M-system R5-TS User manual

Type
User manual

M-system R5-TS is a thermocouple input module that can be used for measuring temperature in various industrial applications. It has two channels for input and can be used with different types of thermocouples. The module has a wide temperature range and can be used in environments with high dust or metal particles. It also has a burnout function that can be used to protect the module from damage in case of a sensor failure. Additionally, the module has a PC configurator that can be used to set various parameters, such as zero scale, full scale, and bias.

M-system R5-TS is a thermocouple input module that can be used for measuring temperature in various industrial applications. It has two channels for input and can be used with different types of thermocouples. The module has a wide temperature range and can be used in environments with high dust or metal particles. It also has a burnout function that can be used to protect the module from damage in case of a sensor failure. Additionally, the module has a PC configurator that can be used to set various parameters, such as zero scale, full scale, and bias.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6112 Rev.3 P. 1 / 3
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Thermocouple input module (body + CJC sensors *
1
) .......(1)
*1. Two provided for 2 channels input.
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
CONFORMITY WITH EU DIRECTIVES
The equipment must be mounted inside the instrument
panel of a metal enclosure.
The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
HOT INSERTION/REMOVAL OF MODULES
Removing or replacing modules does not affect other mod-
ules on the same backplane. It is possible to replace them
without removing the power supply. However, replacing
multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
GENERAL PRECAUTIONS
DO NOT set the switches while the power is supplied.
The switches are used only for maintenance without the
power.
ENVIRONMENT
Indoor use.
When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
WIRING
Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R5-BS).
THERMOCOUPLE INPUT MODULE
MODEL
R5-TS
R5-TS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6112 Rev.3 P. 2 / 3
COMPONENT IDENTIFICATION
RUN LED
456
123
ON
1
T/C
Burnout
Temp. Unit
2345678
Function
Euro Type
Connector Terminals
RUN
SIDE VIEW FRONT VIEW
STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
SIDE DIP SW
(*) Factory setting
• Thermocouple Type: SW1, 2, 3, 4
SW
T/C
1 2 3 4
OFF OFF OFF OFF (PR)
ON OFF OFF OFF K (CA) (*)
OFF ON OFF OFF E (CRC)
ON ON OFF OFF J (IC)
OFF OFF ON OFF T (CC)
ON OFF ON OFF B (RH)
OFF ON ON OFF R
ON ON ON OFF S
OFF OFF OFF ON C (WRe 5-26)
ON OFF OFF ON N
OFF ON OFF ON U
ON ON OFF ON L
OFF OFF ON ON P (Platinel II)
• Temperature Unit: SW5, 6
SW
TEMP. UNIT
5 6
OFF OFF °C (*)
ON OFF °F
OFF ON K (Absolute Temp)
• Burnout: SW7, 8
SW
BURNOUT7 8
INPUT 1 INPUT 2
OFF OFF Downscale
ON ON Upscale (*)
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R5CON for detailed operation.
CHANNEL INDIVIDUAL SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Zero Scale -32000 to +32000 0
Full Scale -32000 to +32000 10000
Bias [Zero Adj.] -320.00 to +320.00 0.00
Gain [Span Adj.] -32000 to +32000 1.0000
Zero Base Depends on sensor type 0.00
Full Base Depends on sensor type 0.00
CHANNEL BATCH SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Limit (V1.00 or higher) No check mark: Limits to the scaling values equivalent to -15 % to
+115 %.
Check-marked: Limits within Zero Scale to Full Scale.
No check mark
R5-TS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6112 Rev.3 P. 3 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
EXTERNAL DIMENSIONS unit: mm (inch)
456
123
6.5
(.26)
90 (3.54)
LOCKING CLAMP
90 (3.54) 5.6
(.22)
18 (.71)
POSITIONING GUIDE
*
*Euro type connector terminals (4, 5 and 6) provided only with 2-ch. option.
CJC Sensor (model: CJM)
CONNECTION DIAGRAM
INPUT 2
+
T / C
CJC
SENSOR
comp. wire
comp. wire
1
3
2
+
+
T / C
INPUT 1
CJC
SENSOR
4
6
5
+
BUS CONNECTOR
INTERNAL
POWER
INTERNAL
BUS A
INTERNAL
BUS B*
1
3
2
*For dual redundant communication.
Note: The section enclosed by broken line is with 2-ch. option.
WIRING INSTRUCTIONS
EURO TYPE CONNECTOR TERMINAL
Applicable wire size: 0.2 to 2.5 mm
2
Stripped length: 7 mm
  • Page 1 1
  • Page 2 2
  • Page 3 3

M-system R5-TS User manual

Type
User manual

M-system R5-TS is a thermocouple input module that can be used for measuring temperature in various industrial applications. It has two channels for input and can be used with different types of thermocouples. The module has a wide temperature range and can be used in environments with high dust or metal particles. It also has a burnout function that can be used to protect the module from damage in case of a sensor failure. Additionally, the module has a PC configurator that can be used to set various parameters, such as zero scale, full scale, and bias.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI