COOPER POWER SERIES

Eaton COOPER POWER SERIES Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Eaton COOPER POWER SERIES Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the purpose of the Eaton COOPER POWER SERIES insulated protective cap?
    What standards does the insulated protective cap comply with?
    Does the cap require special tools for installation?
    What tests are conducted on the insulated protective cap?
    What are the voltage ratings and characteristics of the 15 kV class insulated protective cap?
    What does the insulated protective cap kit include?
General
Eaton's Cooper Power™ series insulated
protective cap is an accessory device
designed to electrically insulate and
mechanically seal loadbreak bushing inter-
faces. When mated to a loadbreak product
and the drain wire is attached to ground,
the insulated protective cap provides a fully
shielded, submersible insulating cover for
energized bushings. The cap can be used
for permanent or temporary installation on
bushings, junctions or feedthru devices that
meet the requirements of IEEE Std 386™-
2006 standard.
Installation
No special tools are required. A shotgun
stick tool is used to place the protective cap
on an exposed bushing interface. Refer to
Service Information S500-21-1 200 A 15, 25,
and 35 kV Class Insulated Protective Cap
Installation Instructions for details.
Production tests
Tests are conducted in accordance with
IEEE Std 386™-2006 standard.
AC 60 Hz 1 Minute Withstand
34 kV
Minimum Corona Voltage Level
11 kV
Tests are conducted in accordance with
Eaton requirements.
Physical Inspection
Periodic Dissection
Periodic Fluoroscopic Analysis
200 A 15 kV class insulated
protective cap
Loadbreeak
Connectors
CA650 076EN
Effective November 2015
Supersedes 500-21 April 1996
COOPER POWER
SERIES
Ordering information
To order the 15 kV Class Insulated Protective Cap Kit, refer to Table 2.
Each kit contains:
Protective Cap with stranded copper ground wire
Silicone Lubricant
Installation Instruction Sheet
Features and detailed description
Figure 1. Illustration shows construction of insulated protective cap.
SEMI-CONDUCTIVE SHIELD
Molded semi-conductive EPDM
shield meets requirements of
ANSI/IEEE Standard 592.
LATCHING RING
Semi-conductive molded
locking ring locks cap
onto nose piece of mating
interface.
GROUNDING WIRE AND
GROUNDING EYE
48-Inch, #14 AWG stranded
copper ground wire is tin
plated and ensures dead-
front construction when tied
off to
g
round.
GROUNDING EYE
(Optional for larger
grounding wire)
PULLING EYE
Stainless steel reinforced
pulling eye ensures high
strength for shotgun stick
operation.
SEMI-CONDUCTIVE INSERT
Semi-conductive insert is molded of
semi-conductive EPDM and controls
electrical stresses at nose of mating
loadbreak product.
PROBE
Probe provides reliable
conductive path with
mating female contacts.
EPDM INSULATION
High quality peroxide
cured EPDM insulation
is mixed and formulated
in-house for complete
control of insulating
rubber characteristics.
Figure 2. 15 kV insulated protective cap profile and stacking
dimensions.
02.82
(71.5 mm)
S3 = 2.15
(54.5 mm)
Table 1. Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 15
Maximum Rating Phase-to-Phase 14.4
Maximum Rating Phase-to-Ground 8.3
AC 60 Hz 1 Minute Withstand 34
DC 15 Minute Withstand 53
BIL and Full Wave Crest 95
Minimum Corona Voltage Level 11
Table 2. Insulated Protective Cap Kit
Description Catalog Number
Protective Cap LPC 215
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006.
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
200 A 15 kV class insulated protective capCatalog Data CA650076EN
Effective November 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. CA650076EN
For Eaton's Cooper Power series product
information call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.
/