Technical Manual Taster BE-TA55
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
11
Ifachannelpairisselectedasdisabled,noobjectswillbeshown.Sotherearenoopportunitiesfor
programmingthischannel.
Thesearetheavailableobjectsforeachchannel:
Nr.FunctionUsageDatatype
0SwitchedgecontrolDPT1.001Out,Read
0Sendforcedsettingforcecontrol/switchDPT2.001Out,Read
0Shuttersdown/updrivingofshuttersDPT1.008Out,Read
0Dimmingon/offtogglingofthedimminglightsDPT1.001Out,Read
0Switchon/offtwobuttonswitchingDPT1.001Out,Read
0SendvaluesendstheparameterizedvalueDPT5.001Out,Read
0push‐buttonshortsendsactionforshortkeystrokeDPT1.001Out,Read
1ValuefortoggleedgecontrolwithtogglefunctionDPT1.001In,Write
1Stop/Blindsopen/closedrivingoftheblinds/stopping
movementoftheshutters
DPT1.009Out,Read
1DimmingdimmingDPT3.007Out,Read
2ScenescenecontrolDPT18.001Out,Read
0push‐buttonlongsendsactionforlongkeystrokeDPT1.001Ѐut,Read
4BlockingobjectblockstherelatedchannelDPT1.001In,Write
+5nextchannel
Chart2:communicationobjectsperchannel
3.2Communicationobjectslogic
onlyattheplusvariant
Therearecommunicationobjectsforthelogicfunctionateverypushbuttonadditionaltothe
communicationobjectsperchannel.Theseobjectscanbeparameterizedandshownindependent
fromtheparameterizationofthechannels.Thelogicobjectshavethenumbersfrom80ata16‐fold
pushbuttonandthenumbersfrom40atan8‐foldpushbutton.Thefirstlogicblockgetsassigned
thefirstthreenumbers,soatan8‐foldpushbuttonfrom40to42.Everyfollowingblockincreases
thenumbersby3.
Theaddressingcanbemadebyusingthecommunicationobjectsforthelogicanalogoustothe
addressingbythechannels.
Thefollowingcommunicationobjectsforthelogiccanbeshown:
Illustration5:communicationobjectslogic
Ifalogicblockisdisabled,nocommunicationobjectswillbeshown.Thereforenoaddressingis
possible.Everypushbuttoncontainsof4logicblocksforwhichthefollowingobjectscanbeshown:
Nr.FunctionUsageDatatype
40/80Logicinput1ALogicinputDPT1.001In,Write
41/81Logicinput1BLogicinputDPT1.001In,Write
42/82Logicoutput1LogicoutputDPT1.001Out,Read
42/82Logicoutput1sceneLogicoutputsceneDPT18.001Out,Read
+3nextlogicblock
Chart3:communicationobjectslogic