  • Hello! I am an AI chatbot trained to assist you with the EDWARDS SD-TRK SD-TRM Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation Sheet 22SEP04 P/N: 3100691 REV: 1.0
SD-TRK, SD-TRM - Remote Test Stations 1 / 1
SD-TRK, SD-TRM
Remote Test Stations
Product description
SD-TRK SD-TRM
The SD-TRK and SD-TRM remote test stations are used with
SuperDuct series of conventional two-wire and Signature duct
smoke detectors. Each remote test station provides a red LED
to indicate alarms. The SD-TRK requires a key to activate the
test function while the SD-TRM requires the SD-MAG magnetic
test tool (ordered separately).
For operating instructions, refer to the following documentation:
SuperDuct Conventional Two-Wire Duct Smoke Detector
Technical Reference (P/N 3100737)
SuperDuct Signature Duct Smoke Detector Technical
Reference (P/N 3100738)
Specifications
Compatible electrical boxes
North American 1-gang box
Standard 4-in square box, 1-1/2 inches deep, with 1-gang
cover
LED indicators: Alarm (red)
LED type: Clear lens
Wire size: 12 to 22 AWG
Resistance per wire: 10 , max.
Current requirements: Included in controller specification
LED circuit ratings
Voltage: 3 Vdc, max.
Current: 30 mA, max.
Switch ratings (SD-TRK)
Voltage: 125 Vdc, max.
Current: 4 A, max.
Switch ratings (SD-TRM)
Voltage: 200 Vdc, max.
Current: 0.5 A, max.
Compatible detectors: SuperDuct conventional two-wire and
Signature duct smoke detectors
Operating environment
Temperature: 0 to 55 °C (32 to 131 °F)
Humidity: 93% RH, noncondensing
Storage temperature: -20 to 60 °C (-4 to 140 °F)
Installation instructions
Mount the remote test/reset station on a single gang box as
shown in Figure 1.
Figure 1: Installation diagram
Wiring diagram
Wire the remote test station to the duct smoke detector as
shown in Figure 2.
14
13
12
10
Signature
duct smoke
detector
Remote test station
(rear view)
1234
1234
14
13
12
11
2-wire
duct smoke
detector
Figure 2: Wiring diagram
Offset Spec 22SEP04 P/N: 3100691 REV: 1.0
SD-TRK, SD-TRM - Remote Test Stations 1 / 1
OFFSET SPEC
SD-TRK, SD-TRM
Remote Test Stations
E
For: letter, portrait to 1/4
One 8-1/2 in x 11 in sheet printed on one side.
Material is standard white offset stock.
Characters are black on white background.
Fold two times to the dimensions shown, with the part number
on the outside.
4-1/4 in (± 1/16 in)
5-1/2 in (±1/16 in)
P/N: 000000 REV: 0.0
0 / 0
DDMONYY
ECO: 04-S3821
/