WayPoint17A - 3 -
11. Measure output voltage on terminals marked [COM, 24V, 28V] on WayPoint17AU and WayPoint17ADU
(Fig. 2, pg. 4) or [1-4 or 1-8 COM] on WayPoint17A4U, WayPoint17A4DU, WayPoint17A8U and
WayPoint17A8DU before connecting devices (Fig. 3, pg. 5, Fig. 4, pg. 6). This helps avoiding potential damage.
12. Set illuminated master power disconnect circuit breaker to the [OFF] position (Figs. 2-4, pgs. 4-6).
13. Connecting devices to WayPoint17AU or WayPoint17ADU:
For 24VAC output connect devices to terminals marked [COM, 24V] (Fig. 2, pg. 4).
For 28VAC output connect devices to terminals marked [COM, 28V] (Fig. 2, pg. 4).
Connecting devices to WayPoint17A4U or WayPoint17A4DU:
Connect device to terminals marked [1-4] and [COM] (Fig. 3, pg. 5).
Connecting devices to WayPoint17A8U or WayPoint17A8DU:
Connect device to terminals marked [1-8] and [COM] (Fig. 4, pg. 6).
14. Set illuminated master power disconnect circuit breaker to the [RESET/ON] position (Figs. 2-4, pgs. 4-6).
15. LEDs will illuminate indicating each output is powered (Figs. 2-4, pgs. 4-6).
16. Upon completion of wiring secure enclosure door with latches and optional lock.
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: When installing in a non-restricted service area use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
LED Identification Chart:
ON OFF
Normal operating condition.
No AC output. Blown fuse or tripped PTC, illuminated master power
disconnect circuit breaker is tripped or OFF, AC failure.
Technical Specifications:
Parameter Description
Input power
requirements
Input: 115VAC, 60Hz, 2A or 230VAC, 50Hz, 1A.
Indicators
Individual power output LED indicators.
Illuminated master power switch.
Environmental
Conditions
Operating Ambient Temperature:
140ºF (60°C) for 24VAC @ 7.25A (174VA) output
or 158ºF (70°C) for 28VAC @ 6.25A (175VA) output.
Relative Humidity: 85%, +/--- 5%
Storage Temperature: --- 40ºF to 167ºF (-40ºC to 75ºC).
Operating Altitude: --- 1000 to 6,561.679 ft. (--- 304.8 to 2000m).
Regulatory
Compliance
UL/cUL Listed for Information Technology Equipment (UL 60950-1) and
Equipment to be Installed Outdoors (UL 60950-22).
CE European Conformity.
For fuse protected models:
Replace fuses with the same type and rating 5A/32V.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
5A