
T
)
12
W415-0607 / A / 01.18.08
V
1
V
2
90°
45°
90°
90°
Simple venting con guration (only two 90° elbows)
Example 5:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
=
V
1
+
V
2
=
4 + 1.5 = 5.5 ft
H
1
= 2 ft
H
2
= 1 ft
H
3
= 1 ft
H
4
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2 + 1 + 1 + 1.5 = 5.5 ft
H
O
= .03(four 90° elbows + one 45° elbow - 90°)
= .03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft
H
T
= H
R
+ H
O
= 5.5 + 9.45 = 14.95 ft
H
T
+ V
T
= 14.95 + 5.5 = 20.45 ft
Formula 1: H
T
< 3.5V
T
3.5V
T
=
3.5 x
5.5 = 19.25 ft
14.95 < 19.25
Formula 2: H
T
+ V
T
< 24.75 feet
20.45 < 24.75
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 15
For vent con gurations requiring more than two 90° elbows
the following formulas apply:
Formula 1: H
T
< 3.5V
T
Formula 2: H
T
+ V
T
< 24.75 feet
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET
H
T
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
FIGURE 14
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
REAR EXIT / HORIZONTAL TERMINATION
H
3
H
4
90°
REQUIRED
VERTICAL
RISE IN
INCHES
V
T
0
10
51525
100
50
150
3.5 19.2512.5
12
63
147
1
H
1
H
2
(H
T
) > (V
T
)
13
W415-0607 / A / 01.18.08
REQUIRED
VERTICAL RISE
IN FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
H
T
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
Example 6:
V
1
= 5 ft
V
2
= 6 ft
V
3
= 10 ft
V
T
=
V
1
+
V
2
+
V
3
=
5 + 6 + 10 = 21 ft
H
1
= 8 ft
H
2
= 2.5 ft
H
R
= H
1
+ H
2
= 8 + 2.5 = 10.5 ft
H
O
= .03 (four 90° elbows - 90°)
= .03 (90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
= H
R
+ H
O
= 10.5 + 8.1 = 18.6 ft
H
T
+ V
T
= 18.6 + 21 = 39.6 ft
Formula 1: H
T
< V
T
18.6 < 21
Formula 2: H
T
+ V
T
< 40 feet
39.6 < 40
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 16
For vent con gurations requiring more than zero 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet
Simple venting con gurations
TOP OR REAR EXIT VERTICAL TERMINATION
90°
90°
90°
H
2
V
3
90°
FIGURE 17
V
1
H
1
V
2
0
5101520
40
10
20
30
3
(H
T
) < (V
T
)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
14
W415-0607 / A / 01.18.08
VERTICAL THROUGH EXISTING CHIMNEY
This appliance is designed to be attached to a 3" co-linear
exible vent system running the full length of a masonry
chimney.
The exible vent pipe accommodates any contours of a masonry
chimney, however, it is necessary to keep the exible vent pipe
as straight as possible. The inlet air collar of the termination
cap must be connected to the air intake pipe.
Use Simpson Duravent Chimney Liner Termination Kit -
923GK (Base plate and Co-Linear to Co-Axial Adaptor.
Follow manufacturers (Simpson Dura-Vent) installation
instructions.
When installing the unit to this system, Duravent vent
components must be used. You must start with a Duravent
adaptor, GDS924N, directly off the unit. The GDS924N is only
available at your Napoleon® dealer.
INSTALLATION
FIGURE 18
40 FEET
MAXIMUM
3 FEET
MINIMUM
FLEX
VENT
PIPE
EXHAUST
FLUE
PIPE
AIR
INTAKE
PIPE
15
W415-0607 / A / 01.18.08
REAR EXIT CONVERSION
FIGURE 19
4” Gasket
7” Cover Plate
7” Gasket
4” Gasket
4” Collar
7” Gasket
7” Collar
Outer Top
4” Cover Plate
In order to convert the venting con guration from a top exit to a rear exit, remove components as illustrated:
When reinstalling in the alternate position: Check gaskets for tears, replace if necessary to ensure a proper seal.
16
W415-0607 / A / 01.18.08
1. Determine the air terminal location, cut and frame a 9"
square opening in the ceiling and the roof to provide the
minimum 1" clearance between the vent pipe / liner and any
combustible material. Try to center the vent pipe location
midway between two joists to prevent having to cut them.
Use a plumb bob to line up the center of the openings. DO
NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.
A vent pipe shield will prevent any materials such as
insulation, from lling up the 1" air space around the vent pipe.
Nail headers between the joists for extra support.
2. Apply a bead of caulking (not supplied) to the framework
or to the Wolf Steel vent pipe shield plate or equivalent (in
the case of a nished ceiling), and secure over the opening
in the ceiling. A restop spacer must be placed on the bottom
of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around
and place a restop spacer over the vent shield to restrict
cold air from being drawn into the room or around the stove.
Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe / liner is
installed in its nal position, apply high temperature sealant
W573-0002 (not supplied) between the vent pipe / liner and
the restop assembly.
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
INSTALLATION
WALL AND CEILING PROTECTION
FIGURE 20
FIGURE 22a
FIGURE 21
FIRESTOP
UNDERSIDE OF JOIST
9 ”
9”
VENT PIPE
SHIELD
CAULKING
This application occurs when venting through an exterior wall.
Having determined the air terminal location, cut and frame a
hole in an exterior wall with a minimum rectangle opening of
10" high x 9" wide. Firestop spacer and shield do not limit
the thickness of a wall. For wall construction when using less
than 2" x 6" framing, the shield must be cut to suit.
1. Assemble the shield to the spacer as shown, using the
3 shorter screws supplied.
The shield is meant to protect combustible materials within
the wall. If the shield is deeper than the combustible portion
of the wall, cut to t.
2. Apply a bead of caulking all around and place the restop
spacer over the framework to restrict cold air from being drawn
into the room or around the stove. Ensure that both spacer
and shield maintain the required clearance to combustibles.
Secure the spacer in place using the 4 longer screws supplied.
Once the vent pipe is installed in its nal position, apply high
temperature sealant W573-0002 (not supplied) between the
vent pipe and the restop spacer.
3. In the attic, after the vent
pipe has been installed, slide the
vent pipe collar down to cover up
the open end of the shield and
tighten. This will prevent any
materials, such as insulation,
from lling up the 1" air space
around the vent pipe.
SHIELD
VENT
PIPE
COLLAR
VENT PIPE
FIGURE 22b
For optimum performance, it is recommended that
horizontal runs have a minimum 1" rise per foot when
using Simpson Dura-Vent, Selkirk Direct Temp,
American Metal Amerivent, or Wolf Steel rigid or
exible vent components.
For safe and proper operation of the stove, follow
the venting instructions exactly.
17
W415-0607 / A / 01.18.08
SCREWS & WASHERS
4" COUPLER
SELF DRILLING
#8x1/2"
7" RIGID VENT
PIPE
SEALANT
HIGH TEMPERATURE
4" FLEXIBLE
VENT PIPE
7" RIGID
VENT PIPE
1. Attach the telescopic sleeve to the last section of 7" rigid vent pipe. Secure
with screws and high temperature sealant W573-0002 (not supplied).
2. Install the 4" exible vent pipe to the stove. Secure with 3 screws and at
washers. Seal the joint and screw holes using high temperature sealant W573-
0007 (not supplied).
3. Run a bead of high temperature sealant W573-0002 (not supplied) around
the inside of the air intake collar. Pull the telescopic sleeve a minimum 2" into
the air intake collar.
ENSURE THAT THE SEALANT IS NOT VISIBLE ON THE EXTERIOR
PIPES ONCE INSTALLATION IS COMPLETED. AN OPTIONAL
DECORATIVE BRASS BAND IS AVAILABLE FOR THIS USE. (STANDARD
WITH A GD-175 KIT AND GD-176). IN THE EVENT THAT THE VENTING
MUST BE DISASSEMBLED, CARE MUST BE TAKEN TO RESEAL THE
VENTING.
STOVE VENT CONNECTION
SELF DRILLING
#8x1/2"
SCREWS
AIR INTAKE
COLLAR
TELESCOPIC
SLEEVE
4” FLEXIBLE
VENT PIPE
7” RIGID
VENT PIPE
HIGH TEMPERATURE
SEALANT
FIGURE 23
HORIZONTAL VENTING INSTALLATION
All 4" exible vent pipe and 7" rigid vent pipe joints
must be sealed using either high temperature sealant
W573-0002 (not supplied) or the high temperature sealant
W573-0007 Mill Pac (not supplied). However, the high
temperature sealant W573-0007 Mill Pac (not supplied)
must be used on the joint connecting the 4" exible vent
pipe and the exhaust ue collar.
1. Stretch the 4" exible vent pipe to the required length
taking into account the additional length needed for the
nished wall surface. Slip a minimum of 2" of the 4" exible
vent pipe over the inner sleeve of the air terminal. Secure
to the inner sleeve using 3 screws. Seal the joint and screw
heads using the high temperature sealant W573-0002 (not
supplied).
NOTE: If using pipe clamps to connect vent components,
3 screws must also be used to ensure the connection
cannot slip off.
2. Slip the rst section of 7" rigid vent pipe a minimum of
2" over the outer sleeve of the air terminal. Secure to the outer
sleeve using 3 screws. Seal the joint and screw heads using
high temperature sealant W573-0002 (not supplied).
FIGURE 25
SCREWS
#10 x 2"
SEALANT
HIGH TEMPERATURE
2" OVERLAP
VENT PIPE
4"FLEXIBLE
CAULKING
VENT PIPE
7" RIGID
ATTE
NTION-
CHAUD
CAUTION - HOT
3. Insert the vent pipe through the restop / vent pipe shield.
Holding the air terminal (lettering in an upright, readable
position), secure to the exterior wall. Make weather tight by
sealing with caulking (not supplied).
4. If more than one length of vent pipe needs to be used
to reach the stove, couple them together as illustrated in
FIGURE 25. Seal the joints using the same procedure as
described above.
The air terminal mounting plate may be recessed into
the exterior wall or siding by 1½", the depth of the return
ange.
FIGURE 24
The vent system must be supported approximately
every 3 feet for both vertical and horizontal runs.
Use supports or equivalent non-combustible
strapping to maintain the 1" clearance from
combustibles. Use Wolf Steel Ltd. vent spacers
W615-0033 every 18" and at the start, middle and end
of each elbow to maintain the minimum 1 1/4"
clearance between the 4" flexible vent pipe and the
7" rigid vent pipe. These spacers must not be
removed. Use Wolf Steel Ltd. support ring assembly
W010-0370 or equivalent non-combustible strapping
to maintain the minimum clearance to combustibles
for both vertical and horizontal runs.
!
WARNING
18
W415-0607 / A / 01.18.08
RESTRICTING VERTICAL VENTS
Vertical termination installations exiting either from the rear or the top flue collar of the stove may display a
very active flame. If this appearance is not desirable, the vent exit must be restricted to reduce the velocity of
the exhaust gases, thus slowing down the flame pattern and creating a more traditional gentle appearance.
Remove the baf e plate from the rear wall of the rebox, exposing the ue gas outlet opening. Superimpose this outlet hole
with the smaller hole on the kit restrictor plate. Secure with the two screws provided and replace the baf e plate.
VERTICAL VENTING INSTALLATION
1. Follow the instructions for "Horizontal Air Terminal Installations", items 1 to 3.
2. Continue adding components alternating exible and rigid vent pipes. Ensure that all 4"
exible vent pipes and elbows have suf cient vent spacers attached and each component is
securely fastened to the one prior. Attach the 4" telescopic sleeve to the vent run.
Repeat using a 7" telescopic sleeve. Secure and seal as before. To facilitate completion, attach
4" and 7" couplers to the air terminal.
3. Install the air terminal. See item 3 of the Horizontal Air Terminal Installation. Extend the
4" telescopic sleeve; connect to the air terminal assembly. Fasten with self tapping screws
and seal. Repeat using the 7" telescopic sleeve.
FIGURE 26
EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION
1. Fasten the roof support to the roof using the screws
provided. The roof support is optional. In this case the venting
is to be adequately supported using either an alternate method
suitable to the authority having jurisdiction or the optional roof
support.
2. Stretch the 4" exible vent pipe to the required length. Slip
the vent pipe a minimum of 2” over the inner pipe of the air
terminal connector and secure with 3 #8 screws. Seal using a
heavy bead of the high temperature sealant W573-0002 (not
supplied).
NOTE: If using pipe clamps to connect vent components, 3 screws must also be used to
ensure the connection cannot slip off.
3. Slip the 7" rigid vent pipe a minimum of 2" over the air terminal connector and secure
with 3 #8 screws. Seal using a heavy bead of the high temperature sealant W573-0002 (not
supplied).
4. Thread the air terminal connector / vent pipe assembly down through the roof. The air terminal
must be located vertically and plumb. Attach the air terminal connector to the
roof support, ensuring
that the top of the air terminal is 16” above the highest point that penetrates the roof.
If the attic space is tight, we recommend threading the Wolf Steel vent pipe collar or equivalent
loosely onto the air terminal connector / vent pipe assembly as it is passed through the attic.
The air terminal connector must be located vertically and plumb.
5. Remove nails from the shingles, above and to the sides of the chimney. Place the
ashing over the air terminal connector leaving a min. 3/4” of the air terminal connector
showing above the top of the ashing. Slide the ashing underneath the sides and
upper edge of the shingles. Ensure that the air terminal connector is properly centred
within the ashing, giving a 3/4” margin all around. Fasten to the roof. Do not nail
through the lower portion of the ashing. Make weather-tight by sealing with caulking.
Where possible, cover the sides and top edges of the ashing with roo ng material.
6. Aligning the seams of the terminal and air terminal connector, place the terminal
over the air terminal connector making sure the inner pipe goes into the hole in the
terminal. Secure with the three screws provided.
7. Apply a heavy bead of weatherproof caulking 2" above the ashing. Note: Maintain
a minimum 2” space between the air inlet base and the storm collar. Install the storm
collar around the air terminal and slide down to the caulking. Tighten to ensure that a
weather-tight seal between the air terminal and the collar is achieved.
ROOF SUPPORT
AIR
TERMINAL
CONNECTOR
4” FLEX
VENT PIPE
7” RIGID
VENT PIPE
INNER
PIPE
HIGH
TEMPERATURE
SEALANT
STORM COLLAR
FLASHING
CAULKING
WEATHER
SEALANT
2”
AIR INLET
BASE
FIGURE 27
FIGURE 28a&b
FIGURE 29
SHIELD
VENT
PIPE
COLLAR
VENT PIPE
19
W415-0607 / A / 01.18.08
FIGURE 30
FIGURE 31
RESTRICTOR
PLATE
1. Remove the front and the door from the stove.
2. Remove the screws securing the baf e plate. Figure 31.
Note: The baf e rests on two screws that are attached to the
back of the rebox.
3. Using the screws supplied, attach the restrictor plate as
show in Figure 31.
4. Replace the baf e.
BAFFLE PLATE
SCREWS
FIGURE 32
GAS INSTALLATION
This Mobile/Manufactured Home Listed appliance comes
factory equipped with a means to secure the unit. The stove
is equipped with two 1/4" diameter holes located in the front
left and right corners of the base. For mobile home installa-
tions, the stove must be fastened in place. Use #10 hex head
screws, inserted through the holes in the base to secure.
Always turn off the pilot and the fuel suuply at the source,
prior to moving the mobile home. After moving the mobile
home and prior to lighting the stove, ensure that the logs are
positioned correctly.
MOBILE HOME INSTALLATION
Proceed once the vent installation is complete.
1. Move the stove into position and secure to the oor
through the 1/4" holes located at either side of the base.
2. The stove is designed to accept 3/8" gas supply line.
The stove is equipped with a 3/8" manual shut-off valve and
exible connector. Do not kink exible connector.
3. Connect the gas supply in accordance to local codes.
In the absence thereof, install according to the National
Installation Code.
4. When exing any gas line, support the gas valve so that
the lines are not bent or kinked.
5. Check for gas leaks by brushing on a soap and water
solution.
DO NOT USE OPEN FLAME.
Purge all gas lines with the glass door of the stove re-
moved. Assure that a continuous gas ow is at the burner
before re-installing the door.
This appliance is certi ed to be installed as an OEM (Origi-
nal Equipment Manufacturer) installation in a manufactured
home or mobile home and must be installed in accordance
with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part
3280, in the United States or the Mobile Home Standard,
CAN/CSA Z240 MH Series, in Canada. This appliance is
only for use with the type(s) of gas indicated on the rating
plate. A conversion kit is supplied with the mobile home
appliance.
This appliance is certi ed to be installed in an aftermarket
permanently located, manufactured (mobile) home, where
not prohibited by local codes.
This stove is only for use with the type of gas indicated on
the rating plate. This stove is not convertible for use with
other gases, unless a certi ed kit is used.
Conversion Kits
The mobile home appliance is eld convertible between
Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Napoleon®
dealer/distributor.
Shown
in “OFF”
position.
Manual
Shut-off Valve
A
B
Supply pressure can be checked by turning screw (A)
counter-clockwise until loosened and then placing pressure
gauge tubing over the test point. Gauge should read 7”
(minimum 4.5”) water column for natural gas or 13” (11”
minimum) water column for propane. Check that main burner
is operating on “HI”.
Manifold pressure can be checked the same as above using
screw (B). Gauge should read 3.5” water column for natural
gas or 10” water column for propane. Check that main burner
is operating on “HI”.
AFTER TAKING PRESSURE READINGS, TIGHTEN
SCREWS FIRMLY TO SEAL. DO NOT OVERTORQUE.
LEAK TEST
20
W415-0607 / A / 01.18.08
FIGURE 34
MINIMUM MANTEL, SHELF OR CEILING CLEARANCES
1”
2”
47
1
/2
35
1
/2
5”
BRICK
COMBUSTIBLE NON-COMBUSTIBLE
29
1
/8” MINIMUM
PLUS RISE *
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
12”
MANTEL, SHELF,
OR CEILING
REAR EXIT TOP EXIT
* HORIZONTAL VENT SECTIONS: A minimum clearance of 1"
at the bottom and sides and 2" at the top of the vent pipe in all
horizontal runs to combustibles is required. Use restop spacer
W010-1313 and shield W585-0240 (supplied).
* VERTICAL VENT SECTIONS: A minimum of 1" all around the
vent pipe on all vertical runs to combustibles is required. Use
restop spacer W010-1313 (supplied).
The stove requires a minimum ceiling height
of 47 1/2" for a rear vent. For temperature
requirements, the space around and above the
stove must be left unobstructed.
5”
BRICK
COMBUSTIBLE NON-COMBUSTIBLE
45
1
/2” MINIMUM
PLUS RISE *
MANTEL, SHELF,
OR CEILING
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
1”
2”
15
1
/2
35
1
/2
51”
2”
The stove requires a minimum ceiling height of
51" for a top vent. For temperature requirements,
the space around and above the stove must be
left unobstructed.
FIGURE 35
Minimum clearance to combustible construction from
stove and vent surfaces:
A - 2"
B - 5"
C - 2"
- 1" to bottom and sides of the vent pipe*
- 2" to top of the vent pipe*
Rear Exit
- 47 1/2" to ceiling from base of the unit
Top Exit
- 51" to ceiling from base of the unit
MINIMUM CLEARANCES TO COMBUSTIBLES
BACK WALL
SIDE WALL
BACK WALL
SIDE WALL
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32