Samsung NS1254DXEA User manual

Category
Split-system air conditioners
Type
User manual
Cassette Type Series
AC777FB4DEH
AC777FB4PEH
AC777FB4FEH
NS7774PXEA
NS7774DXEA
NS7774ZXEA
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Preparation for installation ............................................................................................................................................................................................... 3
Deciding on where to install the indoor unit ........................................................................................................................................................... 4
Indoor unit installation ....................................................................................................................................................................................................... 8
Purging the unit ..................................................................................................................................................................................................................... 9
Connecting the refrigerant pipe .................................................................................................................................................................................... 9
Cutting/Flaring the pipes ............................................................................................................................................................................................... 10
Performing leak test & insulation ............................................................................................................................................................................... 11
Drainpipe and drain hose installation ...................................................................................................................................................................... 12
Installing DPM ..................................................................................................................................................................................................................... 14
Connecting the connection cord ............................................................................................................................................................................... 15
Installation Procedure ........................................................................................................................................................................................................ 16
Setting an indoor unit address and installation option ..................................................................................................................................... 18
Troubleshooting ................................................................................................................................................................................................................. 25
Contents
Safety precautions
Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
t"MXBZTEJTDPOOFDUUIFBJSDPOEJUJPOFSGSPNUIFQPXFSTVQQMZCFGPSFTFSWJDJOHJUPSBDDFTTJOH
its internal components.
t7FSJGZUIBUJOTUBMMBUJPOBOEUFTUJOHPQFSBUJPOTBSFQFSGPSNFECZRVBMJGJFEQFSTPOOFM
t7FSJGZUIBUUIFBJSDPOEJUJPOFSJTOPUJOTUBMMFEJOBOFBTJMZBDDFTTJCMFBSFB
General information
X
Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be able
to use it as reference after installation.
X
For maximum safety, installers should always carefully read the following warnings.
X
4UPSFUIFPQFSBUJPOBOEJOTUBMMBUJPONBOVBMJOBTBGFMPDBUJPOBOESFNFNCFSUPIBOEJUPWFSUPUIFOFXPXOFSJGUIFBJSDPOEJUJPOFSJT
sold or transferred.
X
5IJTNBOVBMFYQMBJOTIPXUPJOTUBMMBOJOEPPSVOJUXJUIBTQMJUTZTUFNXJUIUXP4".46/(VOJUT5IFVTFPGPUIFSUZQFTPGVOJUTXJUI
EJòFSFOUDPOUSPMTZTUFNTNBZEBNBHFUIFVOJUTBOEJOWBMJEBUFUIFXBSSBOUZ5IFNBOVGBDUVSFSTIBMMOPUCFSFTQPOTJCMFGPSEBNBHFT
BSJTJOHGSPNUIFVTFPGOPODPNQMJBOUVOJUTW
X
The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of
FMFDUSJDBOESFRVJSFNFOUTTFUGPSUIJOUIFi0QFSBUJOHMJNJUTwUBCMFJODMVEFEJOUIFNBOVBMTIBMMJNNFEJBUFMZJOWBMJEBUFUIFXBSSBOUZ
X
The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable to be
installed in areas used for laundry.
X
Do not use the units if damaged. If problems occur, switch the unit o and disconnect it from the power supply.
X
*OPSEFSUPQSFWFOUFMFDUSJDTIPDLTöSFTPSJOKVSJFTBMXBZTTUPQUIFVOJUEJTBCMFUIFQSPUFDUJPOTXJUDIBOEDPOUBDU4".46/(T
UFDIOJDBMTVQQPSUJGUIFVOJUQSPEVDFTTNPLFJGUIFQPXFSDBCMFJTIPUPSEBNBHFEPSJGUIFVOJUJTWFSZOPJTZ
X
"MXBZTSFNFNCFSUPJOTQFDUUIFVOJUFMFDUSJDDPOOFDUJPOTSFGSJHFSBOUUVCFTBOEQSPUFDUJPOTSFHVMBSMZ5IFTFPQFSBUJPOTTIPVMECF
QFSGPSNFECZRVBMJöFEQFSTPOOFMPOMZ
X
5IFVOJUDPOUBJOTNPWJOHQBSUTXIJDITIPVMEBMXBZTCFLFQUPVUPGUIFSFBDIPGDIJMESFO
X
%POPUBUUFNQUUPSFQBJSNPWFBMUFSPSSFJOTUBMMUIFVOJU*GQFSGPSNFECZVOBVUIPSJ[FEQFSTPOOFMUIFTFPQFSBUJPOTNBZDBVTF
FMFDUSJDTIPDLTPSöSFT
X
%POPUQMBDFDPOUBJOFSTXJUIMJRVJETPSPUIFSPCKFDUTPOUIFVOJU
X
"MMUIFNBUFSJBMTVTFEGPSUIFNBOVGBDUVSFBOEQBDLBHJOHPGUIFBJSDPOEJUJPOFSBSFSFDZDMBCMF
X
The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with current laws.
X
5IFBJSDPOEJUJPOFSDPOUBJOTBSFGSJHFSBOUUIBUIBTUPCFEJTQPTFEPGBTTQFDJBMXBTUF"UUIFFOEPGJUTMJGFDZDMFUIFBJSDPOEJUJPOFS
must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly and safely.
Installing the unit
*.1035"/58IFOJOTUBMMJOHUIFVOJUBMXBZTSFNFNCFSUPDPOOFDUöSTUUIFSFGSJHFSBOUUVCFTUIFOUIFFMFDUSJDBMMJOFT
"MXBZTEJTBTTFNCMFUIFFMFDUSJDMJOFTCFGPSFUIFSFGSJHFSBOUUVCFT
X
6QPOSFDFJQUJOTQFDUUIFQSPEVDUUPWFSJGZUIBUJUIBTOPUCFFOEBNBHFEEVSJOHUSBOTQPSU*GUIFQSPEVDUBQQFBSTEBNBHFE
%0/05*/45"--JUBOEJNNFEJBUFMZSFQPSUUIFEBNBHFUPUIFDBSSJFSPSSFUBJMFSJGUIFJOTUBMMFSPSUIFBVUIPSJ[FEUFDIOJDJBOIBT
collected the material from the retailer.)
X
"GUFSDPNQMFUJOHUIFJOTUBMMBUJPOBMXBZTDBSSZPVUBGVODUJPOBMUFTUBOEQSPWJEFUIFJOTUSVDUJPOTPOIPXUPPQFSBUFUIFBJS
conditioner to the user.
X
%POPUVTFUIFBJSDPOEJUJPOFSJOFOWJSPONFOUTXJUIIB[BSEPVTTVCTUBODFTPSDMPTFUPFRVJQNFOUUIBUSFMFBTFGSFFøBNFTUPBWPJE
UIFPDDVSSFODFPGöSFTFYQMPTJPOTPSJOKVSJFT
WARNING
3
ENGLISH
8IFOEFDJEJOHPOUIFMPDBUJPOPGUIFBJSDPOEJUJPOFSXJUIUIFPXOFSUIFGPMMPXJOHSFTUSJDUJPOTNVTUCFUBLFOJOUPBDDPVOU
X
Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both
TJEFTBOEBMMPXSFQBJSTPSNBJOUFOBODFPQFSBUJPOTUPCFDBSSJFEPVU5IFVOJUTDPNQPOFOUTTIPVMECFBDDFTTJCMFBOEFBTZUP
EJTBTTFNCMFXJUIPVUFOEBOHFSJOHQFPQMFBOEPCKFDUT
'PSUIJTSFBTPOXIFOQSPWJTJPOTPGUIFJOTUBMMBUJPONBOVBMBSFOPUDPNQMJFEXJUIUIFDPTUSFRVJSFEUPBDDFTTBOESFQBJSUIFVOJUT
JO4"'&5:$0/%*5*0/4BTTFUPVUJOQSFWBJMJOHSFHVMBUJPOTXJUIIBSOFTTFTMBEEFSTTDBòPMEJOHPSBOZPUIFSFMFWBUJPOTZTUFNXJMM
/05CFDPOTJEFSFEQBSUPGUIFXBSSBOUZBOEXJMMCFDIBSHFEUPUIFFOEDVTUPNFS
Power supply line, fuse or circuit breaker
X
"MXBZTNBLFTVSFUIBUUIFQPXFSTVQQMZJTDPNQMJBOUXJUIDVSSFOUTBGFUZTUBOEBSET"MXBZTJOTUBMMUIFBJSDPOEJUJPOFSJODPNQMJBODF
with current local safety standards.
X
"MXBZTWFSJGZUIBUBTVJUBCMFHSPVOEJOHDPOOFDUJPOJTBWBJMBCMF
X
7FSJGZUIBUUIFWPMUBHFBOEGSFRVFODZPGUIFQPXFSTVQQMZDPNQMZXJUIUIFTQFDJöDBUJPOTBOEUIBUUIFJOTUBMMFEQPXFSJTTVóDJFOU
to ensure the operation of any other domestic appliance connected to the same electric lines.
X
"MXBZTWFSJGZUIBUUIFDVUPòBOEQSPUFDUJPOTXJUDIFTBSFTVJUBCMZEJNFOTJPOFE
X
7FSJGZUIBUUIFBJSDPOEJUJPOFSJTDPOOFDUFEUPUIFQPXFSTVQQMZJOBDDPSEBODFXJUIUIFJOTUSVDUJPOTQSPWJEFEJOUIFXJSJOHEJBHSBN
included in the manual.
X
"MXBZTWFSJGZUIBUFMFDUSJDDPOOFDUJPOTDBCMFFOUSZTFDUJPOPGMFBETQSPUFDUJPOTyBSFDPNQMJBOUXJUIUIFFMFDUSJDTQFDJöDBUJPOT
BOEXJUIUIFJOTUSVDUJPOTQSPWJEFEJOUIFXJSJOHTDIFNF"MXBZTWFSJGZUIBUBMMDPOOFDUJPOTDPNQMZXJUIUIFTUBOEBSETBQQMJDBCMF
to the installation of air conditioners.
X
%FWJDFTEJTDPOOFDUFEGSPNUIFQPXFSTVQQMZTIPVMECFDPNQMFUFMZEJTDPOOFDUFEJOUIFDPOEJUJPOPGPWFSWPMUBHFDBUFHPSZ
Do NOT install the air conditioner in a location where it will come into contact with the following elements :
X
Combustible gases
X
Saline air
X
Machine oil
X
Sulphide gas
X
4QFDJBMFOWJSPONFOUBMDPOEJUJPOT
*GZPVNVTUJOTUBMMUIFVOJUJOTVDIDPOEJUJPOTöSTUDPOTVMUZPVSEFBMFS
Avoid installing the air conditioner :
X
In areas where it is exposed to direct sunlight. Close to heat sources.
X
In damp areas or locations where it could come into contact with water. (for example rooms used for laundry)
X
In areas where curtains and furniture could aect the supply and discharge of air.
X
8JUIPVUMFBWJOHUIFSFRVJSFENJOJNVNTQBDFBSPVOEUIFVOJUBTTIPXOJOUIFESBXJOH
X
*OTDBSDFMZWFOUJMBUFEBSFBT
X
0OTVSGBDFTUIBUBSFVOBCMFUPTVQQPSUUIFXFJHIUPGUIFVOJUXJUIPVUEFGPSNJOHCSFBLJOHPSDBVTJOHWJCSBUJPOT
during the use of the air conditioner.
X
In a position that does not enable the condensate drainage pipe to be correctly installed. (at the end of the
JOTUBMMBUJPO*UJTBMXBZTFTTFOUJBMUPDIFDLUIFFóDJFODZPGUIFESBJOBHFTZTUFN
General
Preparation for installation
X
Make sure that you earth the cables.
%POPUDPOOFDUUIFFBSUIXJSFUPUIFHBTQJQFXBUFSQJQFMJHIUJOHSPEPSUFMFQIPOFXJSF*GFBSUIJOHJTOPU
DPNQMFUFFMFDUSJDTIPDLPSöSFNBZPDDVS
X
Install the circuit breaker.
*GUIFDJSDVJUCSFBLFSJTOPUJOTUBMMFEFMFDUSJDTIPDLPSöSFNBZPDDVS
X
Make sure that the condensed water dripping from the drain hose runs out properly and safely.
X
Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric appliance.
X
Install the indoor unit away from lighting apparatus using the ballast.
*GZPVVTFUIFXJSFMFTTSFNPUFDPOUSPMSFDFQUJPOFSSPSNBZPDDVSEVFUPUIFCBMMBTUPGUIFMJHIUJOHBQQBSBUVT
X
Do not install the air conditioner in following places.
1MBDFXIFSFUIFSFJTNJOFSBMPJMPSBSTFOJDBDJE3FTJOQBSUTøBNFBOEUIFBDDFTTPSJFTNBZESPQPSXBUFSNBZ
leak. The capacity of the heat exchanger may reduce or the air conditioner may be out of order.
5IFQMBDFXIFSFDPSSPTJWFHBTTVDIBTTVMGVSPVTBDJEHBTHFOFSBUFTGSPNUIFWFOUQJQFPSBJSPVUMFU
The copper pipe or connection pipe may corrode and refrigerant may leak.
5IFQMBDFXIFSFUIFSFJTBNBDIJOFUIBUHFOFSBUFTFMFDUSPNBHOFUJDXBWFT5IFBJSDPOEJUJPOFSNBZOPUPQFSBUF
normally due to control system.
5IFQMBDFXIFSFUIFSFJTBEBOHFSPGFYJTUJOHDPNCVTUJCMFHBTDBSCPOöCFSPSøBNNBCMFEVTU
5IFQMBDFXIFSFUIJOOFSPSHBTPMJOFJTIBOEMFE(BTNBZMFBLBOEJUNBZDBVTFöSF
4
Deciding on where to install the indoor unit
Preparation for installation
X The following accessories are supplied with the indoor unit.
5IFUZQFBOERVBOUJUZNBZEJòFSEFQFOEJOHPOUIFTQFDJöDBUJPOT
Indoor unit
Space requirements for indoor unit
Accessories
X
There must be no obstacles near the air inlet and outlet.
X
Install the indoor unit on a ceiling that can support its weight.
X
.BJOUBJOTVóDJFOUDMFBSBODFBSPVOEUIFJOEPPSVOJU
X
Make sure that the water dripping from the drain hose runs away correctly and safely.
X
5IFJOEPPSVOJUNVTUCFJOTUBMMFEJOUIJTXBZUIBUUIFZBSFPVUPGQVCMJDBDDFTT/PUUPVDIBCMFCZUIFVTFST
*OTVMBUJPODPWFS
band
Insulation pipe $BCMFUJF Drain hose
Installation
manual
Clamp
t *GZPVJOTUBMMUIFDBTTFUUFUZQFJOEPPSVOJUPOUIFDFJMJOHXJUIIVNJEJUZPWFSZPVNVTUBQQMZFYUSBNNPG
polyethylene foam or other insulation with similar material on the body of the indoor unit.
5
ENGLISH
t 5IFVOJUTNVTUCFJOTUBMMFEBDDPSEJOHUPEJTUBODFTEFDMBSFEJO
order to permit accessibility from each side,
either to guarantee correct operation of maintenance or
repairing products.
5IFVOJUTQBSUTNVTUCFSFBDIBCMFBOESFNPWBCMFDPNQMFUFMZ
under safety condition (for people or things).
t %POPUIPMEUIFEJTDIBSHFXIJMFDBSSZJOHUIFJOEPPSVOJUUPBWPJEUIFQPTTJCJMJUZPGCSFBLBHF:PVNVTUIPMEUIF
hanger plate on the corner and carry the indoor unit.
X 8IFOJOTUBMMJOHBDBTTFUUFUZQFJOEPPSVOJUPOUIFDFJMJOHBOEJUTJOTUBMMBUJPODPOEJUJPOJTUFNQFSBUVSFPWFS¡$BOE
IVNJEJUZPWFSJOTUBMMBNNUIJDLOFTTPGQPMZFUIZMFOFJOTVMBUJPOPSTJNJMBSUZQFPGJOTVMBUJPOPOUIFJOEPPSVOJU
body.
Insulation installation guide
X $VUUIFQBSUXIFSFQJQFTBSFQVMMFEPVUPSTPNFDVSWFEQBSUGPSJOTVMBUJOHXPSL
X 8IFOJOTVMBUJOHBDPOOFDUJOHEVDUUIFPVUMFUBOEJOMFUQBSUGSPOUCBDLTIPVMECF
insulated together.
X *OTVMBUFUIFFOEPGUIFQJQFBOETPNFDVSWFEBSFBCZVTJOHTFQBSBUFJOTVMBUPS
Thickness: more than 10mm
Indoor unit " BCD&
Cassette type
XBZ$BTTFUUF-
(840x288x840)
77090FB4P77
77100FB4P77
77100FB4F77
770904PX77
7712547X77
771004PX77
771004ZX77
910X235 940X235 610X235 650X235 9
XBZ$BTTFUUF.
(840x246x840)
77'#177
77090FB4D77
77100FB4D77
771977
770904DX77
771004DX77
910X193 940X193 610X193 650X193 9
XBZ$BTTFUUF4
(840x204x840)
77052FB4D77
77'#%77
77%977
910X151 940X151 610X151 650X151 9
D
"
C
B
&
6
Deciding on where to install the indoor unit
.0%&-
77052FB4D77
77'#%77
77%977
77'#177
77090FB4D77
77100FB4D77
771977
770904DX77
771004DX77
77090FB4P77
770904PX77
771254DX77
77100FB4P77
77100FB4F77
771004PX77
771004ZX77
771254PX77
771404PX77
771404DX77
C mm 251 293 335 335
/FUEJNFOTJPO mm 840×204×840 840×246×840 840×288×840 840×288×840
Required space for an indoor unit installation
Obstruction
20mm
NN
1500mm
or more
A$NN
2500mm or more
7
ENGLISH
6OJUNN
.0%&-
77052FB4D77
77'#%77
77%977
77'#177
771977
77090FB4D77
77100FB4D77
770904DX77
771004DX77
77090FB4P77
770904PX77
771254DX77
77100FB4P77
77100FB4F77
771004PX77
771004ZX77
771254PX77
771404DX77
771404PX77
" mm 204 246 288
B mm 253 295 
/FUEJNFOTJPO mm 840 X 204 X 840 840 X 246 X 840 840 X 288 X 840
/FUXFJHIU kg 15.0 16.0 18.0 20.0
-JRVJEQJQFDPOOFDUJPO 1/4" 3/8"
(BTQJQFDPOOFDUJPO 1/2" 5/8"
Drain Hose connection mm OD : Φ32.0, ID : Φ26.5
Drawing of the indoor unit
890~910 (Celling opening)
950
4VTQFOTJPOQPTJUJPO
890~910 (Celling opening)
4VTQFOTJPOQPTJUJPO
Sub duct connection
55 840

346
185
96
950
120
45
86
164
216
55 55840
330 240

300
8
Indoor unit installation
Ceiling support
Pad stopper
Bracket
Ceiling
NN
20mm
Indoor unit
(BVHFPG
Dimensions
Concrete
4VTQFOTJPOCPMU.GJFMETVQQMZ
Hole in anchor
Hole in plug
Insert
8IFOEFDJEJOHPOUIFMPDBUJPOPGUIFBJSDPOEJUJPOFSXJUIUIFPXOFSUIFGPMMPXJOHSFTUSJDUJPOTNVTUCFUBLFOJOUPBDDPVOU
1. Determine the position of the pipe and drain hose hole as seen in the
picture and drill the hole with an inner diameter of 65mm so that it slants
slightly downwards.
2. Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in gure.
3. Install the suspension bolts depending on the ceiling type.
4. Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
5. Hang the indoor unit to the suspension bolts between two nuts.
6. Screw the nuts to suspend the unit. Cut a pad stopper and place it on the
bracket at this time.
7. Adjust the unit to the appropriate position considering the installation area
for the front panel.
1) Place the pattern sheet on the indoor unit.
"EKVTUBTQBDFCFUXFFOUIFDFJMJOHBOEUIFJOEPPSVOJUCZVTJOHUIFHBVHF
of dimensions.
'JYUIFJOEPPSVOJUTFDVSFMZBGUFSBEKVTUJOHMFWFMPGUIFVOJUCZVTJOHB
MFWFMFS
3FNPWFUIFQBUUFSOTIFFUDPOOFDUUIFPUIFSDBCMFTBOEJOTUBMMUIFGSPOU
panel.
t 4JODFUIFEJBHSBNJTNBEFPGQBQFSJUNBZTISJOLPSTUSFUDITMJHIUMZ
due to temperature or humidity. For this reason, before drilling the
holes maintain the correct dimensions between the markings.
t 1JQJOHNVTUCFMBJEBOEDPOOFDUFEJOTJEFUIFDFJMJOHXIFO
suspending the unit. If the ceiling is already constructed, lay the
piping into position for connection to the unit before placing the unit
inside the ceiling.
t &OTVSFUIBUUIFDFJMJOHJTTUSPOHFOPVHIUPTVQQPSUUIFXFJHIUPGUIF
indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
t *GUIFMFOHUIPGTVTQFOTJPOCPMUJTNPSFUIBONJUJTSFRVJSFEUP
QSFWFOUWJCSBUJPO
t :PVNVTUJOTUBMMBMMUIFTVTQFOTJPOSPET
t *UJTJNQPSUBOUUPMFBWFTVóDJFOUTQBDFJOUIFGBMTFDFJMJOHUPBMMPX
access for maintenance or repairs to the drainage pipe connection,
UIFSFGSJHFSBOUQJQFDPOOFDUJPOPSUPSFNPWFUIFVOJUJGOFDFTTBSZ
9
ENGLISH
There are two refrigerant pipes of dierent diameters :
X
"TNBMMFSPOFGPSUIFMJRVJESFGSJHFSBOU
X
"MBSHFSPOFGPSUIFHBTSFGSJHFSBOU
X
The inside of copper pipe must be clean & has no dust
1. Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, rst manually
and then with a torque wrench, a spanner applying the following torque.
2. Must use insulator which is thick enough to cover the refrigerant tube to protect the condensate water on the outside
of pipe falling onto the oor and the eciency of the unit will be better.
3. Cut o any excess foam insulation.
4. Be sure that there must be no crack or wave on the bended area.
5. It would be necessary to double the insulation thickness(10mm or more) to prevent condensation even on the
insulator when if the installed area is warm and humid.
6. Do not use joints or extensions for the pipes that connect the indoor and outdoor unit. The only permitted connections
are those for which the units are designed.
Purging the unit
'SPNGBDUPSZUIFVOJUJTTVQQMJFEBOETFUXJUIBQSFDIBSHFPGOJUSPHFOHBTJOTFSUHBT5IFSFGPSFBMMJOTFSUHBTNVTUCFQVSHFE
before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
3&46-5"MMJOFSUHBTFTDBQFTGSPNUIFJOEPPSVOJU
t 5PQSFWFOUEJSUPSGPSFJHOPCKFDUTGSPNHFUUJOHJOUPUIFQJQFTEVSJOH
JOTUBMMBUJPOEP/05SFNPWFUIFQJODIQJQFDPNQMFUFMZVOUJMZPVBSF
ready to connect the piping.
t *GUIFQJQFTNVTUCFTIPSUFOFESFGFSUPQBHF
t $POOFDUUIFJOEPPSBOEPVUEPPSVOJUTVTJOHQJQFTXJUIøBSFEDPOOFDUJPOTOPUTVQQMJFE'PSUIFMJOFTVTF
JOTVMBUFEVOXFMEFEEFHSFBTFEBOEEFPYJEJ[FEDPQQFSQJQF$V%)1UZQFUP*40PS6/*&/TVJUBCMF
GPSPQFSBUJOHQSFTTVSFTPGBUMFBTUL1BBOEGPSBCVSTUQSFTTVSFPGBUMFBTUL1B$PQQFSQJQFGPSIZESP
sanitary applications is completely unsuitable.
t 'PSTJ[JOHBOEMJNJUTIFJHIUEJòFSFODFMJOFMFOHUINBYCFOETSFGSJHFSBOUDIBSHFFUDTFFUIFPVUEPPSVOJU
installation manual.
t "MMSFGSJHFSBOUDPOOFDUJPONVTUCFBDDFTTJCMFJOPSEFSUPQFSNJUFJUIFSVOJUNBJOUFOBODFPSSFNPWJOHJUDPNQMFUFMZ
Refrigerant oil
Spanner
6OJPO
Torque wrench
Flare nut
Outer Diameter (D) 5PSRVF/tN
ø6.35 mm 14~18
ø9.52 mm 34~42
NN 49~61
ø15.88 mm 68~82
ø19.05 mm 100~120
Connecting the refrigerant pipe
-JRVJETJEF
(BTTJEF
10
Cutting/Flaring the pipes
1. Make sure that you have the required tools available. (pipe cutter, reamer, aring tool and pipe holder)
2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle
with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.
3. To prevent any gas from leaking out, remove all burrs at the cut edge of the pipe, using a reamer.
4. Slide a are nut on to the pipe and modify the are.
5. Check that the aring is correct, referring to the illustrations below for examples of incorrect aring.
6. Align the pipes and tighten the are nuts rst manually and then with a torque wrench, applying the following torque.
t *GUIFQJQFTSFRVJSFCSB[JOHFOTVSFUIBU0'/0YZHFO'SFF/JUSPHFOJTøPXJOHUISPVHIUIFTZTUFN
t /JUSPHFOCMPXJOHQSFTTVSFSBOHFJT_.1B
Oblique Rough
Burr
Pipe
cutter
Pipe
Outer Diameter (D) Depth (A)
ø6.35 mm 1.3 mm
ø9.52 mm 1.8 mm
NN 2.0 mm
ø15.88 mm 2.2 mm
ø19.05 mm 2.2 mm
Pipe
Flare
6OFWFO
Thickness
CrackedDamaged
Surface
InclinedCorrect
7BMWF
Flare nut 7BMWFDBQ Pressure port cap 7BMWFOFFEMF Pressure port
8SFODINN /tN 8SFODINN /tN 8SFODINN /tN 8SFODINN /tN 8SFODINN /tN
1/4"  18 23 20 18 16~18 "MMFOIFY 9 0.34
3/8" 22 42 23 20 18 16~18 "MMFOIFY 9 0.34
1/2" 26 55 29 40 18 16~18 "MMFOIFY 13 0.34
5/8" 29 65 29 40 18 16~18 "MMFOIFY 13 0.34
3/4" 36 100 38 40 18 16~18 "MMFOIFY 13 0.34
11
ENGLISH
To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant
pipe using a leak detector for R410A.
Before recreating the vacuum and recirculating the refrigerant gas, it is advisable to pressurize the
whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar in
order to immediately detect leaks on the refrigerant ttings.
Made vacuum for 15 minutes and pressurising system with nitrogen.
t *GUIFQJQFTSFRVJSFCSB[JOHFOTVSFUIBU0'/0YZHFO'SFF/JUSPHFOJTøPXJOHUISPVHIUIFTZTUFN
Leak test
Performing leak test & insulation
Once you have checked that there are no leaks in the system, you can insulate the piping and hose.
1
To avoid condensation problems, place Acrylonitrile Butadien Rubber separately
around each refrigerant pipe.
2 Wind insulating tape around the pipes and drain hose avoiding to compress
the insulation too much.
3
Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit.
4 The pipes and electrical cables connecting the indoor unit with the outdoor
unit must be xed to the wall with suitable ducts.
5 Select the insulation of the refrigerant pipe.
X Insulate the gas side and liquid side pipe referring to the thickness
according to the pipe size.
X-FTTUIBOJOEPPS
UFNQFSBUVSFPG¡$BOEIVNJEJUZPGJTUIFTUBOEBSE
condition. If installing in a high humidity condition, use one grade thicker insulator by referring to the table below.
*GJOTUBMMJOHJOBOVOGBWPSBCMFDPOEJUJPOTVTFUIJDLFSPOF
X*OTVMBUPSTIFBUSFTJTUBODFUFNQFSBUVSFTIPVMECFNPSFUIBO¡$
Insulation
/PHBQ
/#3
*OTVMBUJPODPWFSQJQF
Indoor unit
#FTVSFUPPWFSMBQ
the insulation
Insulation pipe
t .VTUöUUJHIUMZBHBJOTU
body without any gap.
t "MXBZTNBLFUIFTFBNPGQJQFTGBDFVQXBSET
t "MMSFGSJHFSBOUDPOOFDUJPONVTUCFBDDFTTJCMFJOPSEFSUPQFSNJU
FJUIFSVOJUNBJOUFOBODFPSSFNPWJOHJUDPNQMFUFMZ
Pipe
Pipe size
Insulation Type (Heating/Cooling)
RemarksStandard [Less than 30°C, 85%] High humidity [Over 30°C, 85%]
EPDM,NBR
-JRVJE
pipe
Ø6.35 ~ Ø9.52 9t 9t
Internal temperature is
IJHIFSUIBO¡$
_ 13t 13t
(BT
pipe
Ø6.35 13t 19t
Ø9.52
19t 25t

Ø15.88
Ø19.05
t 5IFJOTVMBUJPOIBTUPCFQSPEVDFEJOGVMMDPNQMJBODFPG&VSPQFBO
SFHVMBUJPOSFH&&$&6UIBU
requires the use of sheaths insulation form without using CFC and
)$'$HBTFTGPSIFBMUIBOEUIFFOWJSPONFOU
12
Drainpipe and drain hose installation
1 Push the supplied drain hose as far as possible over the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and x it with clamps.
4 Insulate the complete drain piping inside the building (eld supply).
If the drain hose cannot be suciently set on a slope, t the hose with drain raising piping (eld supply).
5 Push the drain hose up to insulation when connecting the drain hose to drain socket.
A-A
Drain socket
Drain piping
Drain hose
Metal clamp
-BSHFTFBMJOHQBE
Tighten the clamp to the maximum
until you can see eight holes.
X
8IFOJOTUBMMJOHJOTVMBUJPOJOQMBDFTBOEDPOEJUJPOTCFMPXVTFUIFTBNFJOTVMBUJPOUIBUJTVTFEGPSIJHI
humidity conditions.
(FPMPHJDBMDPOEJUJPO
)JHIIVNJEJUZQMBDFTTVDIBTTIPSFMJOFIPUTQSJOHOFBSMBLFPSSJWFSBOESJEHFXIFOUIFQBSUPGUIF
CVJMEJOHJTDPWFSFECZFBSUIBOETBOE
0QFSBUJPOQVSQPTFDPOEJUJPO
3FTUBVSBOUDFJMJOHTBVOBTXJNNJOHQPPMFUD
#VJMEJOHDPOTUSVDUJPODPOEJUJPO
5IFDFJMJOHGSFRVFOUMZFYQPTFEUPNPJTUVSFBOEDPPMJOHJTOPUDPWFSFE
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes
frequently.
5IFQMBDFXIFSFUIFQJQFJTJOTUBMMFEJTIJHIMZIVNJEEVFUPUIFMBDLPGWFOUJMBUJPOTZTUFN
Performing leak test & insulation
13
ENGLISH
t *GBDPODFOUSBUFEESBJOQJQFJTJOTUBMMFESFGFSUPUIFöHVSFCFMPX
Concentrated drain pipe
100mm or
more
1/100 or
more slope
"JSWFOUJMBUJPO
Check that the indoor unit is level with the ceiling by using the leveler.
"JSWFOUJMBUJPO
Ceiling
*OTUBMMBJSWFOUJMBUJPOUPESBJODPOEFOTBUFXBUFSTNPPUIMZ
%POPUHJWFUIFIPTFBOEVQXBSEHSBEJFOUBGUFSUIF
DPOOFDUJPOQPSU5IJTXJMMDBVTFXBUFSUPøPXCBDLXBSET
when the unit is stopped, resulting in water leaks.
6OEFSHSBEJFOU
Ceiling
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as close
to the unit as possible.
Support pieces
1~1.5m
Ceiling
1/100 or more
If it is necessary to increase the height of the drainpipe,
install the drainpipe straightly within 300 mm from the
drain hose port. If it is raised higher than 550 mm, there
can be water leaks.
300mm or less
Ceiling
20mm or more
Drain hose
#BOEKPJOU
1/100 or more
550mm or less
Install horizontally
Max. allowable bending angle
Max. allowable axis gap
Be horizontal
Indoor
6OJU
Flexible hose
Max. 20mm
Indoor
6OJU
Max. 30˚
Indoor
6OJU
14
AA
Drainpipe and drain hose installation
1. Check the leak test at the connection part of the exible hose and the
distributing pipe (PVC).
$POOFDUBHFOFSBMIPTFUPUIFDPOOFDUJPOQBSUPGUIFøFYJCMFIPTFPGUIF
indoor unit, and pour in some water.
"GUFSQPVSJOHTPNFXBUFSSFBTTFNCMFUIFSVCCFSDBQPOUIFDPOOFDUJPO
QBSUPGBøFYJCMFIPTFPGUIFJOEPPSVOJUBOEUJHIUFOJUXJUIBCBOEöSNMZUP
QSFWFOUMFBLBHF
$IFDLUIFMFBLUFTUBUUIFQBSUXIFSFUIFBEIFTJWFGPSUIFøFYJCMFIPTFBOE
the distributing pipe is used.
2. Check the condensed water drainage.
1) Pour about 2 liters of water into the indoor unit drain board as shown in the
picture.
2) 8IFOUIFFMFDUSJDDBCMFDPOOFDUJPOJTDPNQMFUFE
X Turn the indoor unit and outdoor unit on.
X Operate the Cool mode.
8IFOUIFFMFDUSJDDBCMFDPOOFDUJPOIBTOPUCFFODPNQMFUFE
X3FNPWFUIFDPOUSPMCPYDPWFSPGUIFJOEPPSVOJU
X$POOFDUUIFQPXFSTVQQMZPG7)[UP-/UFSNJOBM
X3FBTTFNCMFUIFDPOUSPMCPYDPWFSBOEUVSOPOUIFJOEPPSVOJU
3) Check whether the drain pump works correctly.
4) Check whether the drainage is performing correctly at the end of the drain pipe.
5) Check for leakage at the drain pipe and drain pipe connection part.
8IFOMFBLBHFPDDVSTDIFDLXIFUIFSUIFJOEPPSVOJUJTMFWFMBOEDIFDLUIFESBJOIPTFDPOOFDUJPOQBSUESBJOQJQF
connection part and drain pump connection.
8IFOUIFESBJOBHFDIFDLJTDPNQMFUFEBOEUIFDPOEFOTFEXBUFSSFNBJOTPOUIFESBJOCPBSESFNPWFUIFXBUFS
Testing the drainage
8BUFSMFBLBHF
check part
Hose
Installing DPM
8IFOJOTUBMMJOH%1.ZPVTIPVMETFUA%1.TFUUJOHUPUIFPVUEPPSVOJU
If DPM model is not set, communication error may occur.
8IJMFUIFPVUEPPSVOJUJTUSBDLJOHUIFJOEPPSVOJUGPSPOFNJOVUFBGUFSUIFQPXFSTVQQMZJTUVSOFEPOUIFPQFSBUJPONBZ
stop if the remote control reception signal of the installed indoor unit is dierent.
t 5IFMFBLUFTUTIPVMECFQFSGPSNFEGPSNPSFUIBOIPVSTBUMFBTU
t 0OMZJO$PPMNPEFZPVDBODIFDLUIFDPSSFDUPQFSBUJPOPGUIFESBJO
pump.
t 8IFOUIFøPBUTXJUDIJTOPUEFUFDUFEEVFUPJOTVóDJFOUXBUFSPOUIFESBJOCPBSEUIFESBJOQVNQXJMMOPUXPSL
t *GQPXFSTVQQMZJTEJSFDUMZDPOOFDUFEUP-/UFSNJOBMDPNNVOJDBUJPOFSSPSNFTTBHFNJHIUBQQFBS
t "GUFSDPNQMFUJOHUIFESBJOBHFDIFDLUVSOUIFVOJUPòBOEEJTDPOOFDUUIFQPXFSTVQQMZ
t 3FBTTFNCMFUIFDPOUSPMCPYDPWFS
15
ENGLISH
Connecting the connection cord
t "MXBZTSFNFNCFSUPDPOOFDUUIFSFGSJHFSBOUQJQFTCFGPSFQFSGPSNJOHUIFFMFDUSJDDPOOFDUJPOT
8IFOEJTDPOOFDUJOHUIFTZTUFNBMXBZTEJTDPOOFDUUIFFMFDUSJDDBCMFTCFGPSFEJTDPOOFDUJOHUIFSFGSJHFSBOUQJQFT
t "MXBZTSFNFNCFSUPDPOOFDUUIFBJSDPOEJUJPOFSUPUIFHSPVOEJOHTZTUFNCFGPSFQFSGPSNJOH
the electric connections.
The indoor unit is powered by the outdoor unit by means of a H07 RN-F connection cable (or a more power model),
with insulation in synthetic rubber and jacket in polychloroprene(neoprene), in accordance with the requirements of standard EN 60335-2-40.
1. Remove the screw on the electrical component box and remove the cover plate.
2. Route the connection cord through the side of the indoor unit and connect the cable to terminals; refer to the gure below.
3. Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4. Reassemble the electrical component box cover, carefully tightening the screw.
Indoor Power supply
Communication Cable
Power Supply .BY.JO7
Indoor Power cable
7_)[ 
_NN¤XJSFT
_NN¤XJSFT
J Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation
*&$*&$$&/&-&$)3/'PS*&$*&$$&/&-&$)3/'
J 4DSFXTPOUFSNJOBMCMPDLNVTUOPUCFVOTDSFXFEXJUIUIFUPSRVFMFTTUIBOLHGtDN
J 4JODFJUIBTUIFFYUFSOBMQPXFSTVQQMZSFGFSUPUIFPVUEPPSVOJUJOTUBMMBUJPONBOVBMGPS."*/108&3
Wiring diagram
1 phase 3 phase
1(L) 2(N)
N
L
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
F2F1
*OEPPS6OJU
Main power cable
Cable clamp
Indoor Power
Communication cable
1(L)
1(L)
F2
F1
2(N)
2(N)
*OEPPS6OJU
F2
F1
Cable clamp
Indoor Power
Communication cable
Cable tie
1IBTF8JSFT
power cable
"$7
Cable tie
Between Indoor and Outdoor Connection cable Specications(Common in use)
Terminal Block SPEC (Indoor)
8IFOJOTUBMMJOHUIFJOEPPSVOJUJOBDPNQVUFSSPPNVTFUIF
double shielded(Tape aluminum / polyester braid + copper)
cable of FROHH2R type.
"$108&3.4$3&8
11 13
$0..6/*$"5*0/.4$3&8
 9.0
13.8
18
5JHIUFOJOH5PSRVFLHGtDN
M3.5 8.0~12.0
M4 12.0~18.0
J
/·m = 10 kgf·cm
16
Installation Procedure
How to connect your extended power cables
1. Prepare the following tools.
Tools Crimping pliers
$POOFDUJPOTMFFWF
(mm)
Insulation tape Contraction tube (mm)
Spec .) 20xØ6.5(HxOD) 8JEUINN Y-Y0%
Shape
2. "TTIPXOJOUIFöHVSFQFFMPòUIFTIJFMETGSPNUIFSVCCFSBOEXJSFPG
the power cable.
- 1FFMPòNNPGDBCMFTIJFMETGSPNUIFQSFJOTUBMMFEUVCF
CAUTION
t "GUFSQFFMJOHPòUIFUVCFXJSFZPVNVTUJOTFSUBDPOUSBDUJPO
tube.
t 'PSJOGPSNBUJPOBCPVUUIFQPXFSDBCMFTQFDJöDBUJPOTGPS
indoor and outdoor units, refer to the installation manual.
6OJUNN
Power cable
3. Insert both sides of core wire of the power cable into the connection
TMFFWF
f Method 1
1VTIUIFDPSFXJSFJOUPUIFTMFFWFGSPNCPUITJEFT
$POOFDUJPOTMFFWF
f Method 2
5XJTUUIFXJSFDPSFTUPHFUIFSBOEQVTIJUJOUPUIFTMFFWF
$POOFDUJPOTMFFWF
4. 6TJOHBDSJNQJOHUPPMDPNQSFTTUIFUXPQPJOUTBOEøJQJUPWFSBOEDPNQSFTTBOPUIFSUXPQPJOUTJOUIFTBNF
location.
- The compression dimension should be 8.0.
- "GUFSDPNQSFTTJOHJUQVMMCPUITJEFTPGUIFXJSFUPNBLFTVSFJUJTöSNMZQSFTTFE
Compression
dimension
f Method 1
Compress it 4 times.
5 mm
f Method 2
Compress it 4 times.
5 mm
17
ENGLISH
5. 8SBQJUXJUIUIFJOTVMBUJPOUBQFUXJDFPSNPSFBOEQPTJUJPOZPVSDPOUSBDUJPOUVCFJOUIFNJEEMFPGUIFJOTVMB
tion tape.
"UPUBMPGUISFFPSNPSFMBZFSTPGJOTVMBUJPOJTSFRVJSFE
f Method 1
40 mm
Insulation tape
f Method 2
Insulation tape
35 mm
6. "QQMZIFBUUPUIFDPOUSBDUJPOUVCFUPDPOUSBDUJU
Contraction tube
 "GUFSUVCFDPOUSBDUJPOXPSLJTDPNQMFUFEXSBQJUXJUIUIFJOTVMBUJPOUBQFUPöOJTI
CAUTION
t Make sure that the connection parts are not exposed to outside.
t #FTVSFUPVTFJOTVMBUJPOUBQFBOEBDPOUSBDUJPOUVCFNBEFPGBQQSPWFESFJOGPSDFEJOTVMBUJOHNBUFSJBMT
UIBUIBWFUIFTBNFMFWFMPGXJUITUBOEWPMUBHFXJUIUIFQPXFSDBCMF$PNQMZXJUIUIFMPDBMSFHVMBUJPOT
on extensions.)
Insulation tape
t *ODBTFPGFYUFOEJOHUIFFMFDUSJDXJSFQMFBTF%0/05VTFBSPVOETIBQFE1SFTTJOHTPDLFU
- *ODPNQMFUFXJSFDPOOFDUJPOTDBODBVTFFMFDUSJDTIPDLPSBöSF
WARNING
AA
18
Step 1. Entering mode to set option
1. 3FNPWFCBUUFSJFTGSPNUIFSFNPUFDPOUSPMMFS
2. *OTFSUCBUUFSJFTBOEFOUFSUIFPQUJPOTFUUJOHNPEFXIJMFQSFTTJOH)JHI5FNQCVUUPOBOE-PX5FNQCVUUPO
3. $IFDLJGZPVIBWFFOUFSFEUIFPQUJPOTFUUJOHTUBUVT
Step 2. The procedure of option setting
"GUFSFOUFSJOHUIFPQUJPOTFUUJOHTUBUVTTFMFDUUIFPQUJPOBTMJTUFECFMPX
0QUJPOTFUUJOHJTBWBJMBCMFGSPN4&(UP4&(
t 4&(4&(4&(4&(BSFOPUTFUBTQBHFPQUJPO
t 4FUUIF4&(_4&(4&(_4&(BT0/TUBUVTBOE4&(_4&(_BT0''TUBUVT
4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&(
0XXXXX1XXXXX
4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&( 4&(
2XXXXX3XXXXX
The procedure of setting option
Setting an indoor unit address and installation option
X
Set the indoor unit address and installation option with remote controller option.
4FUUIFFBDIPQUJPOTFQBSBUFMZTJODFZPVDBOOPUTFUUIF"%%3&44TFUUJOHBOEJOEPPSVOJUJOTUBMMBUJPOTFUUJOHPQUJPOBUUIF
TBNFUJNF:PVOFFEUPTFUUXJDFXIFOTFUUJOHJOEPPSVOJUBEESFTTBOEJOTUBMMBUJPOPQUJPO
0O4&(_ 0ò4&(_
J The display of the remote controller may be different depending on the model.
High Temp
Button
High Fan Button
Mode change
-PX5FNQ
Button
-PX'BO#VUUPO
Entering mode for
setting option
Option setting
mode
MR-DC00, MR-DH00
High Temp
Button
High Fan Button
Mode change
-PX5FNQ
Button
-PX'BO#VUUPO
Entering mode for
setting option
Option setting
mode
MR-EC00, MR-EH00
19
ENGLISH
Option setting 4UBUVTW
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
2. Setting Cool mode
1SFTT.PEFCVUUPOUPCFDIBOHFEUP$PPMNPEFJOUIF0/TUBUVT
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
4. Setting Dry mode
1SFTT.PEFCVUUPOUPCFDIBOHFEUP%3:NPEFJOUIF0/TUBUVT
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
6. Setting Fan mode
1SFTT.PEFCVUUPOUPCFDIBOHFEUP'"/NPEFJOUIF0/TUBUVT
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
8. Setting Heat mode
1SFTT.PEFCVUUPOUPCFDIBOHFEUP)&"5NPEFJOUIF0/TUBUVT
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
4FUUJOH"VUPNPEF
1SFTT.PEFCVUUPOUPCFDIBOHFEUP"650NPEFJOUIF0''TUBUVT
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
4&( 4&(
4&(
4&(
4&(
4&(
4&(
4&(
4&(
4&(
4&(
4&(
20
Setting an indoor unit address and installation option
Option setting Status
12. Setting Cool mode
Press Mode button to be change to Cool mode in the OFF status.
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
14. Setting Dry mode
Press Mode button to be change to Dry mode in the OFF status.
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
16. Setting Fan mode
Press Mode button to be change to Fan mode in the OFF status.
4FUUJOH4&(4&(PQUJPO
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
18. Setting Heat mode
1SFTT.PEFCVUUPOUPCFDIBOHFUP)&"5NPEFJOUIF0''TUBUVT
4FUUJOH4&(4&(NPEF
1SFTT-PX'BOCVUUPO
UPFOUFS4&(WBMVF
Press High Fan button(
UPFOUFS4&(WBMVF
&BDIUJNFZPVQSFTTUIFCVUUPO
will be selected in rotation.
4&(
4&(
4&(
4&(
4&(
4&(
4&(
4&(
Step 4. Input option
Press operation button
with the direction of remote control for set.
For the correct option setting, you must input the option twice.
Step 5. Check operation
3FTFUUIFJOEPPSVOJUCZQSFTTJOHUIF3&4&5CVUUPOPGJOEPPSVOJUPSPVUEPPSVOJU
2. Take the batteries out of the remote controller and insert them again and then press the operation button.
Step 3. Check the option you have set
"GUFSTetting option, press
button to check whether the option code you input is correct or not.
¤
¤
¤
¤
¤
¤
¤
¤
¤
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Samsung NS1254DXEA User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI