Sensor and System Wiring Diagrams
9
Hazardous Location Wiring
IMPORTANT: Refer to section 9 for Hazardous Location Wiring.
NOTE: For APG Modbus programming instructions, please see MPI
user manual. APG Modbus software can be downloaded from www.
apgsensors.com/support.
MPI-E/R Intrinsically Safe Modbus System Wiring MPI-E/R Intrinsically Safe Modbus System Wiring with RST-6001
IMPORTANT: MPI level sensor MUST be installed according to drawing 9005491
(Intrinsically Safe Installation Drawing for Hazardous Areas) in section 9 to meet listed
approvals. Faulty installation will invalidate all safety approvals and ratings.
DANGER: WARNING -- EXPLOSION HAZARD -- SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- LA SUBSTITIOND E COMPOSANTSP EUTR
ENDRE CE MATERIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
DANGER: WARNING -- EXPLOSION HAZARD -- DO NOT DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-
HAZARDOUS;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- AVANT DE DECONNECTER L’EQUIPEMENT,
COUPER LE COURANT OU S’ASSURER QUE L’EMPLACEMENT EST DESIGNE NON
DANGEREUX.
DANGER: OPEN CIRCUIT BEFORE REMOVING COVER or KEEP COVER TIGHT WHILE
CIRCUITS ARE ALIVE;
AVERTISSEMENT -- COUPER LE COURANTAVANT D’ENLEVER LE COUVERCLE, ou GARDER
LE COUVERCLE FERME TANT QUE LES CIRCUITS SONT SOUS TENSION.
7
General Care
Your level sensor is very low maintenance and will need little care as long as it was installed
correctly. However, in general, you should periodically inspect your MPI unit to ensure the stem
is free of any heavy buildup that might impede the movement of the oat(s). If sediment or other
foreign matter becomes trapped between the stem and oat(s), detection errors can occur.
If you need to remove the oats(s) from the stem of your MPI, be sure to note the orientation of the
oat(s) prior to removal. This will help ensure proper re-installation of the oat(s).
Also, ensure that the housing cover is snuggly secured. If the cover becomes damaged or is
misplaced, order a replacement immediately.
8
Repair Information
The MPI-E Chemical’s chemical resistant coating is a durable thermoplastic. This means that if
damage occurs, repair is possible:
• Use a heat gun on a low setting to heat the damaged location until coating becomes soft and
malleable. If coating begins to ripple or bubble, too much heat has been applied.
• With a blunt object, gently smear the coating to recover the damaged area.
• Allow chemical resistant coating patch to cool before reinstalling probe.
• Keep MPI-E Chemical probe and chemical resistant coating away from ammable material
during patching process.
If your MPI level sensor needs repair, contact us via email, phone, or online chat on our website. We
will issue you an RMA number with instructions.
• Phone: 888-525-7300
• Online chat at www.apgsensors.com
NOTE: For MPI-E Chemical sensors: Chemical resistant coating will
scar and expose stainless steel if scraped or abused. Use caution
when handling. Always transport in packaging to protect probe and
coating.
IMPORTANT: All repairs and adjustments of the MPI level sensor must be made by the
factory. Modifying, disassembling, or altering the MPI, other than patching the chemical
resistant coating on an MPI-E Chemical probe, is strictly prohibited.
Power
Supply
+8-24 Vdc
GND
Use Shielded Cable
120 Ω terminating resistor
may be necessary for long
cable runs.
V+
B (TX-)
A (TX+)
Sensor 1
GND
V+
B (TX-)
A (TX+)
Sensor 2
GND
V+
B (TX-)
A (TX+)
Sensor 3
GND
Master
Device
RS-485 A (TX+)
RS-485 B (TX-)
MPI Sensor MPI Sensor MPI Sensor
Note: When connecting MPI
sensors to your system, reversing
A and B connections may be necessary
if sensors do not communicate with
Modbus Master device.
120 Ω terminating resistor across A & B
terminals of last or only sensor, if necessary.
For installations without IS barriers only.
Wiring T’s must be located on
controller/supply side of IS barriers.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
Power
Supply
+8-24 Vdc
GND
Use Shielded Cable
Equivalent 120 Ω
terminating resistor
internal to RST-6001
USB to computer
with APG Modbus
software
RST-6001
Modbus
Controller
V+
B
A
Sensor 1
GND
V+
B
A
Sensor 2
GND
V+
B
A
Sensor 3
GND
A
B
-5V
MPI sensor
+5V
MPI sensor MPI sensor
Note: An independent +8-24 Vdc
power supply is required when using
an RST-6001 Modbus Controller. The
RST-6001 can only supply ±5 Vdc, not
the +8-24 Vdc required by the MPI.
Wiring T’s must be located on
controller/supply side of IS barriers.
120 Ω terminating resistor across A & B
terminals of last or only sensor, if necessary.
For installations without IS barriers only.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
See Hazardous Installation
Drawing for Intrinsically Safe
installation requirements.
Otherwise, wire directly.
APPROVALS DATE
FINISH
MATL
APVD
CHKD
DRWN
SIZE
A
VERON TNEMUCODON TRAPEDOC EGAC
SHEET OF
CONTRACT
888.525.7300
Logan, Utah USA
1025 West 1700 North
APPROVEDDATECHANGE ORDERDESCRIPTIONREVZONE
REVISIONS
CO-3441 retsedihC .C8102/92/8.esaeler laitinI-- A
C. Chidester
S. Hutchins
R. Barson
6/5/2018
8/29/2018
8/29/2018
A
11
for Hazardous Locations
Intrinsically Safe Installation Drawing
MPI Series
PROPRIETARY AND CONFIDENTIAL
LOGAN, UTAH AND MAY NOT BE
USED, REPRODUCED, PUBLISHED, OR
IN ANY WAY DIRECTLY OR INDIRECTLY
THIS DRAWING IS THE PROPERTY OF
AUTOMATION PRODUCTS GROUP, INC.
DISCLOSED TO OTHERS WITHOUT
IF LOANED, IT IS SUBJECT TO RETURN
UPON DEMAND AND MAY NOT BE USED
WRITTEN CONSENT OF THE COMPANY.
DETRIMENTAL TO THE COMPANY.
9005491VARIOUS
RS-485 B
RS-485 A
V+
V- (GND)
MPI
Vmax (or Ui) = 28V
Unclassified Location
Imax (or Ii) = 280mA
Pi = 850mW
Ci = 0.374uF
Li = 3.50uH
Associated Apparatus
Voc (or Uo) ≤ Vmax (or Ui)
Hazardous Location
Class I, Zone 0, AEx ia IIB T4 Ga
Isc (or Io) ≤ Imax (or Ii)
Po ≤ Pi
Ca (or Co) ≥ Ci + Ccable
La (or Lo) ≥ Li + Lcable
with Entity Parameters
Ex ia IIB T4 Ga, Ta -40°C to 85°C
- Installation must be in accordance with NEC Articles 504 and 505.
Class I, Division 1, Groups C,D T4
52797
MDI
Modbus Address: Master
Controling: Sensor 1
MPI Sensor
Modbus Address: 1
Hazardous Area
Zone 1
Zone 0 or Zone 1
MDI
Modbus Address: Master
Controling: Sensor 1
MPI Sensor
Modbus Address: 1
Hazardous AreaNon-hazardous Area
Approved
IS Barrier
Passive Control Equipment
Modbus: Sniffer
Sniffing: MDI
Zone 1
Zone 0 or Zone 1
MPI - MDI Use Case Diagram MPI - MDI with Passive Controller Use Case Diagram